12 000 WATT AM BROADCAST TRANSMITTER
XL12
Page 6-10
01 January 2002
6.6.14.6
Internal Interlock Alarm:
The
Internal Interlock Alarm
output is applied to the
remote interface PWB's
INT INTLK ALARM
terminal.
When the interlock circuit is intact, the output is an
open collector. When the interlock is open, the
Internal Interlock Alarm
output will be a current-
sink-to-ground. The RF output will be turned off by
removing 24 VDC from the transmitter's control
circuits.
6.6.14.7
External Interlock Alarm:
The
External Interlock Alarm
output is applied to the
remote interface PWB's
EXT INTLK ALARM
terminal.
When the interlock circuit is intact, the output is an
open collector. When the interlock is open, the
External Interlock Alarm
output will be a current-
sink-to-ground. The RF output will be turned off by
removing 24 VDC from the transmitter's control
circuits.
6.6.14.8 Filter Temperature Alarm:
The
Filter
Temperature Alarm
output is applied to the remote
interface PWB's
ALARM - FILTER TEMP
. When the
output filter's temperature exceeds the maximum
ambient temperature of 85
°
C, the output will become
a current-sink-to-ground.
6.6.14.9
Power Supply Temperature
Alarm:
The
Power Supply Temperature Alarm
Alarm output is applied to the remote interface
PWB's
ALARM - P/S TEMP
.
When the temperature in
the power supply exceeds the maximum ambient
temperature of 85
°
C, or the power supply's B+
charge/discharge cycle exceeds its allowable period,
the output will become a current-sink-to-ground.
6.6.14.10 Power Module Alarm:
The
Power
Module Alarm
output is applied to the remote
interface PWB's
ALARM - PWR MOD
. It is triggered
by either a PA or modulator failing.
6.6.14.11 Power Supply Alarm:
The
Power
Supply Alarm
output is applied to the remote
interface PWB's
ALARM - PWR SUPPLY
. It becomes
a current-sink-to-ground when there is a B+ voltage
rectifier failure or when a B+ voltage supply
becomes more than ten percent of the ideal voltage
for the power transformer's selected primary winding
taps.
6.6.14.12 Modulation Protection Alarm:
The
Modulation Protection Alarm
output is applied to
the remote interface PWB's
ALARM - MOD PROTECT
.
It becomes a current sink-to-ground when the level
of audio has exceeded a maximum value-time
product.
6.6.14.13 PDM Inhibit Alarm:
The
PDM Inhibit
Alarm
output is applied to the remote interface
PWB's
ALARM - PWM INHIBIT
. This alarm is
triggered manually when the PDM Inhibit function
has been accessed during repair or maintenance.
6.6.14.14 Standby Alarm:
The
Standby Alarm
output is applied to the remote interface PWB's
ALARM - STANDBY
. This alarm is triggered (output
becomes a current sink-to-ground) when there has
been an automatic transfer from the main transmitter
to the standby transmitter.
6.6.15 REMOTE STATUS INDICATIONS:
Outputs that indicate status of operator controlled
circuits are available at terminals of TB2 on the
remote interface PWB. These outputs are provided
for external monitoring. Each status output contains
a switching transistor that provides an open collector
when its circuit is passive (not-true condition exists)
and a current-sink-to-ground when a true (circuit
active) condition exists. Each external monitoring
circuit must present an impedance, between the
switching transistor and a positive DC voltage
source, that will result in not more than 40
milliamperes flowing through the transistor when
turned on. Each status circuit's positive voltage
source must not exceed 24 VDC. Each status
output is protected against transients and/or over
voltage by a 39 volt zener diode.
6.6.15.1
Remote Status:
The
Remote
Status
output is applied to the remote interface
PWB's
REMOTE STATUS
terminal. When transmitter's
CONTROL
switch is set to
LOCAL
and the remote
control functions have no influence on the
transmitter's on/off status or preset RF power levels,
the
Remote Status
output is an open collector.
When the transmitter's
CONTROL
switch is set to
REMOTE
and the remote control functions are
controlling transmitter operation, the
Remote Status
output is a current sink-to-ground.
Содержание XL12
Страница 44: ...12 000 WATT AM BROADCAST TRANSMITTER XL12 Page 2 20 01 January 2002 Figure 2 4 External Input Output Interface...
Страница 135: ...12 000 WATT AM BROADCAST TRANSMITTER XL12 Page 7 9 01 January 2002 Figure 7 14 PDM Output Monitor TP18 PDM 72kHz...
Страница 193: ...Figure SD 1 Electrical Schematic XL12 12 000 Watt AM Broadcast Transmitter Page SD 1 01 January 2002...
Страница 194: ...Figure SD 2 Electrical Schematic Exciter Stage Page SD 2 01 January 2002...
Страница 195: ...Figure SD 3 Electrical Schematic RF Drive Stage Page SD 3 01 January 2002...
Страница 196: ...Figure SD 4 Electrical Schematic RF Power Stage Page SD 4 01 January 2002...
Страница 197: ...Figure SD 5 Electrical Schematic Control Monitor Functions Page SD 5 01 January 2002...
Страница 198: ...Figure SD 6 Electrical Schematic AC DC Power Stage Page SD 6 01 January 2002...
Страница 199: ...Figure SD 7 Electrical Schematic Remote Interface PWB NAPI25A Page SD 7 01 January 2002...
Страница 200: ...Figure SD 8 Electrical Schematic Exciter Interface PWB NAPI22E Page SD 8 01 January 2002...
Страница 201: ...Figure SD 9 Electrical Schematic RF Drive Tuning PWB NAPI60 Page SD 9 01 January 2002...
Страница 202: ...Figure SD 10 Electrical Schematic Distribution PWB NAPI50B Page SD 10 01 January 2002...
Страница 203: ...Figure SD 11 Electrical Schematic DC Power Supply PWB NAPS16C Page SD 11 01 January 2002...
Страница 204: ...Figure SD 12 Electrical Schematic DC Power Supply Monitor PWB NAPI48B Page SD 12 01 January 2002...
Страница 205: ...Figure SD 13 Electrical Schematic RF Combiner Output Filter NAF101C NAF102 Page SD 13 10 July 2003...
Страница 208: ...Figure MD 1 Assembly Detail XL12 12 000 Watt AM Broadcast Transmitter Top and Front Page MD 1 01 January 2002...
Страница 209: ...Figure MD 2 Assembly Detail XL12 12 000 Watt AM Broadcast Transmitter Rear and Sides Page MD 2 01 January 2002...
Страница 210: ...Figure MD 3 Assembly Detail NAC101 Control Monitor Panel Page MD 3 01 January 2002...
Страница 211: ...Figure MD 4 Assembly Detail NAPD07 01 and NAPD07 02 Meter Switch Monitor PWBs Page MD 4 01 January 2002...
Страница 212: ...Figure MD 5 Assembly Detail NAPI25A Remote Interface PWB Page MD 5 01 January 2002...
Страница 213: ...Figure MD 6 Assembly Detail NAE73A Exciter Panel Page MD 6 01 January 2002...
Страница 214: ...Figure MD 7 Assembly Detail NAPI22E Exciter Interface PWB Page MD 7 01 January 2002...
Страница 215: ...Figure MD 8 Assembly Detail NAE83 RF Drive Panel Page MD 8 01 January 2002...
Страница 216: ...Figure MD 9 Assembly Detail NAAA02 RF Drive Amplifier Page MD 9 01 January 2002...
Страница 217: ...Figure MD 10A Assembly Detail NAPI60 01 and NAPI60 02 RF Drive Tuning PWB Page MD 10A 01 January 2002...
Страница 218: ...Figure MD 10B Assembly Detail NAPI60 03 and NAPI60 04 RF Drive Tuning PWB Page MD 10B 01 January 2002...
Страница 219: ...Figure MD 11 Assembly Detail NAPS10B Regulated Power Supply PWB Page MD 11 01 January 2002...
Страница 220: ...Figure MD 12 Assembly Detail NAPI50B Distribution PWB Page MD 12 01 January 2002...
Страница 221: ...Figure MD 13 Assembly Detail Fan Tray P N 183 8350 Page MD 13 01 January 2002...
Страница 222: ...Figure MD 14 Assembly Detail NAF102 RF Output Filter Top View Page MD 14 01 January 2002...
Страница 223: ...Figure MD 15 Assembly Detail NAF102 RF Output Filter Rear View Page MD 15 01 January 2002...
Страница 224: ...Figure MD 16 Assembly Detail NAFP90 Forward Reflected Power Probe Page MD 16 01 January 2002...
Страница 225: ...Figure MD 17 Assembly Detail NAX161 Static Drain Choke Page MD 17 01 January 2002...
Страница 226: ...Figure MD 18 Assembly Detail NAF101 8 Input RF Combiner Filter Rear View Page MD 18 01 January 2002...
Страница 227: ...Figure MD 19 Assembly Detail NAF101 8 Input RF Combiner Filter Side View Page MD 19 01 January 2002...
Страница 228: ...Figure MD 20 Assembly Detail NAPP02 RF Current Probe PWB Page MD 20 01 January 2002...
Страница 229: ...Figure MD 21 Assembly Detail Capacitive Divider Assembly 176 8253 Page MD 21 01 January 2002...
Страница 230: ...Figure MD 22 Assembly Detail NAX202 04 Surge Arrestor Assembly DWA00 555 Page MD 22 01 January 2002...
Страница 231: ...Figure MD 23 Assembly Detail NASR108 AC DC Power Supply Top View Page MD 23 01 January 2002...
Страница 232: ...Figure MD 24 Assembly Detail NASR105 01 Power Transformer Assembly Page MD 24 01 January 2002...
Страница 233: ...Figure MD 25 Assembly Detail 3 Rectifier UP28 Page MD 25 01 January 2002...
Страница 234: ...Figure MD 26 Assembly Detail NAPS16C DC Power Supply PWB Page MD 26 01 January 2002...
Страница 235: ...Figure MD 27 Assembly Detail NAPI48B DC Power Supply Monitor PWB Page MD 27 01 January 2002...
Страница 236: ...Figure MD 28 Dimensional Information XL12 12 000 Watt AM Broadcast Transmitter Page MD 28 01 January 2002...
Страница 237: ...Figure MD 29 Assembly Dimensional Information NAX165 Circuit Breaker Enclosure Page MD 29 01 January 2002...
Страница 238: ...Figure SD 13 Electrical Schematic RF Combiner Output Filter NAF101A NAF102 Page SD 13 01 January 2002...