In this field, define the delay in seconds for the Answer Timeout. 
The delay can be set between 1 and 10 seconds. 
 

Interval between Requests: 

In  this  field,  define  the  delay  between  the  scan  commands  sent  to  the  IP  device.  The  delay  can  be  set 
between 30 and 65535 seconds. 
 

Number of unsuccessful Requests before Action: 

In this field, define the number of Port scanning commands to be sent to the IP device before executing the 
actions. 
The number can be set between 1 and 65535 seconds. 
 

Delay before First Request after Action: 

In this field, define the time in seconds before restarting the monitoring after the reboot action. The delay can 
be set between 30 and 65535 seconds. 
 

Maximum Number of Actions 

You can limit the number of times the action can be be executed. This option is useful to limit the number of 
times a server can be rebooted. In this field, define the number of times the rule can be executed. 
The delay can be set between 0 and 255 seconds. Default is 0 and means that the action can be performed 
continuously. 
 

Configuring the Actions 

For the Event defined above, you can choose and configure following actions: 
 

Set Outputs 

This type of Action only appears if: 
- your Device has own Power Outlets or has access to Power Outlets of connected xBus Peripheral 
Units 
- your Device has access to Relay Outputs of connected xBus Peripheral Units 
- you have created interface associations (Go to Settings/Associations). 

 
Select this checkbox and choose in the corresponding drop-down lists the Output to use for this Rule. 
Each Power Outlet can be switched to On, Off or Restarted. 
If you choose "Restart" you can also define a Restart delay between 0 and 3600 seconds. 
-  If  you  choose  0  second  for  the  delay,  the  delay  will  be  the  delay  defined  in  the  Peripherals  page  (goto 
Settings/Peripherals/Edit). 
- If you choose a delay different from 0, this delay will replace the delay defined in the Peripherals page (goto 
Settings/Peripherals/Edit). 
Each Relay Output can be switched to Open, Close, Pulse Open, Pulse Close. 
If you choose Pulse open or Pulse close you can also define a delay between 0 and 3600 seconds. 
-  If  you  choose  0  second  for  the  delay,  the  delay  will  be  the  delay  defined  in  the  Peripherals  page  (goto 
Settings/Peripherals/Edit). 
-  If  you  choose  a  delay  different  from  0,  this  delay  will  replace  the  delay  defined  Peripherals  page  (goto 
Settings/Peripherals/Edit).  

 

Rule to cancel 

This type of Action only appears if you already have created a Rule which you want to cancel 
Select this checkbox and choose in the corresponding drop-down lists the Rule you want to cancel. 
 

Send Magic to 

Your Device has the possibility to send a Magic Word over IP to another Device in order to remotely trigger 
an action. 
-  Send  magic:  specify  the  Magic  Word  to  use,  it  can  be  from  1  to  32  characters  long,  and  can  contain 
alphanumeric characters.  
- to: specify the IP address of the destination device 
- port: specify the Port number used to send the Magic Word, default port number is 52389 
 

Send Syslog Message 

This type of Action can only be configured if you have already specified at least one destination 
Syslog Server (Go to General/Log Settings Page). 

Check this box if you want to send a message to a Syslog server. In the following drop-down lists choose the 
facility and the severity of the message to send. 
 

Содержание EPC 4 IEC

Страница 1: ...User Guide ePowerSwitch 4 IEC R2 www neol com...

Страница 2: ...ol S A S This documentation the ePowerSwitch 4IEC its peripherals accessories and accompanying software were produced with great care yet errors are possible Neol S A S assumes no responsibility for e...

Страница 3: ...Hidden Page account 17 Settings Groups 20 Settings Peripherals ePowerSwitch 4IEC 21 Settings Rules 23 Settings Rules Schedule Rule 25 Settings Rules Timer Rule 28 Settings Rules Ping Monitoring Rule 3...

Страница 4: ...ePowerSwitch Ger t berschreiten Die ePowerSwitch Ger te sind nur f r den Innengebrauch bestimmt und d rfen nicht in feuchten oder berm ig hei en Umgebungen eingesetzt werden Vor nderungen oder Eingrif...

Страница 5: ...atedly power on but not ready 2 times repeatedly waiting on IP address from DHCP server 4 times repeatedly System error contact the manufacturer Network RJ45 Connector Auto Sensing 10 100 Mbits sec Et...

Страница 6: ...riated three wire power cords two poles plus ground to connect your electrical devices to the ePowerSwitch 4IEC unit 3 Plug the power cable into a grounded socket The Power LEDs light on to confirm th...

Страница 7: ...ameters are not compatible with those of your PC 1 Start the Finder exe program contained on the CD ROM 2 Open the File menu and choose SCAN or click on the first left button in the tool bar to discov...

Страница 8: ...suggest to disable the Finder program after the first configuration Chapter 2 Configuration through an RS232 Terminal connection 1 Use the provided RS232 cable to connect the ePowerSwitch 4IEC to an a...

Страница 9: ...low control If you use the Micro Terminal program on the CD folder miscellaneous you only have to choose the used serial port this program is already configured at 9600 n 8 1 4 On your computer press...

Страница 10: ...ion Protocol requires a DHCP host to be set up on the network IP Address IP address of the ePowerSwitch 4IEC default is 192 168 100 200 Subnet Mask Subnet Mask of the ePowerSwitch 4IEC default is 255...

Страница 11: ...he IP address of the timeserver you wish to use in the Primary field The address of a second timeserver can be specified in the Secondary field The secondary timeserver is optional and is used only if...

Страница 12: ...om The name can be from 1 to 64 characters long and can contain alphanumeric characters This should be a valid address generally servers reject messages that don t have a valid from address Authentica...

Страница 13: ...eric characters Default name is location Read Community In this field enter the name you want to give to the Read Community field The name can be from 1 to 64 characters long and can contain alphanume...

Страница 14: ...The Trigger function must be activated on both the emitter device your Device and the target Device Trigger Port Port number used by the Trigger function default is 52389 The Trigger function must be...

Страница 15: ...and at least one DNS Server on the Network Settings Page General IP Configuration page Secondary Syslog Server In this field you can define the IP Address of a secondary Syslog Server You can enter e...

Страница 16: ...C Save Click this button to save the current system settings onto your local hard drive Load Click this button and select a settings file you want to download to the ePowerSwitch 4IEC Restore Click th...

Страница 17: ...he Account It enables to deactivate temporarily this account while keeping all its settings for a later use User Name In this field enter the name you want to give to the user The name can be from 1 t...

Страница 18: ...art specified power outlets Buttons ON and OFF do no longer appear This function is very helpful if you have to restart the router used to access to your Power Switch It avoids to switch the router Of...

Страница 19: ...e it go to the Settings Groups page Device In this drop down list choose the device from which one you want to add Inputs or Outputs to the current account Only properly connected devices or devices w...

Страница 20: ...ge 21 Jul 2011 02 29 01 Version 2 3 0 0 M0 O1 On M0 O2 On M0 O3 On M0 O4 On Each Power Outlet support individually 3 commands On Off and Restart using following syntax M0 Ox ON OFF RESTART M0 ID of yo...

Страница 21: ...an ID Code to clearly identify each group of power outlets All the ID Codes used to identify groups start with the letter G Group Name In this field enter the name you want to give to the selected gr...

Страница 22: ...anumeric characters Do not use quotes or special characters in labels Activated This check box must be checked to activate the device and enables to deactivate it temporarily while keeping all its set...

Страница 23: ...tomatically creates an ID Code to clearly identify the Shutdown Function SD1 identifies the Shutdown Function 1 Create a new Shutdown Association Click on this button to create a new Shutdown Associat...

Страница 24: ...over SNMP or a Syslog message at regular interval during a given time 2 Timer Rule This rule can be used to trigger user specified actions according to a defined time table This rule can be used to s...

Страница 25: ...ripherals and to trigger different actions when an xBus Peripheral is disconnected cable disconnected or broken or connected again 9 Trigger Rule This Rule is used to send a request over the Internet...

Страница 26: ...to 32 If you delete a rule in the middle of the Rule list the number of this rule will only be used again if no other rule is available Rule Name In this field enter the name you want to give to the...

Страница 27: ...als Edit If you choose a delay different from 0 this delay will replace the delay defined in the Peripherals page goto Settings Peripherals Edit Each Relay Output can be switched to Open Close Pulse O...

Страница 28: ...r General Log Settings Page or one destination SNMP Server Goto General SNMP Page Up to 255 characters may be entered in this free text field The text will appear in the Syslog the Trap and the emails...

Страница 29: ...32 characters long and can contain alphanumeric characters Do not use quotes or special characters in labels Rule Color In this field select one of the 48 standard colours you want to use to highligh...

Страница 30: ...etween 0 and 3600 seconds If you choose 0 second for the delay the delay will be the delay defined in the Power Outlets Page If you choose a delay different from 0 this delay will replace the delay de...

Страница 31: ...the Rule list the number of this rule will only be used again if no other rule is available Rule Name In this field enter the name you want to give to the rule The name can be from 1 to 32 characters...

Страница 32: ...0 second for the delay the delay will be the delay defined in the Peripherals page goto Settings Peripherals Edit If you choose a delay different from 0 this delay will replace the delay defined in t...

Страница 33: ...at least one destination Syslog Server General Log Settings Page or one destination SNMP Server Goto General SNMP Page Up to 255 characters may be entered in this free text field The text will appear...

Страница 34: ...f the Rule list the number of this rule will only be used again if no other rule is available Rule Name In this field enter the name you want to give to the rule The name can be from 1 to 32 character...

Страница 35: ...an be switched to On Off or Restarted If you choose Restart you can also define a Restart delay between 0 and 3600 seconds If you choose 0 second for the delay the delay will be the delay defined in t...

Страница 36: ...at least one destination Syslog Server General Log Settings Page or one destination SNMP Server Goto General SNMP Page Up to 255 characters may be entered in this free text field The text will appear...

Страница 37: ...y for the rule in the Rule Panel page Go to Misc Rule Panel if the rule is triggered Rule Type In this Drop Down list choose Analog Input Monitoring Rule Rules are used to control Actions according to...

Страница 38: ...estart you can also define a Restart delay between 0 and 3600 seconds If you choose 0 second for the delay the delay will be the delay defined in the Peripherals page goto Settings Peripherals Edit If...

Страница 39: ...one destination Syslog Server General Log Settings Page or one destination SNMP Server Goto General SNMP Page Up to 255 characters may be entered in this free text field The text will appear in the S...

Страница 40: ...to give to the Rule The name can be from 1 to 32 characters long and can contain alphanumeric characters Rule Color In this Drop Down Color Picker choose the color you want to apply for the rule in th...

Страница 41: ...the Port number used to send the Magic Word default port number is 52389 Send Syslog Message This type of Action can only be configured if you have already specified at least one destination Syslog Se...

Страница 42: ...roup of Power Outlets an RS232 interface and the MAC address of a Server To remove an existing Association click on the corresponding Delete button To modify an Association click on the corresponding...

Страница 43: ...n this field enter the MAC address of the PC you want to associate on the Wake Up on LAN function Shutdown Activated This check box must be checked to activate the function and enables to deactivate i...

Страница 44: ...d or have been connected to the ePowerSwitch 4IEC At a glance the administrator can check the status of the power supplies of the ePowerSwitch 4IEC and the connected Peripherals He can also check the...

Страница 45: ...only some specific rules In the example below the user Bill has the possibility to supervise 2 rules and to see on a glance the rules which have been triggered The page is automatically refreshed ever...

Страница 46: ...perature humidity ambient light display the status of all digital inputs If you log in as a user ePowerSwitch 4IEC handles up to 40 accounts you will be able to control individually all the power outl...

Страница 47: ...S HTTP Port is 80 Finder program is enabled HTTP config is enabled Press M to modify these settings Syntax of the command line P0y z the command line MUST start with a slash Parameter Value Function y...

Страница 48: ...uct to update MUST be accessible using a browser by the PC used for the Update Please check before trying to update your product It is NOT possible to update products using an old hardware Firmware 2...

Страница 49: ...he state of the D1 door contact of the DIM1 Digital Input Module the administrator could add following line in the Syslog Trap Message text area Door contact status is DIM1 DI1 The schedule rule can b...

Страница 50: ...onnection RS232 SUB D 9 female Operating temperature 0 C to 50 C Operating humidity 10 to 80 RH not condensing Dimensions LxDxH 478 x 42 x 62 mm Weight 1 3 kg Approvals CE EN55022 EN55024 Commonly use...

Страница 51: ...e number restored Power Supply B of Satellite number restored Rule number Outlet number of Master has been switched ON Rule number Group number has been switched ON Rule number Dry Contact Output numb...

Страница 52: ...51 STATEMENT OF CONFORMITY All modifications reserved 13Sep2017...

Отзывы: