![National Instruments SCC-LP Series Скачать руководство пользователя страница 5](http://html.mh-extra.com/html/national-instruments/scc-lp-series/scc-lp-series_user-manual_709424005.webp)
©
National Instruments Corporation
5
SCC-LP Series Lowpass Filter Modules User Guide
The signal source can be floating or ground-referenced. The SCC-LP
XX
input circuitry includes high-impedance bias resistors typically required for
floating sources. Therefore, floating signal sources do not require external
bias resistors connected to ground.
Note
For floating signal sources in high-noise environments, connect the negative
terminal of the signal source to the AI GND terminal on the SC-2345 screw-terminal block
to reduce common-mode noise.
Figure 1.
SCC-LP
XX
Signal Connections
For information about configuring the SCC-LP
XX
module using
NI-DAQmx, refer to the
SCC Quick Start Guide
.
AI (
X
)
AI (
X
+8)
SCC-LP
+
–
E Series DAQ Device
+
–
+
–
+
–
Signal source may be floating or ground-referenced.
10 M
Ω
10 M
Ω
AI SENSE
1
3
4
2
AI GND
Fourth-Order
Butterworth
Lowpass
Filter
1 k
Ω
1 k
Ω
1 k
Ω
1 k
Ω
Fourth-Order
Butterworth
Lowpass
Filter
Signal
Sources