measure the total load connected to the circuit and compare to its ratings. Transfer any load in
excess of the device ratings to another circuit.
Keep in mind that turning off the circuit and reconnecting appliances, equipment and
components may temporarily clear an arc that may not reappear or may appear some time after
the circuit and loads are re-energized.
If there is no clear indication of any problems with an AFCI, GFCI, fixed wiring or appliances,
replace the AFCI or GFCI. If the new device does not trip, the previous device was damaged or
deteriorated. If the new device trips, troubleshoot the fixed wiring and appliances, correct
deficiencies, and test AFCIs and GFCIs in accordance with Section 5.