FlexPAK
5.2 Simple TVFD Valve Settings
5.2.1 Hardware
Simple TVFD Valve controlled by the V11 TVFD (SLV) Solenoid Lower Valve and the V12 TVFD (SUV) Solenoid
Upper Valve.
5.2.2 PLC Settings
1 Presep (Softkey) = Off (standard setting).
2 AEB-TVFD (Softkey) =Off (standard setting=On).
3 TVFDAdv (Softkey) = Off (standard setting).
Presep overrides 2 above.
If TVFDAdv is activated (Switch = On), TVFDAdv overrides 1 and 2 above.
5.2.3 Timer Settings
BinOpnTm
TL = Delay after the upper slide starts to close before the lower slide starts to open. The default is 5 seconds.
TH = Emptying Time. The default is 5 seconds.
PresepTm
TL = Delay after the lower slide starts to close before the upper slide starts to open. The default is 5 seconds.
TH = Time delay to the next possible emptying sequence. The default is 5 seconds.
5.3 Pre-Separator Settings
5.3.1 Hardware
• Pre-Separator 1 controlled by the V11 TVFD (SLV) Solenoid Lower Valve.
• Pre-Separator 2 controlled by the V12 TVFD (SUV) Solenoid Upper Valve.
5.3.2 PLC Settings
1 Presep (Softkey) = On (standard setting=Off)
2 AEB-TVFD (Softkey) =Off (standard setting=On)
3 TVFDAdv (Softkey) = Off (standard setting)
Presep overrides 2 above.
If TVFDAdv is activated (Switch = On), TVFDAdv overrides 1 and 2 above.
5.3.3 Timer settings: Pre-Separator 1
BinOpnTm
TL = Delay before Pre-Separator 1 starts bin emptying. The default is 5 seconds.
TH = Emptying Time. The default is 5 seconds.
5.3.4 Timer settings: Pre-Separator 2
PresepTm
TL = Delay after Pre-Separator 1 starts to close before Pre-Separator 2 starts to open.
TH = Emptying Time. Default 5 second
47