NI 9235/9236
4
ni.com
Caution
S
u
bstit
u
tion of components may impair
s
u
itability for Class I, Division 2.
Caution
For Zone 2 applications, install the system
in an enclos
u
re rated to at least IP 54 as defined by
IEC 60529 and EN 60529.
Caution
For Zone 2 applications, connected signals m
u
st
be within the following limit:
Capacitance .......................... 0.2
μ
F max
Special Conditions for Hazardous Locations Use in Europe
This eq
u
ipment has been eval
u
ated as Ex nA IIC T4 eq
u
ipment
u
nder DEMKO Certificate No. 07 ATEX 0626664X. Each mod
u
le
is marked
II 3G and is s
u
itable for
u
se in Zone 2 hazardo
u
s
locations. If yo
u
are
u
sing the NI 9235/9236 in Gas Gro
u
p IIC
hazardo
u
s locations or in ambient temperat
u
res of
–40 °C
≤
Ta
≤
70 °C, yo
u
m
u
st
u
se the device in an NI chassis
that has been eval
u
ated as EEx nC IIC T4, Ex nA IIC T4, or
Ex nL IIC T4 eq
u
ipment.