11
Fastening on wooden window frames: Ø4 self-threading wood screws
(2 pieces
for recessed mounting and 4 pieces for surface mounting)
, with an appropriate
length for the type of window frame.
Fastening on PVC window frames: Ø3.9x13 self-threading metal screws
(2
pieces for recessed mounting and 4 pieces for surface mounting)
, with an
appropriate length for the type of window frame.
Equipment and tools: tape-measure, pencil, drill/electric screwdriver, set of drill
bits for metal, insert for screwing in, electrician's scissors, screwdrivers.
10. Programming the actuator
10.1.
Opening stroke-end
The opening stroke-end of the actuator can be adjusted by selecting the dip-
switches located inside the actuator underneath the black rubber plug (T)
(see fig.
below)
, near the label that indicates the state of the dip-switches.
The setting can be made very easily by selecting the dip-switches as specified in the
table below.
STROKE
(mm)
DIP-SWITCH
WITHOUT
BK-LOCK
WITH
BK-LOCK
1
2
3
4
4
70
ON
OFF
OFF
OFF
ON
125
OFF
ON
OFF
170
OFF
OFF
ON
210
OFF
OFF
OFF
The actuator is factory-set with the longest stroke (210 mm).
10.2.
Closure stroke-end
The stroke-end at closure is automatic and cannot be programmed.
The actuator stops when the charge is absorbed when the window is completely
closed and the weather stripping is completely depressed.
After each closure or intervention of electronic protection devices, the chain will
move about 1 mm in the opposite direction to give correct compression to the seals
and release the mechanical parts.
10.3.
Operation with
The actuator can also work in combination with the
lock; this operating mode can be selected using dip
set on ON without the lock being connected, the actuator will not move.
11. Actuator kit with electromechanical lock
Warning
. Always comply with the corr
the two machines; an incorrect connection may damage the machines and
create a hazardous situation.
11.1.
Electrical connection and operating logic
In order for the two machines to work in combination with one another, the
connection must be made by connecting the wires according to the following
diagram.
-
In the BK-LOCK electromechanical lock select, using dip
stroke and set, using dip-switch No. 2, the “
instructions in the BK-LOCK
Power the two machines with a voltage of 24V
inverting the polarity to open and close the system.
Powering Black wire with +24V
effects:
the lock moves in the opening direction;
the lock arrives at stroke
the chain actuator begins opening, opening the movable sash;
the KIMO chain actuator reaches stroke
Powering Red wire with +24V
effects:
the chain actuator moves in the closing direction;
the actuator reaches stroke
12
Operation with BK-LOCK electromechanical lock
The actuator can also work in combination with the BK-LOCK
lock; this operating mode can be selected using dip-switch No.4. If the dip
set on ON without the lock being connected, the actuator will not move.
Actuator kit with electromechanical lock
. Always comply with the correct electrical connections between
the two machines; an incorrect connection may damage the machines and
create a hazardous situation.
Electrical connection and operating logic
In order for the two machines to work in combination with one another, the
connection must be made by connecting the wires according to the following
- +
24
V
3
1
2
1
2
3
24V
electromechanical lock select, using dip-switch No. 1, the desired
switch No. 2, the “
OPERATION WITH ACTUATOR
LOCK manual also)
.
Power the two machines with a voltage of 24V
(Red wire and
inverting the polarity to open and close the system.
with +24V
and Red wire with -24V
produces the following
the lock moves in the opening direction;
the lock arrives at stroke-end, stop;
the chain actuator begins opening, opening the movable sash;
the KIMO chain actuator reaches stroke-end.
re with +24V
and Black wire with -24V
produces the following
the chain actuator moves in the closing direction;
the actuator reaches stroke-end and stops with a short relax;
electromechanical lock
LOCK electromechanical
switch No.4. If the dip-switch is
set on ON without the lock being connected, the actuator will not move.
ect electrical connections between
the two machines; an incorrect connection may damage the machines and
In order for the two machines to work in combination with one another, the required
connection must be made by connecting the wires according to the following
switch No. 1, the desired
ATION WITH ACTUATOR
” mode
(see
wire and Black wire),
produces the following
the chain actuator begins opening, opening the movable sash;
produces the following
end and stops with a short relax;