Naturela NPBC-V3M-1 Скачать руководство пользователя страница 8

Electronic pellet burner controller - NPBC-V3M-1 / NPBC-V4T-1

Automatic work mode

 

  (

  Auto

 

 ):

By selecting this mode, a choice for the

 

external installation, which is going to be heated by the boiler,

appears:

Work modes with external installations:

CH Priority

  – only the building heating installation works. The circulation pump turns on

when the temperature of the water in the boiler gets higher than the set temperature in the menu
CH   Setup.  The  pump   works   until   the   temperature   of   the   water   gets   lower   than   the   set
temperature. When the room thermostat activates due to reaching the set temperature, the pump
keeps working, but the burner's power starts to decrease with one power level down on time
intervals set from the menu 

Burning Shutdown

. At the end it goes through Suspend mode too

before it turns off. If the room thermostat goes back to its normal condition before the burner is
off, it will continue its work according to the temperature of the water in the boiler. If the room
thermostat is active for longer period (the time for Burning Sh Suspend time has run
out) the burner turns off and will be ignited again after the thermostat gets back to its normal
condition.

DHW Priority

 – the domestic hot water heater (DHW) has a priority in heating. The pump of

the water heater's installation turns on when all of the following conditions are implemented:

The temperature of the water in the boiler is above 35

o

C

The difference between the temperature of the water in the boiler and in the water heater
is above 5

o

C

The temperature of the water in the water heater is lower than the temperature set in the
menu 

DHW Setup

, line 

Set Temp.

 

After reaching the set temperature, the circulation pump turns off and then turns back on again

when the temperature of the water in the water heater gets lower than the difference 

Set Temp

– Hysteresis

 in the menu 

DHW Setup

. When the water heater reaches the set temperature, if

the   room   thermostat   is   activated   from   the   menu  

Addons   Acctivation

,   the   central   heating

installation's pump turns on. In this case, if the room thermostat activates because of reaching
the set temperature and if the temperature of the water in the water heater is higher than  

Set

Temp – Hysteresis

, the burner switches to  

Suspend

  mode. After the set time for Suspend

mode runs out, the burner turns off. It turns on again when the temperature of the water in the
boiler gets lower than the set temperature minus the temperature difference set for the second
power level in the menu  

Burn Level

. The conditions for the circulation pumps of the water

heater or the heating installation should be implemented, as well.

For a  normal  heat  exchange,   the  set temperature  of  the  boiler  must be  at  least  5
degrees higher than the set temperature of the water heater!

If the room thermostat is not activated in the menu 

Addons Activation

, the temperature

in the rooms is considered as not reached and the central heating circulation pump

User Manual / version 2.6

 

http://www.naturela-bg.com/en/

 

page 8 of 28

Содержание NPBC-V3M-1

Страница 1: ...Electronic pellet burner controller NPBC V3M 1 NPBC V4T 1 Electronic Pellet Burner Controller NPBC V3M 1 SOFTWARE VERSION 3 3a 3 2 User Manual version 2 6 http www naturela bg com en page 1 of 28...

Страница 2: ...wer up the FC output during the Intermediate cleaning procedures 4 An option to set time constant for the internal auger motor in addition to its main active time that depends on the fuel auger s acti...

Страница 3: ...additional fan for example for taking out the exhaust gases from the boiler if necessary Both blowers power can be adjusted from the controller NPBC V3M 1 has an option to control the temperature of t...

Страница 4: ...r in the boiler Temperature sensor for the hot water heater High temperature pt100 sensor to measure the temperature of the flue gases This temperature sensor is not used to detect the burning fire bu...

Страница 5: ...Electronic pellet burner controller NPBC V3M 1 NPBC V4T 1 User Manual version 2 6 http www naturela bg com en page 5 of 28...

Страница 6: ...Electronic pellet burner controller NPBC V3M 1 NPBC V4T 1 User Manual version 2 6 http www naturela bg com en page 6 of 28...

Страница 7: ...the work process keeps the set temperature In the work mode field will be shown Auto Programme This mode has additional programming periods of the day when boiler s work is allowed In this mode the b...

Страница 8: ...s above 35o C The difference between the temperature of the water in the boiler and in the water heater is above 5o C The temperature of the water in the water heater is lower than the temperature set...

Страница 9: ...thermostat is not activated in the menu Addons Activation the temperature in the rooms is considered as not reached and the central heating circulation pump works unconditionally Summer Mode the boile...

Страница 10: ...tion which would be turning on On or turning off Off the burner Turning off the controller To turn off the controller press F and choose Standby The screen will take the following view After that an e...

Страница 11: ...if any Error messages can be BB Alarm an alarm from the back burning thermistor Sensor E1 the temperature sensor in the boiler is disconnected or missing Sensor E2 the temperature sensor in the boiler...

Страница 12: ...flame indicator field and the burner goes to burning phase If the pellets do not ignite before the set time is up a new portion of pellets is loaded and a new attempt for ignition is made After as ma...

Страница 13: ...e set differential temperature for the first power level the burner goes to Suspend mode indicated by If the Suspend mode continues longer than the set time for this mode and there is no need of incre...

Страница 14: ...ores the changes made on the current screen Manual control of the feed screw motor Manual Feed By using the up or down arrow keys turn on or off the check box in front of Feed If the check box is chec...

Страница 15: ...e setting Set Time Sets the clock Date setting Set Date Sets the date Contrast Sets the contrast of the LCD display Language Choose the language you prefer for the menus FACTORY SETTINGS Factory setti...

Страница 16: ...arrow buttons or change the value of the currently blinking parameter in the relevant direction the Enter button switches to the next editable parameter the F button saves the changes in the current m...

Страница 17: ...if a back burning alarm has been registered General Setup set the number of ignition attempts Retries the work time of the auger for initial feed Feed and the speed of the Exhaust Fan EFan Ignition cy...

Страница 18: ...r power regulation Set the difference between the set temperature and the boiler temperature for each level 3rd level Setup adjust the work mode for 3rd power level maximum power Set the active time o...

Страница 19: ...e active time of the auger when loading a portion of pellets the cycle time before loading a new portion of pellets and the speed of the fans Settings here are the same as above Smooth extinction of t...

Страница 20: ...et the duration of the procedure from the second parameter on the second line If you want to deactivate the intermediate cleaning procedures set this parameter to 0 You have the option to choose the f...

Страница 21: ...se options If Tstat NO is checked the room thermostat will be with normally opened sockets Burner feeder active time set Burner Feeder adjust the internal auger motor s if any active time It turns on...

Страница 22: ...ter circulation pump DHW Pump Thermostat activates the option to work with a room thermostat External Stop Ext Stop This menu gives an option to use an external stop switch for the burner Connect this...

Страница 23: ...gh In both cases the boiler needs to be cleaned up If the burner doesn t have a high temperature sensor pt100 this function could be disabled by removing the check sign on the row Active The following...

Страница 24: ...ontroller NPBC V3M 1 NPBC V4T 1 Test turning on of the rest of the outputs Test Outputs When a row is checked power is supplied to this output for test purposes User Manual version 2 6 http www nature...

Страница 25: ...0 250 2 General Setup Retries 0 5 3 Feed seconds 1 99 10 EFan speed level 1 100 15 Ignition Cycle Setup Heater seconds 0 600 30 Fan phase 1 speed level 1 100 5 minutes 1 9 2 Fan phase 2 speed level 1...

Страница 26: ...Burning Shutdown 3rd Power Level seconds 10 300 60 2nd Power Level seconds 10 300 60 1st Power Level seconds 10 300 60 Suspend Time Suspend Time minutes 0 180 20 Overheating Max C 0 20 0 Interm Cleani...

Страница 27: ...Electronic pellet burner controller NPBC V3M 1 NPBC V4T 1 NPBC_Monitor exe NPBC V3M monitoring software User Manual version 2 6 http www naturela bg com en page 27 of 28...

Страница 28: ...Electronic pellet burner controller NPBC V3M 1 NPBC V4T 1 SETTING ALL PARAMETERS WITH NPBC_MONITOR EXE User Manual version 2 6 http www naturela bg com en page 28 of 28...

Отзывы: