Catalogue number:  

AN

□□□□□□ 

 

 

 

AS 

 
Air Circuit Breaker  1600-5000  70-85kA

 

 

 

 

AS

□□□□□□

 

1  LCD:  indication  of  measurement 
and information 

2  LED:  indication  of  trip  information 
and overload state 

3 Key: Move to menu or reset 

4 Iu, Ir: Long-time current setting, tr: 
Long-time tripping delay setting 

5 Isd: Short-time current setting, tsd: 
Short-time tripping delay setting 

6 Ii: Instantaneous current setting 

7 Ig: Ground fault current setting, tg: 
Ground fault tripping delay setting 

8  Test  terminal:  OCR  test  terminal 
(Connected with OCR tester) 

 
 
 
 
 
 
 
 

N.A.W. Controls Pty. Ltd. 

Telephone: (03) 9464 6555 

www.nawcontrols.com.au

 

LS ACB AS & AN range

 

June 2020 

Long  time 

Current setting (A)

Iu = In×

0.5

0.6

0.7

0.8

0.9

1

Ir = Iu×

0.8

0.83

0.85

0.88

0.9

0.93 0.95

0.98

1

Time delay (s)

tr@(1.5×lr)

12.5

25

50

100

200

300

400

500

Off

Accuracy: ±15% or below

tr@(6.0×lr)

0.5

1

2

4

8

12

16

20

Off

100ms

tr@(7.2×lr)

0.34

0.69

1.38

2.7

5.5

8.3

11

13.8

Off

Short Time

Current setting (A)

Isd = Ir×

1.5

2

3

4

5

6

8

10

Off

Accuracy:  ±10%
Time delay (s)

tsd

I²t Off

0.05

0.1

0.2

0.3

0.4

I²t On @(10×lr)

0.1

0.2

0.3

0.4

I²t Off

Min. Trip Time (ms)

20

80

160

260

360

Max. Trip Time (ms)

80

140

240

340

440

Instantaneous

Current setting (A)

Ii = In×

2

3

4

6

8

10

12

15

Off

Tripping time

Ground fault

Pick-up (A)

Ig = In×

0.2

0.3

0.4

0.5

0.6

0.7

0.8

1

Off

Time delay (s)

I²t Off

0.05

0.1

0.2

0.3

0.4

Accuracy: ±10%(Ig˃0.4In)

I²t On @(1×ln)

0.1

0.2

0.3

0.4

              ±20%(Ig˃0.4In)       .       

or below 50ms

Min. Trip Time (ms)

20

80

160

260

360

Max. Trip Time (ms)

80

140

240

340

440

Earth leakage (Option)

Current setting (A)

I

Δn

0.5

1

2

3

5

10

20

30

Off

Time delay (ms)

Δt

Alarm Time(ms)

140

230

350

800

950

Accuracy:  ±15%

Alarm Time(ms)

140

230

350

800

Trip Unit: A type

Below 50ms

tg

(I²t Off)

Содержание Eureka AN Series

Страница 1: ...ion of protective coordination by ZSI A Configuration Fixed Type ACB Catalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Air Circuit Breaker 1 Trip relay 2 Counter 3 ON button 4 OFF button 5 Series name 6 Charge handle 7 Rated name plate 8 Charge Discharge indicator 9 ON OFF indicator 10 Corporation logo 11 Arc cover 12 Terminal cover 13 Cradle 14 Draw out handle 15 Position indicator ...

Страница 2: ...inal cover 13 Cradle 14 Draw out handle 15 Position indicator 16 Handle storage space 17 Pad lock button 18 Arc chute 19 Control cover 20 Fixed type bracket 1 Terminal cover of control circuit 2 Cradle finger Line side 3 Cradle finger Load side 4 Draw out handle 5 Position indicator 6 Handle storage space 7 Pad lock button 8 Connecting conductor Line side 9 Connecting conductor Load side N A W Con...

Страница 3: ...r supply terminal 4 Trip relay control terminal 5 Carrying grip 6 Trip coil or UVT coil 7 Mechanism 8 Main body 9 Counter 10 Trip coil 11 Closing coil 12 Motor Ass y 13 Aux switch 14 ON button 15 OFF button 16 MTD base 17 Trip relay 18 Front cover N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Страница 4: ...ty kA Ics Icu 100 100 100 Rated making capacity kA peak IEC 60947 2 220V 230V 380V 415V 143 154 220 KS C 4620 AC 50 60Hz 460V 480V 500V 143 154 220 550V 600V 690V 105 143 187 Rated short time 1 sec 50 65 85 withstand current kA 2 sec 42 55 75 3 sec 36 55 65 Operating time ms Maximum total breaking time 40 Maximum closing time 80 Life cycle time Mechanical 10000 Electrical 2000 Main body Motor char...

Страница 5: ...Catalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range May 2020 Electrical Single Line Diagram ...

Страница 6: ...h A7 AL1 MRB RES DC110 125V Auto reset T TM Temperature monitoring A8 AL1 MRB RES AC200 250V Auto reset H1 AC DC 100 130V A9 AL1 MRB RES AC110 130V Auto reset H2 AC DC 200 250V Y2 AL1 AL2 MRB 2b contact H3 DC 125V Y6 AL1 AL2 MRB Auto reset 2b contact H4 DC 24 30V Z2 AL1 AL2 MRB 1a1b contact H5 DC 48 60V Z6 AL1 AL2 MRB Auto reset 1a1b contact H6 AC 380 480V C C Counter H7 AC 48V S CS2 Charge switch...

Страница 7: ...elay s tr 1 5 lr 12 5 25 50 100 200 300 400 500 Off Accuracy 15 or below tr 6 0 lr 0 5 1 2 4 8 12 16 20 Off 100ms tr 7 2 lr 0 34 0 69 1 38 2 7 5 5 8 3 11 13 8 Off Short Time Current setting A Isd Ir 1 5 2 3 4 5 6 8 10 Off Accuracy 10 Time delay s tsd I t Off 0 05 0 1 0 2 0 3 0 4 I t On 10 lr 0 1 0 2 0 3 0 4 I t Off Min Trip Time ms 20 80 160 260 360 Max Trip Time ms 80 140 240 340 440 Instantaneou...

Страница 8: ...e last downstream device Instantaneous I Ii 1 Standard current setting knob Ii Setting range 2 3 4 6 8 10 12 15 Off In 2 Relay operates basing on the largest load current among the 3 phases 3 Total breaking time is below 50ms Long time delay L Iu Ir tr 1 Standard current setting knob Ir Setting range in N type and A type 0 4 1 0 In Iu 0 5 0 6 0 7 0 8 0 9 1 0 In Ir 0 8 0 83 0 85 0 88 0 9 0 93 0 95 ...

Страница 9: ...UF_Pick up 55 1Hz 0 1Hz Under 60Hz 55Hz OF_Pick up 1Hz 0 1Hz frequency 50Hz 45Hz OF_Pick up 1Hz 0 1Hz 0 2 40sec 1 2 40sec 0 1sec 0 1sec Other protections Time delay s Pick up 1 2 40sec N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 Catalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Ground Fault G Ig tg 1 Standard setting current knob ...

Страница 10: ...controls com au LS ACB AS AN range June 2020 ZSI Zone Selective Interlocking A P S type 1 In case of that short time delay or ground fault accident occurs at ZSI built in system the breaker at accident site sends ZSI signal to halt upstream breaker s operation 2 To eliminate a breakdown trip relay of MCCB at accident site activates trip operation without time delay 3 The upstream breaker that rece...

Страница 11: ...r AN AS Air Circuit Breaker 1600 5000 70 85kA AS Accessories Counter The Counter displays the total number of NO OFF operations performed on the ACB N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Страница 12: ...ng button due to user s accidental handling It is not possible to perform ON OFF operation under the Button lock status Under Voltage Trip device UVT If the voltage of the main or the control power is under voltage UVT which is installed inside of the breaker breaks the circuit automatically Please connect with UVT time delay device to present the time delay function because UVT is technically an ...

Страница 13: ...d the switch AL outputs the fault location MRB and AL can be operated only when tripping by an OCR To re close a circuit breaker after a trip press MRB to reset it for closing Trip alarm contact and MRB Manual reset bottom need to be purchased together Resistive load lamp load Inductive load A Motor load 8 VDC 11 3 6 3 30 VDC 10 3 6 3 125 VDC 0 6 0 1 0 6 0 1 250 VDC 0 3 0 05 0 3 0 05 250 VAC 11 1 ...

Страница 14: ...temperature rises to an abnormal value the unit automatically sounds an alarm TRIO unit is installed on the cradle or the inside of panel LED Status DI1 Indicates digital Input 1condition DI2 Indicates digital Input 2condition DO ON Indicates temperature alarm output is ON DO OFF Indicates temperature alarm output is OFF 5 CB ON Indicates circuit break close condition CB OFF Indicates circuit brea...

Страница 15: ...60V AC DC 100 130V AC DC 200 250V AC 380V AC 440 480V Load curent Max 5A 3A 1A 0 5A 0 3A 0 3A Starting current Max Load rpm Motor Charge time Dielectric strength Using temperature range Using humidity range Charge switch 10A at 250VAC 15000 19000 rpm Less than 5sec 2kV min 20 60 Max RH 80 No dew condensation 5 times of load current Type AN AS D AN AS E AS F AS G Endurance 20000 15000 10000 10000 N...

Страница 16: ... AN25E3 25H AS32E3 32H AS40E3 40V AN16D3 16A AS20D3 20A AN25E3 20A AN32E3 32A AS40E3 40A AS50F3 50A N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 Catalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS ...

Страница 17: ... AS Characteristic Curve Short time delay S AS16D3 16H AS20D3 20H AN25E3 25H AS32E3 32H AS40E3 40V AN16D3 16A AS20D3 20A AN25E3 20A AN32E3 32A AS40E3 40A AS50F3 50A N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Страница 18: ...aracteristic Curve Instantaneous I Ground fault G AS16D3 16H AS20D3 20H AN25E3 25H AS32E3 32H AS40E3 40V AN16D3 16A AS20D3 20A AN25E3 20A AN32E3 32A AS40E3 40A AS50F3 50A N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Страница 19: ...gue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AS 06 16D Fixed unit AS16D3 16H Door Frame N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Страница 20: ...e number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AN 06 16D Draw out Unit AN16D3 16A Door Frame N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Страница 21: ...Catalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AS 20D Fixed Unit AS20D3 20H N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Страница 22: ...atalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AS 20D Draw out Unit AS20D3 20A N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Страница 23: ...e number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AN AS 20 35E Fixed Unit AN25E3 25H AS32E3 32H N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Страница 24: ... number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AN AS 20 35E Draw out Unit AN25E3 25A AN32E3 32A N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range May 2020 ...

Страница 25: ...Catalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AS 40E Fixed Unit AS40E3 40V N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Страница 26: ...atalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AS 40E Draw out Unit AS40E3 40A N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Страница 27: ...atalogue number AN AS Air Circuit Breaker 1600 5000 70 85kA AS Dimension AS 50F Draw out Unit AS50F3 50A N A W Controls Pty Ltd Telephone 03 9464 6555 www nawcontrols com au LS ACB AS AN range June 2020 ...

Отзывы: