background image

FlexPAK DX

6.5 Change control filter

WARNING! Risk of personal injury

• The vacuum and compressed air to the unit

must be turned off before commencing filter

change.

• Use proper protective equipment.

Always check the main filter for damage when

replacing the control filter.

The control filter should normally be replaced after

6000 hours of operation. The control filter must also

be replaced if damaged or if there is a high-pressure

drop over the control filter.
Follow the procedure below:
1 Access the filter by removing the lid and side of

the FlexPAK DX.

2 Disconnect the top piping of the filter housing and

open the top cover.

3 Remove and put the old filter in a large plastic bag,

or wrap it in plastic foil. Avoid dust spreading.

4 Fit a new filter cartridge in place. Ensure that the

filter cartridge is centred and that the rubber seal

on the housing is intact.

5 Close the top cover and reconnect the pipes.
6 Check the earth connection between the control

filter and GND1.

6.6 Check the filter cleaning function

WARNING! Risk of personal injury

Crush hazard. Pay attention when the com-

pressed air pressure cylinder and valve disc

move. Make sure that the protection hood over

the filter cleaning unit is fitted after the check.

Check the automatic filter cleaning as follows:
1 Check the automatic cleaning equipment once a

year.

2 Remove the top cover from the filter and inspect

the valve disc.

3 Start the unit and press the filter cleaning button,

see 

Figure 8

. The compressed air cylinder should

lift the valve disc. Loud noise can be heard as air

rushes into the filter bin to blow off the dust from

the outside of the filter package. This will be re-

peated 3 times for each filter cleaning cycle.

4 Stop the vacuum unit and shut off the air supply.
5 Check the valve disc fastening, damage and wear.

Replace if required.

6 Replace the protecting top cover.

6.7 The motor and the fan unit

Inspect and clean the motor compartment regularly.

The motor has 2 ball bearings. The bearings are to be

replaced after approximately 15,000 hours of opera-

tion. If the ambient temperature often reaches 35°C

(95°F), the time between replacements is to be re-

duced. In any case, the bearings are to be replaced

every fifth year.
The bearings are a standard type. Contact Nederman

or an authorized Nederman distributor for replace-

ment of the bearings.
Old grease is to be removed and new grease used. The

grease is to meet the DIN 51825-K2N 40, SKF LGHP 2

or FAG Arcanol Multitop standards.

6.8 Cooling filter for the frequency con-

verter

The service life of the cooling filter for the frequency

converter depends on the air-bound dust surround-

ing the vacuum unit. The expected service life is 6–48

months. Check the filter regularly through the filter

holder grid. If the filter is clogged, the frequency con-

verter will shut off due to overheating.
Ensure that the cooling filter is not exposed to any

combustible materials. Running the unit without the

cooling filter may cause serious damage. When chan-

ging the filter, see the label placed over the filter in-

take.
The unit may never be run without a cooling filter for

the frequency converter.

6.9 Loading new software

This section is only for Nederman qualified ser-

vice technicians. Only Nederman qualified ser-

vice technicians may make changes to, or in-

stall new software.

Make notes of actual parameter settings.

6.9.1 Frequency converter control panel

To change the software or install new software for

the unit, the parameters in the frequency converter

have to be changed by means of the frequency con-

verter control panel available from Nederman.

6.9.2 Firmware and software labelling

The software version is found on a label taped

to the front of the PLC. LOGO 8 software is up-

dated using an SD Card. Follow the included in-

structions when the software needs to be up-

dated.

To find the firmware and software revision

number in the PLC display, see 

Figure 8

, item 1.

Pressing ‘OK’ when the PLC displays this menu

will show this information. See also the PLC

Settings Manual.

26

Содержание FlexPAK DX

Страница 1: ...Installation and service manual Compact dust collectors FlexPAK DX DX Models Original installation and service manual EN INSTALLATION AND SERVICE MANUAL 2021 07 07 144885 07 ...

Страница 2: ...FlexPAK DX Trace back information Workspace Main version a2 Checked in 2021 07 07 Skribenta version 5 4 024 ...

Страница 3: ...ries 20 5 Installation 20 5 1 Delivery check 21 5 2 Installation requirements 21 5 2 1 Bolts 21 5 3 Duct dimensions and installation 21 5 3 1 Requirements 21 5 3 2 Recommendations 21 5 4 Installing the unit 22 5 4 1 Indoor installation 22 5 4 2 Outdoor installation 22 5 4 3 Moving the unit 22 5 5 Electrical installation 22 5 6 Suppression system installation 23 5 7 General requirements 23 5 8 Auto...

Страница 4: ...Loading new software 26 6 9 1 Frequency converter control panel 26 6 9 2 Firmware and software labelling 26 6 9 3 Upgrading the system 27 6 10 Spare Parts 27 6 10 1 Ordering spare parts 27 6 11 Recycling 27 6 11 1 Environmental information 27 7 Troubleshooting 28 7 1 Tools 28 7 2 Remove the lid of the start and control unit 28 8 Acronyms and abbreviations 30 9 Appendix A Installation protocol 32 1...

Страница 5: ...s AB Ph Nederman Co SWEDEN Type Art no V Ser no Hz kW 50 A kW V A 60 Hz Year of manufacture hp 1 2116mm 83 3 772 mm 30 4 1670mm 65 8 1019 mm 40 1 58 mm 2 3 45 98 mm 90 88 90 98 98 98 98 98 220 320 540 640 O 14 18x 2A 5 ...

Страница 6: ...FlexPAK DX 2116mm 83 3 1750mm 69 1650mm 65 0 120mm 4 8 80mm 3 25 1010mm 40 2B 2116mm 83 3 1114mm 43 9 1469mm 57 8 1670mm 65 7 508mm 20 0 2C 6 ...

Страница 7: ...FlexPAK DX A E E A B C D G F 3A J I H 45 3B 7 ...

Страница 8: ...FlexPAK DX 13 12 10 9 7 8 2 1 3 4 6 5 11 4A 11 7 8 9 12 13 15 14 17 16 10 18 4B 8 ...

Страница 9: ...FlexPAK DX 20 21 19 Ø 151 mm Ø 195 mm 7 68 in Ø 220 mm 8 66 in 10 mm 39 in 8x Ø 5 94 in 22 5 4 5 7 x 5 mm 20 in 4C 1 2 3 6 7 8 9 16 15 14 13 11 10 12 4 5 5 9 ...

Страница 10: ...FlexPAK DX 6 A B 7 10 ...

Страница 11: ...FlexPAK DX EMERGENCY STOP SIEMENS LOGO 12 24RC XXXXXXX XXXXX XXXX ESC OK Stop Set Param Set Prg Name 6 1 5 4 2 3 8 11 ...

Страница 12: ...FlexPAK DX 4 1 6 7 8 10 9 11 5 2 3 9 1643 1mm 65 662 1mm 26 2 1771 4 1mm 70 Ø13mm 1 1643 1mm 65 662 1mm 26 2 1771 4 1mm 70 Ø13mm 10 12 ...

Страница 13: ...FlexPAK DX 11 12 13 14 13 ...

Страница 14: ...FlexPAK DX A A A A C Min 2 1m 83 15 1 0 m 39 4 16 A B C 17 14 ...

Страница 15: ...r personnel 3 Description 3 1 Function FlexPAK DX is a complete vacuum unit with a dir ect driven side channel fan fitted as one unit on a steel frame and a start and control unit with an integ rated 24 V transformer The unit is controlled by a fre quency converter has automatic start stop and auto matic filter cleaning 3 1 1 Filtration in two stages FlexPAK DX filters particles in two stages In t...

Страница 16: ...ystem see Figure 2B Flameless venting see Figure 2C 3 3 1 Explosion venting The risk area may extend beyond the values given below The final risk area is to be evalu ated with regards to affecting factors found in Standard EN 14491 For assistance and information contact Neder man The harmful effects of an explosion are minimized by venting the pressure and flame of the explosion through an explosi...

Страница 17: ...ased into the sur roundings and this must be taken into consideration when positioning the FlexPAK DX Please consult your local fire authority when determining suitable posi tioning of the FlexPAK DX with the flameless device Please refer to the installation and service or user manual for the flameless device supplied with the FlexPAK DX to find other limitations and information regarding safe use...

Страница 18: ...mm 7 87 6 29 150 160 mm 7 87 6 29 Sound level 70 dB A 70 dB A Ambient temperature range 0 40 C 32 104 F 0 40 C 32 104 F Process air temperature 0 60 C 32 140 F 0 60 C 32 140 F Relative humidity Max 85 Max 85 Compressed air 6 7 bar 87 102 psi 6 7 bar 87 102 psi Material recycling 93 6 per weight 93 6 per weight Control filter area 1x12 m 1x129 sqft 1x12 m 1x129 sqft Control filter material Polyeste...

Страница 19: ... filter see Fig ure 4A and Figure 4B 12 Cooling valve see Figure 4A and Figure 4B 13 High pressure side channel fan with pump char acteristic see Figure 4A and Figure 4B 14 PT100 sensor see Figure 4B 15 Outlet silencer after fan see Figure 4B 16 Control Filter and filter cartridge see Figure 4B 17 Pressure sensor see Figure 4B 18 Acoustic enclosure see Figure 4B 19 Cooling air hose from the freque...

Страница 20: ...xPAK DX start and control unit is prepared for the connection of Nederman accessories and custom er connections The installation of accessories extra equipment and functions is described in the manual for each product and according to the electrical diagrams that came with the unit Consult your local Nederman represent ative for available accessories The most common accessory is a PS cable which a...

Страница 21: ...e such as PVC is not to be used Almost all types of dust pick up stat ic electricity when sucked through a plastic pipe which significantly increases the risk for an explosion if the dust is combustible Do not collect material that may cause igni tion or blocking It is strictly prohibited to col lect material that may undergo dangerous chemical or thermal reactions and or self ig nite Some types o...

Страница 22: ...ed to a heat exchanger but there are not to be any dampers that may obstruct the air flow 5 4 2 Outdoor installation If installed outdoors consider the following The area needs to be protected from the weather Cover the top of the unit to protect it from snow rain or falling debris Install a lightning conductor see Section 5 7 General requirements Environmental and ambient conditions See Sec tion ...

Страница 23: ...h a protection device 5 8 Automatic bin emptying function See the PLC Settings Manual 5 9 Machining chips and swarf extrac tion See the PLC Settings Manual 5 10 Pneumatic filter cleaning valve See the PLC Settings Manual 5 11 ATEX Duct Isolation Valve See the PLC settings Manual 5 12 Ground check measurement All metal parts of the unit are to be grounded The system is to have two independent groun...

Страница 24: ...tively in a com mon protective hose Air pressure hoses are to be anchored mechanically 6 Maintenance Read Chapter 3 Description before carrying out any maintenance work Maintenance work means that the equipment will have to be opened and possibly dis mantled This may constitute a risk and the mainten ance personnel need to know about the risks that may occur when acting incorrectly WARNING Explosi...

Страница 25: ...ces Inspect the explosion venting panel and verify that it is intact 6 3 Empty the collector bin WARNING Risk of personal injury Ensure that there is no vacuum in the dust separator before removing the collector bin Crush hazard Be careful when lowering and refitting the collector bin Use proper pro tective equipment Wear goggles a dust mask and gloves when emptying the collector bin The plastic b...

Страница 26: ...lean the motor compartment regularly The motor has 2 ball bearings The bearings are to be replaced after approximately 15 000 hours of opera tion If the ambient temperature often reaches 35 C 95 F the time between replacements is to be re duced In any case the bearings are to be replaced every fifth year The bearings are a standard type Contact Nederman or an authorized Nederman distributor for re...

Страница 27: ...rts See also w w w n e d e r m a n c o m 6 10 1 Ordering spare parts When ordering spare parts always state the following The part number and control number see the product identification plate Detail number and name of the spare part see w w w n e d e r m a n c o m e n s e r v i c e s p a r e p a r t s e a r c h Quantity of the parts required 6 11 Recycling The product has been designed for compo...

Страница 28: ...circuited If the PS cable is damaged press the Standby Running but ton to put the unit into Off mode and investigate the fault If necessary loosen the PS cable from the control unit see the electrical diagrams and use an ohmmeter across the leads in turn to locate the fault Defect PT100 tem perature sensor Check whether the PT100 sensor is defective as follows 1 Disconnect the PT100 sensor wire fr...

Страница 29: ...l have to replace the pressure sensor Deposits or blockage in ducts on the way to the unit Clean the ducts Check the transport velocity The duct system is not properly dimensioned Re dimension the duct system or add an extra suction source Valves in the duct system are not working Check the duct system valves Low vacuum or air flow The filter cleaning does not work or is insufficient Check the fun...

Страница 30: ...act your nearest authorized distributor or Nederman for technical advice Filter cleaning does not work The cleaning interval is too short Extend the cleaning interval Compressed air Pr t is 1 bar See Section 3 5 Technical data Too low compressed air pressure can result in premature filter clogging If the pres sure is lacking or too low the piston cannot open the FCV and lid properly This results i...

Страница 31: ...ressure Sensor Filter Cleaning MFDPS Wr Main Filter Differential Pressure Sensor Warning MI Maintenance interval OT Operating total PE Protective earth PLC Programmable logic controller PS Pilot signal PSIFC Pilot signal interlock filter cleaning PTC Positive temperature coefficient PES Potential equalization system PVC Polyvinyl chloride RPS Relief Panel Sensor SLV Solenoid lower valve SSR Start ...

Страница 32: ...ckets Unit No Date Performed by Control items Result Application requirements limits Material chemical thermal reaction risk Radiation heat from surroundings Delivery checks Missing components Transport damage Before installation Foundation Total weight product accessories and collected material Anchor bolts Access for maintenance filter replacement 1 m above the unit Mounting check availability M...

Страница 33: ...air valve Compressed air connected to the unit Ground check measurement Check Incoming duct Incoming mains ground GND1 External mains ground Accessories if applicable Signs and warnings Intended use marked or indicated Safe bag replacement described or indicated Initial start up function test Maintenance switch Motor the direction of rotation Automatic filter cleaning Manual filter cleaning Cover ...

Страница 34: ...sult Result Result Manual Nut VV Previous service record Inspect clean outside the unit Remove dust deposits clean work area Remove corrosion by grinding apply primer and touch up paint Vacuum measure negative pressure Cooling valve Motor bearings Fan Cooling fan motor Bearing motor fan Safety switch Box housing Main switch Cable harness Electrical connection points Ground earth connection Indicat...

Страница 35: ...ng valve check Filter bags visual check Filter bags check pressure drop perform ance The main filter replace Clean and dry air check Ground measurement check GND1 Fan Incoming duct Incoming mains ground GND1 External mains ground Gaskets check for leakage and replace if necessary Plastic bag replace Bearings motor replace Bearings fan replace Check that the ventilation of the room is clear if plac...

Страница 36: ...www nederman com ...

Отзывы: