Connect the cable of the internal simple UPS (a power cable and two signal cables) to the
CN104, CN105 and CN103 connector of the control kit.
7.
Motherboard’s Jumper setting
[In case of Express5800/T110i-S]
The jumper on motherboard must be configured when using internal simple UPS. When using N8181-
152 internal simple UPS, set jumper (BIOS OR) on the motherboard to
“Enabled” (Set to 2-3).
If N8181-152 internal simple UPS is not used, set jumper (BIOS OR) on the motherboard to
“Disabled”
(Set to 1-2).
Important
To avoid system malfunction, do not change other jumper setting.
Tips
The procedure of installing this product depends on your server type.
Please work with a procedure of the sever you
’re using.
CN104 Connector
CN105 Connector
CN103 Connector
Motherboard
Rear Side
Front Side
Power Connector
Power Connector
I2C Connector
BIOS OR
Jumper
Disabled
3
2
1
3
2
1
Enabled