The moving secondary block frame is mechanically connected to a secondary slider
batton on the front of the Citadel breaker.
This “slider batton” allows the moving contact block to manually be pushed rearward and
thereby connect with the stationary cell side.
This action allows a breaker in the “disconnect” positon to be placed into a “Test” position.
The breaker can now be operated electrically and mechanically. All secondary control
auxiliary connections will make and break as though the Citadel breaker was in the fully
connected position.
Secondary slider batton
FIGURE 64
S W I T C H G E A R C U B I C L E & D R A W - O U T F E A T U R E S