Continuous
60 VDC, Measurement Category I
Withstand
1,000 Vrms, verified by a 5 s dielectric withstand test
Note
Measurement Categories CAT I and CAT O are equivalent. These test
and measurement circuits are for other circuits not intended for direct
connection to the MAINS building installations of Measurement Categories
CAT II, CAT III, or CAT IV.
Safety Guidelines for Hazardous Locations
The NI-9264 is suitable for use in hazardous locations; , and hazardous locations;
and nonhazardous locations only. Follow these guidelines if you are installing the
NI-9264 in a potentially explosive environment. Not following these guidelines may
result in serious injury or death.
Caution
Do not disconnect I/O-side wires or connectors unless power has
been switched off or the area is known to be nonhazardous.
Caution
Do not remove modules unless power has been switched off or
the area is known to be nonhazardous.
Caution
Substitution of components may impair suitability for Class I,
Division 2, or Zone 2.
Caution
The system must be installed in an enclosure certified for the
intended hazardous (classified) location, having a tool secured cover/door,
where a minimum protection of at least IP54 is provided.
Caution
For Division 2 and Zone 2 applications, connected signals must
be within the following limits.
© National Instruments
5
NI-9264 Getting Started