10.  Configure operation settings of the internal simple uninterrupted power supply as needed.   

You  can  configure  the  internal  simple  uninterrupted  power  supply  by  EXPRESSSCOPE  Engine 
3/BMC Management Console, NEC ESMPRO/ServerManager, or Server Configuration Utility.   
For details, 

 Refer the online help stored in EXPRESSSCOPE Engine  3/ BMC  Management Console and NEC 

ESMPRO/ServerManager,   

 Refer chapter 2 (2.7 Battery Configuration) in the 

“Maintenance Guide” about Server Configuration 

Utility.   

* In case of Express5800/T110i-S, use EXPRESSSCOPE engine 3, and in case of 

Express5800/T110j-S, use BMC Management Console. 

 
Internal simple uninterrupted power supply is configured as below at the factory shipment. 

Shutdown at power lost : Enable 

Shutdown delay time : 30 seconds 

Battery turn off delay time: 3600 seconds 

Boot after power recovery: Enable 

Boot timeout after DC-ON: 0 seconds. 

 
ESMPRO/ServerManager(older than ver.6.20) cannot reset to default settings. 
You need to change some settings manually in order to set default status.

 

 

 
3. Removal 

You can replace or remove the internal simple UPS  control kit by a reverse procedure. If internal simple 

UPS becomes exhausted, replace only N8181-152 Internal simple UPS. 

You can check the internal simple UPS degradation status by Battery LED (        ). 

 
 
 
 

 

 

LED Status 

Description 

On 

Exhausted 

Off 

Normal operation 

 

4. Precautions for operating with internal simple UPS   

 

Charge  the  internal  simple  UPS  before  you  start  operation.  You  can  check  charging  state  and 
settings  of  internal  simple  UPS  with  EXPRESSSCOPE  Engine  3/  BMC  Management  Console  or 
NEC ESMPRO. For details, see the manual provided with each tool. 

* In case of Express5800/T110i-S, use EXPRESSSCOPE engine 3, and in case of 

Express5800/T110j-S, use BMC Management Console. 

 

Following is the limitations when using internal simple UPS. 

 

Up to 4 hard disk drivers can be installed. 

 

High Temperature Resistant Kit cannot be mounted. 

 

The backup device can be mounted on only 3.5-inch additional bay(1). 

 

Redundant power unit cannot be installed. 

 

If errors are detected after you finished installation, confirm the mount procedure and confirm the 
cable of internal simple UPS is surely connected. 

 

The setting to start shutdown when power supply abnormality occurs is enabled by default. 

 

Detection of abnormal temperature 
If the internal simple UPS is used in the system, there is a possibility to detect abnormal temperature 
due to following characteristics of the battery. 

 

AC off/on repeatedly in very short term. 

 

System is in heavy load condition when system turns to battery backup operation. 

In this case, if the temperature returns to normal value after a while, it is no problem. 
Please check system operating condition, load status and settings of battery operation. 
If abnormal temperature detects continuously, the internal simple UPS or the internal simple UPS 
control kit may have problem. Please consult your sales or service representative. 

Note 

Battery LED 

Содержание N8181-153

Страница 1: ...1 1 N8181 153 CBZ 008540 001 04...

Страница 2: ...2 OFF...

Страница 3: ...3 1 1 1 2 1 3 LED 1 4 2 5 2 6 1 7 1 8 1 9 1 3 5 2 8 6 1 7 3 LED 2 5 9 4...

Страница 4: ...4 2 1 2 3 5 2 4 LED 3 3 1 3 5 2 3 2 1 1 3 5 2 3 5 2 3 5 1 3 5 1 2 5 HDD 3 5 2 3 5 1...

Страница 5: ...5 3 3 2 3 4 I2C I2C 3 5 3 3 2 7 4 I2C I2C 7 4 I2C P2 P1...

Страница 6: ...6 3 6 2 3 3 4 2 LED 4 1 LED 4 2 1 4 3 LED 2 7 4 LED 3 5 2...

Страница 7: ...7 5 LED 3 5 2 LED CN102 6 N8181 152 6 1 N8181 152 6 2 x1 LED CN102...

Страница 8: ...8 6 3 x1 x2 CN104 CN105 CN103 7 Express5800 T110i S iStorage NS100Th BIOS OR 2 3 2 1 CN104 CN105 CN103 I2C 3 2 1 3 2 1 BIOS OR...

Страница 9: ...https www support nec co jp T110i S NS100Th SDR Express5800 T110j S iStorage NS100Ti POWER ON POWER OFF 30 POWER ON 10 EXPRESSSCOPE 3 BMC ESMPRO ServerManager Server Configuration Utility BBU MODEL 3...

Страница 10: ...xpress5800 T110i S iStorage NS100Th EXPRESSSCOPE 3 Express5800 T110j S iStorage NS100Ti BMC 30 3600 DC ON 0 ESMPRO ServerManager Ver 6 20 3 N8181 152 4 EXPRESSSCOPE 3 BMC ESMPRO Express5800 T110i S iS...

Страница 11: ...ion Utility Battery Configuration Battery Information Battery Pack Information BMC Battery Power ESMPRO Server Manager IPMI Battery Power Offline TOOL MENU Maintenance Utility IPMI Information Viewer...

Страница 12: ...terms are defined as follows Precautions and notices against hazards are presented with one of the following two symbols The individual symbols are defined as follows Attentions Prohibited Actions Man...

Страница 13: ...floor Places with drastic changes in temperature Place where vibration or impact may be generated Places with corrosive gas sulfur dioxide hydrogen sulfide nitrogen dioxide chlorine ammonia ozone etc...

Страница 14: ...s included in this product Each components are same feature size If backup device is already installed in 3 5 inch expansion bay 2 the device tray attached in this product will be used for battery ins...

Страница 15: ...tion figured below and slide it toward the front side until the front of control kit touches the chassis 3 2 Fix it with a countersunk screw and a flat head screw Note If backup device is installed in...

Страница 16: ...onnect two power cables that removed in step 3 3 to connector on the control kit Indicated by circle on the figure Please refer step 7 4 for detailed power connector location on the motherboard Rear S...

Страница 17: ...t edge of the device tray 4 2 Fix with a flat head screw 4 3 At the position marked in the figure fix the LED cable to device tray with a cable tie Pass through a cable tie by two holes in the figure...

Страница 18: ...procedures 6 1 Mount N8181 152 internal simple UPS to the battery holder bracket as the direction figured below And fix the battery with spring 6 2 Insert the battery holder bracket that the internal...

Страница 19: ...per BIOS OR on the motherboard to Enabled Set to 2 3 If N8181 152 internal simple UPS is not used set jumper BIOS OR on the motherboard to Disabled Set to 1 2 Important To avoid system malfunction do...

Страница 20: ...procedure below 1 Connect a power code to the server 2 Wait for 40 seconds after AC power is supplied to the server 3 Turn on the server 4 Insert an SDR Update Tool CD ROM to the optical disk drive an...

Страница 21: ...th internal simple UPS Charge the internal simple UPS before you start operation You can check charging state and settings of internal simple UPS with EXPRESSSCOPE Engine 3 BMC Management Console or N...

Страница 22: ...Sensor Status Current Battery Power Remarks 1 No part of this manual may be reproduced in any form without the prior written permission of NEC Corporation 2 The contents of this User s Guide may be re...

Отзывы: