82 Troubleshooting
5.2.14 Error 352
Error conditions and checklist
Error
Description
E352
High water pressure
If an error signal is received from the water pressure sensor, the system displays the E352
on the front panel. High water pressure errors occur if the water pressure is 3.9 bar or
higher for 3 sec.
The error is automatically cancelled if the water pressure returns to 3.9 bar or lower.
Checklist
1. Check if the input water pressure sensor is wet for any reason, including leakage.
2. Check the controller.
Is there a leak inside
the boiler?
Is the water
pressure sensor
normal?
1. Check connections
Repair the leak
Replace the water pressure sensor
Yes
No
Yes
No
Testing method
Fault
Possible causes
Check method
E352
High water pressure
Check the water supply pressure. (3.9 bar or higher is the error state)
Check if the safety valve is stuck.
Check the Auto feeder valve.
High water pressure
sensor
Water pressure sensor
fault
1. Check the output voltage. (Normal state: 0.25-4.93 V)
2. Replace the faulty or open water pressure sensor.
Содержание NCB500-2S/37K
Страница 3: ......
Страница 4: ...Revisions 3 Version Description of changes Date 1 00 First issue September 7 2022 Revisions...
Страница 115: ...Memo...
Страница 116: ...Memo...
Страница 117: ...Memo...
Страница 118: ...Memo...