background image

Troubleshooting Network Communication

If the MON-10496 does not connect to NI InsightCM with a status of Online, try the following
troubleshooting tips:

Check the Ethernet cable connections on the MON-10496, server, and router.

If you have network firewalls or other security software enabled, try temporarily turning
them off. You might also need to add an exception for NI InsightCM by completing the
following steps:
1.

Navigate to the standard Microsoft Windows Control Panel utility for managing
firewall settings.

2.

Click 

Allow a program or feature through Windows Firewall

.

3.

Click 

Allow another program

.

4.

Select NI InsightCM and click 

Add

.

5.

Click 

OK

 and close the firewall settings.

Ensure that the ports are open to communication on the server. If you are using an
intelligent switch on the network, ensure that the switch is not disabling these ports. Refer
to the 

NI InsightCM Readme

 on 

ni.com/manuals

 for more information about server ports.

If you have multiple network cards on the server, ensure that you use the Windows
Control Panel to disable all other network adapters, such as wireless adapters. Turning off
the wireless antenna is insufficient.

Battery Replacement and Disposal

Note

 

The following information applies to the internal sbRIO-9607.

This device contains a long-life coin cell battery for the RTC. If you need to replace the battery
or return the device to NI, use the Return Material Authorization (RMA) process or contact an
authorized NI service representative. Go to 

ni.com/r/10496battery

 for more information about

replacing the battery. If you return the device to NI, you shall also be responsible for using
sufficient protective packaging in accordance with all applicable laws and transportation
requirements. Visit 

ni.com/contact

 or call (866) 275-6964 for more information on the RMA

process.

16

  | 

ni.com

  | 

MON-10496 User Guide

Содержание MON-10496

Страница 1: ...USER GUIDE MON 10496 Wireless Monitoring Gateway MON 10496 Note Read the MON 10496 Safety Environmental and Regulatory Information document on ni com manuals before installing ...

Страница 2: ... Door 8 Mounting 8 Installing the Antenna and Boot 9 Connecting 10 Wiring Guidelines 10 Connecting the Ethernet Cable 11 Connecting Power and Ground 12 Using the Desiccant Kit 14 Network Connection 15 Troubleshooting Network Communication 16 Battery Replacement and Disposal 16 Where to Go Next 17 Product Certifications and Declarations 17 Worldwide Support and Services 17 Related Documentation The...

Страница 3: ...t Contents 1 2 3 4 5 6 1 MON 10496 2 MON 10496 Safety Environmental and Regulatory Information 3 NI Monitoring Devices Card 4 1 Antenna with weather protective boot 5 1 M16 Gland 6 1 PG16 Gland What You Need to Get Started Hardware needed M6 to M8 bolts and nuts or 1 4 in to 5 16 in bolts and nuts Washers recommended M16 gland supplied by NI PG16 gland supplied by NI or 0 5 in conduit fitting 2 mm...

Страница 4: ...aution The protection provided by the MON 10496 can be impaired if it is used in a manner not described in the user documentation Attention La protection apportée par le MON 10496 risque d être endommagée s il est utilisé d une autre façon que celle décrite dans la documentation utilisateur Caution An external circuit breaker box must be installed according to applicable electrical codes by traine...

Страница 5: ...iques applicables et au couple spécifié par le fabricant Caution Ensure that hazardous voltage wiring is performed only by qualified personnel adhering to local electrical standards Attention Les raccords de conduits ou presse étoupe doivent être installés par du personnel qualifié conformément aux normes électriques applicables et au couple spécifié par le fabricant EMC Notices Refer to the follo...

Страница 6: ...s Diagrams Exterior Parts Diagram MON 10496 1 2 3 3 3 3 2 6 5 4 1 Antenna 2 Mounting flanges 3 Captive screws 4 M16 gland for Ethernet cable 5 PG16 gland for power cable 6 Door 6 ni com MON 10496 User Guide ...

Страница 7: ...battery which is a lithium cell battery that stores the system clock information when the MON 10496 is powered off Only a slight drain on the RTC battery occurs when power is applied to the MON 10496 power connector The rate at which the RTC battery drains when power is disconnected depends on the ambient storage temperature For longer battery life store the MON 10496 at a cooler temperature and a...

Страница 8: ... 1 Loosen the four captive screws on the door of the device with a 1 4 in socket or 6 mm 1 4 in flat blade screwdriver 2 Open the door of the device slowly 3 Clean the gasket and gasket mating surface with a dry or damp cloth prior to closing the device door 4 Close the door slowly 5 Tighten the four captive screws on the door of the device to 1 3 N m 11 5 lb in Mounting The MON 10496 must be moun...

Страница 9: ...ice against the surface on which you want to mount it 2 Insert bolts into the mounting holes placing at least two bolts on each flange You must use at least four bolts in total to secure the device but may use more than four for additional security 3 Optional place washers between the bolt and the flange and or between the mounting structure and nuts as needed 4 Place nuts onto the bolts and tight...

Страница 10: ...o the device and tighten to a torque of 0 45 N m 4 lb in 4 Slide the large boot down the antenna to the base 5 Press the large boot into place to create a snug seal Connecting Wiring Guidelines Adhere to the following guidelines when wiring the MON 10496 Caution Before opening the MON 10496 for service you must turn off the external power to the device and use the external breaker box to completel...

Страница 11: ...ls to make sure that any devices you connect to the MON 10496 are compatible Connecting the Ethernet Cable Figure 3 CAT5e Ethernet Port Pinout 1 2 3 4 5 6 7 8 Table 1 Signal Descriptions Pin Fast Ethernet Signal Gigabit Ethernet Signal 1 TX TX_A 2 TX TX_A 3 RX RX_B 4 No Connect TX_C 5 No Connect TX_C 6 RX RX_B 7 No Connect RX_D 8 No Connect RX_D Hardware needed CAT5e Ethernet cable RJ45 connector ...

Страница 12: ...the appropriately sized grommet for your cable The M16 gland comes with a pre installed gray 2 mm to 6 mm grommet and an additional black 4 mm to 8 mm grommet For optimum sealing and strain relief only use wiring with a round circular and smooth exterior cable jacket 6 Terminate the RJ45 connector to the Ethernet cable and plug it into the Ethernet port 7 Tighten the M16 dome nut to a torque of 2 ...

Страница 13: ...e backing nut on the PG16 gland and tighten the nut with a 30 mm socket or wrench to a torque of 5 N m 44 2 lb in while holding the gland body with a 27 mm deep socket 3 If you are using a cable that has external metal armor or braid terminate the external armor or braid so that it does not pass through the gland grommet to ensure that the gland can seal properly around the smooth round inner cabl...

Страница 14: ... provide strain relief and weather resistance for the cable Using the Desiccant Kit If your application is outdoors non weather protected according to IEC 60721 3 4 or if the device might be directly exposed to an outdoor climate partially weather protected according to IEC 60721 3 3 3K4 or greater you must use a desiccant pack from the desiccant kit part number 787006 10 to meet the humidity spec...

Страница 15: ... not blocked by the pocket door or Mylar folding on itself 6 Clean the gasket and gasket mating surface prior to closing the device door 7 Close the door slowly 8 Tighten the four captive screws on the door of the device to 1 3 N m 11 5 lb in Network Connection The first time you power up the MON 10496 it attempts to initiate a DHCP network connection If the MON 10496 cannot initiate a DHCP connec...

Страница 16: ...h is not disabling these ports Refer to the NI InsightCM Readme on ni com manuals for more information about server ports If you have multiple network cards on the server ensure that you use the Windows Control Panel to disable all other network adapters such as wireless adapters Turning off the wireless antenna is insufficient Battery Replacement and Disposal Note The following information applie...

Страница 17: ...y compliance information To obtain product certifications and the DoC for NI products visit ni com product certifications search by model number and click the appropriate link Worldwide Support and Services The NI website is your complete resource for technical support At ni com support you have access to everything from troubleshooting and application development self help resources to email and ...

Страница 18: ...ements EULAs and third party legal notices in the readme file for your NI product Refer to the Export Compliance Information at ni com legal export compliance for the NI global trade compliance policy and how to obtain relevant HTS codes ECCNs and other import export data NI MAKES NO EXPRESS OR IMPLIED WARRANTIES AS TO THE ACCURACY OF THE INFORMATION CONTAINED HEREIN AND SHALL NOT BE LIABLE FOR AN...

Отзывы: