National Instruments Corporation
5
SCC-DO01 Isolated Digital Output Module User Guide
Figure 2.
Connecting a Load R
LOAD2
to V
OUT
and V
SS
(Configuration 2)
Figure 2 shows Configuration 2, with a load R
LOAD2
connected to the V
OUT
and V
SS
terminals and a voltage supply connected to the V
COM
and V
SS
terminals. Connect Configuration 2 to the SCC-DO01 by completing the
following steps:
1.
Remove all power from the signal lines.
2.
Strip 7 mm (0.27 in.) of insulation from the ends of the signal wires.
3.
Insert the wires into the screw terminals.
a.
Connect the negative lead of the voltage supply to screw
terminal 1, V
COM
.
b.
Connect the negative lead from R
LOAD2
to screw terminal 2, V
OUT
.
c.
Connect the positive lead of the voltage supply and the positive
lead from R
LOAD2
to screw terminal 1, V
SS
.
4.
Tighten the screws to 0.5 to 0.6 N
⋅
m (4.4 to 5.3 lb
⋅
in.) of torque.
For information about configuring the SCC-DO01 module using
NI-DAQmx, refer to the
SCC Quick Start Guide
.
3
16
Ω
16
Ω
66.5
Ω
1/2 w
1
V
ss
V
COM
+
–
I
O2
R
LOAD2
V
OUT
5–24 VDC
= External voltage source may be floating or ground-referenced.
+5 V
E Series
SCC-DO01
Status
LED
Power-Up
State Switch
P0.(
X )
D GND
2
Load
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com