After programming the stroke end positions, it is recommended to check the opening and 
closing of the window a few times. In the case of error, the programming can be repeated 
to  achieve  the  desired  stroke.  If  you  need  to  perform  the 
instructions given above. 

12.3.  Overlap acquisition

The operation that must be carried out to acquire the overlap (after the 
has already been executed) is described below:

-  The  steps  for  installing  the  actuator/s  on  the  window  and  the  electrical  connections 

have already been explained (see § 10 and 

-  Use the controls to open the window a few centimetres

-  Use the controls to close the window up to the stroke end

-  When the window is completely closed, if acquisition of the overlap is successful, the 

actuator will display an orange flashing light for 3 seconds

 

 

IMPORTANT: 

If,  for  any reason, the  actuator  fails to complete the  closure of 

the  window  correctly,  stopping  before  finishing  the  stroke,  the 
overlap acquisition operation will have to be repeated in that order, until the 
procedure is completed correctly

12.4.  LED Light signals 

If  there  are  any  problems  during  installation  or  operation  of  the  machines,  consult  the 
possible causes listed below: 

The LED can be seen on the cap that conceals the dip
gear reducer, and has three colours

 

R

ED

, indicates an error or malfunction

 

G

REEN

, operation is OK

 

O

RANGE

, wait: functions in progress

 

 
 

17 

After programming the stroke end positions, it is recommended to check the opening and 
closing of the window a few times. In the case of error, the programming can be repeated 
to  achieve  the  desired  stroke.  If  you  need  to  perform  the 

R

ESET

Overlap acquisition 

The operation that must be carried out to acquire the overlap (after the 
has already been executed) is described below: 

The  steps  for  installing  the  actuator/s  on  the  window  and  the  electrical  connections 
have already been explained (see § 10 and 11). 

Use the controls to open the window a few centimetres. 

Use the controls to close the window up to the stroke end. 

indow is completely closed, if acquisition of the overlap is successful, the 

actuator will display an orange flashing light for 3 seconds. 

If,  for  any reason, the  actuator  fails to complete the  closure of 

the  window  correctly,  stopping  before  finishing  the  stroke,  the 
overlap acquisition operation will have to be repeated in that order, until the 
procedure is completed correctly 

 

If  there  are  any  problems  during  installation  or  operation  of  the  machines,  consult  the 

 

The LED can be seen on the cap that conceals the dip-switch, positioned to the left of the 

olours: 

, indicates an error or malfunction; 

, operation is OK;  

, wait: functions in progress. 

 
 
 

After programming the stroke end positions, it is recommended to check the opening and 
closing of the window a few times. In the case of error, the programming can be repeated 

ESET

  procedure,  see  the 

The operation that must be carried out to acquire the overlap (after the 

RESET

 procedure 

The  steps  for  installing  the  actuator/s  on  the  window  and  the  electrical  connections 

indow is completely closed, if acquisition of the overlap is successful, the 

If,  for any reason, the  actuator  fails to complete the  closure of 

the  window  correctly,  stopping  before  finishing  the  stroke,  the 

RESET

  and 

overlap acquisition operation will have to be repeated in that order, until the 

If  there  are  any  problems  during  installation  or  operation  of  the  machines,  consult  the 

switch, positioned to the left of the 

18 

WITH RED LED

 

Number 

of 

Flashes

 

Type of Error

 

Possible Solution

 

Current error: 

The actuator has detected an 

overcurrent in the motor. 

Check that there are no obstacles preventing 

the actuator from completing its stroke. Check 

that the actuator is installed correctly. 

Communication error: 

Communication between the 

devices is interrupted, or the 

devices being used have 

undergone the 

R

ESET

 

procedure 

separately 

Check the condition of the connection cables, 

and repeat the 

R

ESET

 

procedure if necessary. 

Electro-lock error 

Check the electro-lock. See the relevant 

manual  

Discordant internal setting: 

The internal setting of the actuators 

is discordant. 

Repeat the

 

R

ESET 

procedure 

RESET Procedure error: 

The 

R

ESET

 

procedure was not 

completed successfully or was 

interrupted. 

Repeat the

 

R

ESET 

procedure 

Wiring error: 

The power supply cables of the 

devices configured in Syncro³ are 

inverted. 

Check and correct the wiring. 

Encoder error:

 

The internal encoder had a 

counting error 

Repeat the

 

R

ESET 

procedure 

Electric power supply error: 

The power supply voltage is outside 

the permitted range or is unstable. 

Check the electrical contacts at the ends of the 

actuator cable and ensure that the power 

supply is correct. 

Alignment error: 

The rack position displacement of 

the actuators connected in Syncro 

is beyond the permitted maximum. 

Repeat the

 

R

ESET 

procedure 

10 

Memory error: 

The internal memory write process 

failed. 

Repeat the

 

R

ESET 

procedure 

11 

Connection error: 

A RESET procedure is being 

started with actuators different than 

Syncro³ 

Check the type of actuators chosen for the 

system.

 

Repeat the

 

R

ESET 

procedure 

 

WITH GREEN LED

 

LED Status 

Meaning 

STEADY-ON 

Device powered correctly. 
The device has correctly performed a return stroke and is completing the 
operation by memorising the position, or is currently in movement. 

FLASHING 

Device correctly powered. The device has successfully performed an 
outward stroke. The number of flashes indicates the number previously 
assigned to the device during the 

R

ESET

 

procedure 

 

 

Содержание SKYRO 650

Страница 1: ...performed periodically by qualified personnel from a service centre authorised by the manufacturer Do not use if repair or adjustment is required CAUTION if the power cable is damaged it must be repla...

Страница 2: ...nsory or mental capabilities or lacking experience and not allow children to play with the fixed controls and keep any remote out of their reach The actuator is destined exclusively for installation i...

Страница 3: ...an approved type of bipolar dead switch should be used An omnipolar general power switch with minimum distance of 3 mm between contacts should be installed upstream of the control line Application is...

Страница 4: ...sed when the window is particularly heavy or wide and a single actuator doesn t allow complete closure of the window especially in the corners therefore making it necessary to have two or more When a...

Страница 5: ...m 11000 m 15000 m These indications are for specialised technical personnel and basic work and safety All preparatory assembly and electrical connection operations must be performed by to guarantee op...

Страница 6: ...fixing screws Fig 2 C Drill holes into the frame and screw in the motor support bracket making sure that all screws are fitted tightly Fig 3 and Fig 3bis 12 D Line up the front bracket along the centr...

Страница 7: ...rip windows It should be noted that up to a maximum of 8 Syncro actuators 4 for 230V can be fitted with various rod solutions for One motor 1 rod connection bar in tandem Appliances are equipped with...

Страница 8: ...e gives a flashing orange signal to indicate completion of the RESET procedure Each device will give a different number of flashes to indicate that the access code is received actuator 1 flash pause a...

Страница 9: ...ess After programming the stroke end positions it is recommended to check the opening and closing of the window a few times In the case of error the programming can be repeated ESET procedure see the...

Страница 10: ...hand and pull the pivot screw out of the hole this operation should be performed with the window open at least 10 cm to facilitate the screw Manually open the window frame DANGER the window could fall...

Страница 11: ...tional to its importance Inoltre i succitati prodotti sono conformi alle disposizioni pertinenti delle seguenti Direttive Furthermore the products listed above complies with the provisions of followin...

Страница 12: ...23 24 NEKOS S r l Via Capitoni 7 5 36064 Colceresa VI ITALY 39 0424 411011 39 0424 411013 www nekos it info nekos it...

Отзывы: