7
N D B - D O C - 3 - U s e r M a n u a l
6. Operation
This section of the user manual describe how to operate the NDB-DOC-3.
6.1 Cable check test
Perform a cable check test prior to test any power transformer to ensure test
equipment’s integrity.
1.
Turn on the instrument by pressing the power button
.
2.
Connect the test lead to the instrument.
3.
Short all clamps together. Make sure all clamps make good electrical contact.
4.
Press the winding type selection button
to select
MODE: CableCheck
.
5.
Press the start test button
.
6.
The test will last for approximately 8 seconds.
7.
Once completed, the result will be displayed:
•
The green
OK
indicator will turn on, and
Pass
will be displayed on the
screen if cables are in good condition.
•
The
OPEN
yellow indicator will turn on, and
Fail
will be displayed on
the screen if the instrument detected an unexpected resistance value
in the test lead. Make sure all clamps make good electrical contact. If
the problem persists, the test lead must be repaired or replaced.