NCD RS-485 Скачать руководство пользователя страница 1

 
 
 
 
 

 

 
 
 
 
 
 
 

INTRODUCTION RS485 TO WIRELESS 

 
 

The NCD RS-485 to Wireless Adapter converts data in both direction between Wireless and RS-485 

communications.  Inside the modem, you will see a small module, which actually handles the conversion 

process.  This documentation will reference this module and all applicable jumper settings. 

There are 3 versions of this modem, which will be covered in this guide.  The communication protocols are 

slightly different for each version.  We will start the guide by covering the hardware, and then move on to 

protocol for all 3 versions.  Please note this guide will discuss commands in hex values ONLY. 

Also, please note the default RS-485 Communications Baud rate is 9600.  We suggest using the default settings 

for best results. 

Getting to Know NCD RS-485 Node Modules 

NCD RS-485 Node modules are a modular technology, allowing most NCD devices to be retrofitted with RS-485 

communication capabilities.  Node modules have a number of options an

Содержание RS-485

Страница 1: ...is guide The communication protocols are slightly different for each version We will start the guide by covering the hardware and then move on to protocol for all 3 versions Please note this guide wil...

Страница 2: ......

Страница 3: ...communications with a Raspberry Pi 2 or 3 Arduino to Modular Communications Adapter allows RS 485 communications with Arduino Uno Particle Photon to Modular Communications Adapter allows RS 485 commun...

Страница 4: ...tes will be Returned Indicating the Baud Rate 9 600 00 25 80 19 200 00 4B 00 38 400 00 96 00 57 600 00 E1 00 115 200 01 C2 00 Change the RS 485 Baud Rate Send the Following Bytes via RS 485 9600 Baud...

Страница 5: ...p computers that have the resources to properly generate and decode Digi API communication frames If you are unfamiliar with Digi API communication frames please reference the following document from...

Страница 6: ...6E 65 Example of Outgoing Wireless Data 7E 00 25 90 00 13 A2 00 41 8C 58 B6 FF FE C2 69 20 74 68 69 6E 6B 20 69 20 61 6D 20 77 6F 72 6B 69 6E 67 20 66 69 6E 65 1F Read Network ID AutoEncoder The Read...

Страница 7: ...o target communications with a specific device or broadcast data to all devices that share the same Network ID Use the following command to Set the Destination Address of all wireless data Set Destina...

Страница 8: ...es to follow NCD standards for device communications The Emulator version essentially takes incoming RS 485 data and attaches additional information to make existing equipment act like a modern NCD Io...

Страница 9: ...FE 00 00 F7 19 00 00 00 E4 Response 7E 00 1C 90 00 13 A2 00 41 8C 58 B6 FF FE C2 7C 00 00 00 00 00 00 7F FF 00 00 00 00 00 00 00 26 28 bytes Write Network ID Emulator The Write Network ID command upd...

Страница 10: ...8C 58 B6 FF FE C2 7C 00 00 00 00 00 00 FF 00 00 00 00 00 00 00 00 A5 Read Destination Address Emulator The Destination Address can be used to target communications with a specific device or broadcast...

Страница 11: ...t Baud Rate 7E 00 13 10 00 00 00 00 00 00 00 FF FF FF FE 00 00 F7 01 00 25 80 57 Response 7E 00 1C 90 00 13 A2 00 41 8C 58 B6 FF FE C2 7C 00 00 00 00 00 00 FF 00 00 00 00 00 00 00 00 A5 Command Errors...