NI-9238 in a potentially explosive environment. Not following these guidelines may
result in serious injury or death.
Caution
Do not disconnect I/O-side wires or connectors unless power has
been switched off or the area is known to be nonhazardous.
Caution
Do not remove modules unless power has been switched off or
the area is known to be nonhazardous.
Caution
Substitution of components may impair suitability for Class I,
Division 2, or Zone 2.
Caution
The system must be installed in an enclosure certified for the
intended hazardous (classified) location, having a tool secured cover/door,
where a minimum protection of at least IP54 is provided.
Special Conditions for Hazardous Locations Use in Europe and
Internationally
The NI-9238 has been evaluated as Ex nA IIC T4 Gc equipment under
DEMKO 12ATEX 1202658X and is IECEx UL 14.0089X certified. Each NI-9238 is marked
II 3G and is suitable for use in Zone 2 hazardous locations, in ambient
temperatures of -40 °C ≤ Ta ≤ 70 °C. If you are using the NI-9238 in Gas Group IIC
hazardous locations, you must use the device in an NI chassis that has been
evaluated as Ex nC IIC T4, Ex IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.
Caution
Transient protection shall be provided that is set at a level not
exceeding 140% of the peak rated voltage value of 85 V at the supply
terminals to the equipment.
Caution
The system shall only be used in an area of not more than
Pollution Degree 2, as defined in IEC/EN 60664-1.
© National Instruments
5
NI-9238 Getting Started
Содержание NI-9238
Страница 1: ...NI 9238 Getting Started 2022 07 06 ...