The remote monitor will respond and indicate various error conditions that may occur under normal operation.
These warnings should be investigated to prevent damage to the batteries or the NLDC-25 system.
The following symbols or messages may appear on any of the 3 display modes :
Warning Messages
LOW BATTERY or NO BATTERY - This symbol is displayed when either the Main or Auxiliary battery voltage is lower than 11.4V
or there is no connection to one of the batteries. Check fuses and connections to both batteries.
If this symbol and voltage display are flashing, the battery is not holding charge and should be tested.
OVER VOLTAGE PROTECTION - The voltage applied to the SOLAR, ALT or AUX terminals is too high.
Ensure the application voltages are within specification.
OVER TEMPERATURE PROTECTION - The detected auxiliary battery temperature is above 50°C. Charging is stopped to
prevent damage to the battery. It is possible that the battery is damaged or is located in an area that is too hot.
This error will also be displayed if the NLDC-25 temperature is above 115°C. Charge will stop until the system temperature drops
to a safe level.
OVER CURRENT PROTECTION - The detected charge current is higher than specification.
Inspect the installation for cable faults or short-circuits.
REVERSE POLARITY - The connections to the auxiliary battery have been reversed.
Check the battery connections.
BAD BATTERY - The NLDC-25 has detected that the AUX battery is not able to be charged safely.
Test the battery and replace if necessary.
OVP -
OTP -
OCP -
REV -
BAD -