Appendix C
Troubleshooting
C-2
ni.com
reference the signal to the same ground level as the device reference. There
are various methods of achieving this reference while maintaining a high
common-mode Rejection Ratio (CMRR). These methods are outlined in
the
Connecting Analog Input Signals
section of Chapter 2,
.
AI GND is an AI common signal that routes directly to the ground
connection point on the devices. You can use this signal if you need a
general analog ground connection point to the device. Refer to the
Differential Connection Considerations
, for more information.
How can I use the AI Sample Clock and AI Convert Clock signals on
an E Series device to sample the AI channel(s)?
E Series devices use the ai/SampleClock and ai/ConvertClock signals to
perform interval sampling. As Figure C-1 shows, ai/SampleClock controls
the sample period, which is determined by the following equation:
1/sample period = sample rate
Figure C-1.
Interval Sample
The ai/ConvertClock signal controls the convert period, which is
determined by the following equation:
1/convert period = convert rate
This method allows multiple channels to be sampled relatively quickly in
relationship to the overall scan rate, providing a nearly simultaneous effect
with a fixed delay between channels.
Channel 0
Channel 1
Convert Period
Sample Period
Содержание PXI-6031E
Страница 1: ...PXI 6031E...
Страница 2: ...DAQ E Series E Series User Manual E Series User Manual February 2007 370503K 01...