background image

 

 

 

  

OWNER’S MANUAL  

 

MODEL MULTI-FLEX

 

INTRODUCTION 

SPECIFICATIONS 

 UNPACKING 

 INSTALLATION 

 ELECTRICAL 

 OPERATION 

 MAINTENANCE 

 TROUBLESHOOTING 

 REPLACEMENT PARTS 

 MOTOR TROUBLE GUIDE 

***IMPORTANT***

 

THIS  MANUAL  CONTAINS  PRECAUTIONARY  STATEMENTS  RELATING  TO  WORKER  SAFETY.   READ  AND  SAVE

 

THIS MANUAL COMPLETELY AND COMPLY AS DIRECTED.   ALL THE POTENTIAL HAZARDS OF DUST AND MIST 
CONTROL  SYSTEMS  AND  EQUIPMENT  ARE  IMPOSSIBLE  TO  LIST;  THEREFORE,  OBTAIN  THE  SERVICES  OF  A

 

PROFESSIONAL  INSTALLER.

 

A  FIRE  PROTECTION  EXPERT  SHOULD  BE  OBTAINED  IN  THE  EVENT  THE

 

PRODUCT IS INTENDED FOR USES WHICH PRESENT A POTENTIAL RISK OF FIRE OR FIRE PROPAGATION. REFER

 

TO  APPROPRIATE  AUTHORITIES,  AND  DISCUSS  YOUR  INTENDED  USE  WITH  A  LEV-CO  REPRESENTANT. 
WORKERS  HANDLING  EQUIPMENT  OR  SYSTEMS  SHOULD  BE  INSTRUCTED  TO  CONDUCT  THEMSELVES  IN  A 
SAFE MANNER.

 

Page: 

1/15 .

 

 

 

Содержание Multi-flex

Страница 1: ...RECTED ALL THE POTENTIAL HAZARDS OF DUST AND MIST CONTROL SYSTEMS AND EQUIPMENT ARE IMPOSSIBLE TO LIST THEREFORE OBTAIN THE SERVICES OF A PROFESSIONAL INSTALLER A FIRE PROTECTION EXPERT SHOULD BE OBTAINED IN THE EVENT THE PRODUCT IS INTENDED FOR USES WHICH PRESENT A POTENTIAL RISK OF FIRE OR FIRE PROPAGATION REFER TO APPROPRIATE AUTHORITIES AND DISCUSS YOUR INTENDED USE WITH A LEV CO REPRESENTANT ...

Страница 2: ...LTERS TO MAINTAIN WARRANTY TO ORDER SPARE PARTS CONTACT US 1050 BROCK ROAD Unit 22 24 Pickering ON CANADA L1W 3X4 Phone 905 831 7001 or 888 862 5356 Fax 905 831 7443 or 866 840 9923 E mail sales lev co com Website http www lev co com Page 2 15 ...

Страница 3: ...READ INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL OPERATE OR SERVICE YOUR MODEL MINI VAC UNIT RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE Page 3 15 ...

Страница 4: ...e hoods and dust collector should be provided so that a fire protection specialist can install extinguishing equipment You may also want to contact your insurance underwriter 4 Always disconnect unit from power source before inspecting or servicing LEV CO SETS THE STANDARD The Lev co MULTI FLEX collects dust welding smoke mist and other atmospheric pollutants in industrial plants shops schools and...

Страница 5: ...tant paint Includes side access doors dust pan door 5 casters self supporting 6 75 dia by 10 long extractor arm and ULTRA SEAL filter sealing system to prevent by pass NOISE LEVEL ELECTRICAL Standard Motor STD 78 dBA 5 68 dBA 5 with optional silencer 1 5 HP 115 208 230 1 60 17 0 8 5 A Opt 1 5 HP 208 230 460 3 60 4 9 4 6 2 3 A Opt 3 HP HP 208 230 460 575 3 60 8 0 4 0 A STD 2 HP 208 230 460 575 3 60...

Страница 6: ...or blower compartments for any packing materials and remove PREPARATION AND INSTALLATION After initial inspection for shipping damage open the cabinet and motor access door Remove all packing materials and filters to avoid damage and to facilitate the installation The installation should conform to all local ordinances associated with building and electrical codes required for the unit Authorities...

Страница 7: ...ld be performed with the unit running all filters in place and cabinet doors closed Measured motor current readings should be equal to or below motor nameplate rating These specifications can be found on the motor name plate or in the specifications section of this manual The single phase 115V AC motors supplied in the MULTI FLEX have thermal overload protection Motor rotation may be changed if re...

Страница 8: ...s will produce this result e g reverse L1 and L2 or L2 and L3 Figure 5 shows the electrical hook ups on the three phase motor Figure 5 CAUTION OTHER OPTIONS ELECTRICAL The standard Light Kit will require an additional 4 0 A at 115V AC minimum be sure to add this into the power requirements when allocating circuits for the MULTI FLEX unit The standard light will come on only when the unit is operat...

Страница 9: ...ion is noticed or on models so equipped when the optional pressure gauge indicates a restriction The optional pressure gauge is calibrated as follows With clean filters turn unit on and mark the pressure reading on the gauge see diagram included with gauge for hook up Make a second mark at 2 0 higher than initial reading i e if initial reading is 1 0 the second mark should be at 3 0 Whether using ...

Страница 10: ...1 Turn unit off and unplug from electrical circuit 2 Remove filter access panel 3 Clean or replace pre filter per above instructions 4 Release filter retaining clamps located on filter holding frame see Figure 6 5 Slide filters out of the holding frame 6 To replace reverse the procedure above HEPA FILTER on models so equipped cannot be cleaned See your distributor for replacement OTHER SERVICE Mos...

Страница 11: ... vibration noise and short bearing life and clean as necessary An occasional drop of oil on the caster wheel bearing will keep them moving freely Replacement parts are available from your Lev co distributor The following section lists replacement parts for the MULTI FLEX unit REPLACEMENT PARTS Page 11 15 ...

Страница 12: ...ors 3 Replace transformer With voltmeter check input volts and 12 volt output 4 Check circuit breaker 4 No input voltage 2 Motor won t operate 1 Motor overload 1 Too much airflow Be sure arm hose or ducts and doors are installed before running 2 Replace motor Check amps to ensure proper operation 3 Check overload reset Check magnet coil for failure 4 Check circuit breaker 2 Failed motor 3 Relay or...

Страница 13: ...LA FROM NAMEPLATE MOTOR VOLTAGE FROM NAMEPLTE ALWAYS USE LEV CO REPLACEMENT PARTS AND FILTERS TO MAINTAIN WARRANTY TO ORDER SPARE PARTS CONTACT LEV CO 1050 BROCK ROAD Unit 22 24 Pickering ON CANADA L1W 3X4 Phone 905 831 7001 or 888 862 5356 FAX 905 831 7443 or 866 840 9923 E MAIL sales lev co com INTERNET http www lev co com Page 13 15 ...

Страница 14: ...orporating overtempature thermostats should be controlled with a magnetic starter The thermostat circuit must be wired in series with the holding coil circuit as shown on tag or nameplate on motor to remove power from the starter coil if motor overheats TABLE A MINIMUM WIRE SIZES FOR THREE PHASE MOTORS Type S SO SJ SJO etc flexible cable wire sizes See NEC Article 400 for ampacity Note Above wire ...

Страница 15: ...common answers to electrical problems The information is not all inclusive and does not necessarily apply in all cases When unusual operating conditions repetitive failures or other problems occur consult an electric motor service firm for assistance Page 15 15 ...

Отзывы: