Catalogue number:
AN
□□□□□□
AS
Air Circuit Breaker 1600-5000 70-85kA
AS
□□□□□□
OCR Tester (OT)
It is a device which be used to test the operation of Trip Relay under
no power.
•
An of input of 17 times the rated current can be inputted as a
maximum.
•
Allows to manipulate currents on each phase.
•
Frequency is adjustable.
•
It is available to test for long time delay, short time delay,
instantaneous & ground fault.
Temperature Remote I/O Unit (TRIO)
TRIO unit is a device to show the temperature through a sensor
inside the ACB.
Two temperature sensors can be installed at a time and the output
is connected to the control terminal blocks.
It displays the maximum temperature of them and transmits
through a network.
If the temperature rises to an abnormal value, the unit
automatically sounds an alarm.
TRIO unit is installed on the cradle or the inside of panel.
LED Status
DI1 Indicates digital Input #1condition
DI2 Indicates digital Input #2condition
DO ON Indicates temperature alarm output is ON
DO OFF Indicates temperature alarm output is OFF
5 CB ON Indicates circuit break close condition
CB OFF Indicates circuit break open condition
RUN LED Indicates unit run condition
Indicates circuit break terminal
Disconnection / control Err condition
CB ERROR
Applied range
Remarks
Contact switching capacity
AC230V 16A / DC30V 16A
Max. switching capacity
3680VA, 480W
Contact switching capacity
AC230V 6A / DC25V 6A
Induction load
Max. switching capacity
1880VA, 150W
(cosØ=0.4, L / R=7ms)
Classification
CB control
Alarm
1 TRIO Unit
N.A.W. Controls Pty. Ltd.
Telephone: (03) 9464 6555
www.nawcontrols.com.au
LS ACB AS & AN range
June 2020