Continuous

250 V RMS, Measurement Category II

Withstand

2,300 V RMS, verified by a 5 s dielectric withstand test

NI-9421 with DSUB Safety Voltages

Connect only voltages that are within the following limits:

Channel-to-COM

30 V maximum

Overvoltage protection

40 V maximum

Reverse-biased voltage

-30 V maximum

Isolation

Channel-to-channel

None

Channel-to-earth ground

Continuous

60 V DC, Measurement Category I

Withstand

1,000 V RMS, verified by a 5 s dielectric withstand test

Safety Guidelines for Hazardous Locations

The NI-9421 is suitable for use in hazardous locations; , and hazardous locations;

and nonhazardous locations only. Follow these guidelines if you are installing the

NI-9421 in a potentially explosive environment. Not following these guidelines may

result in serious injury or death.

Caution

 Do not disconnect I/O-side wires or connectors unless power has

been switched off or the area is known to be nonhazardous.

Caution

 Do not remove modules unless power has been switched off or

the area is known to be nonhazardous.

© National Instruments

5

NI-9421 Getting Started

Содержание NI 9421

Страница 1: ...NI 9421 Getting Started 2022 07 06...

Страница 2: ...UB Safety Voltages 5 Safety Guidelines for Hazardous Locations 5 Electromagnetic Compatibility Guidelines 7 Special Conditions for Marine Applications 7 Preparing the Environment 7 Connecting the NI 9...

Страница 3: ...ion du produit de toute autre fa on que celle sp cifi e risque de l endommager et de compromettre la protection de s curit int gr e Safety Guidelines for Hazardous Voltages If hazardous voltages are c...

Страница 4: ...haute tension dangereuse est appliqu e aux bornes du produit vous devez vous assurer que les appareils et les circuits auxquels il est connect sont correctement isol s de tout contact humain Caution Y...

Страница 5: ...by a 5 s dielectric withstand test Safety Guidelines for Hazardous Locations The NI 9421 is suitable for use in hazardous locations and hazardous locations and nonhazardous locations only Follow these...

Страница 6: ...I 9421 is marked and is suitable for use in Zone 2 hazardous locations in ambient temperatures of 40 C Ta 70 C If you are using the NI 9421 in Gas Group IIC hazardous locations you must use the device...

Страница 7: ...ception and prevent unacceptable performance degradation install and use this product in strict accordance with the instructions in the product documentation Furthermore any changes or modifications t...

Страница 8: ...e You must use 2 wire ferrules to create a secure connection when connecting more than one wire to a single terminal on the NI 9421 with screw terminal or NI 9421 with spring terminal NI 9421 Signals...

Страница 9: ...applies a voltage or drives a current that is in the input OFF range to DI If no device is connected to DI the channel registers as OFF LED Indications Each channel has an LED that indicates the stat...

Страница 10: ...earn about NI service offerings such as calibration options repair and replacement Visit ni com register to register your NI product Product registration facilitates technical support and ensures that...

Отзывы: