Chapter 3
Connector and Cabling
©
National Instruments Corporation
3-7
NI-FBUS Hardware and Software User Manual
Fieldbus H1 Pinout Information
The FBUS-HSE/H1 LD can be one of up to 32 devices connected to a
Fieldbus H1 network. The connection is made through one of the two 9-pin
male D-SUB Fieldbus H1 connectors on the FBUS-HSE/H1 LD, shown in
Figure 3-9.
Use a Fieldbus cable with a 9-pin female D-SUB connector to connect the
FBUS-HSE/H1 LD to a properly terminated Fieldbus network. When you
are only using an FBUS-HSE/H1 LD, the power hub is not being used for
power. For other F
OUNDATION
™
Fieldbus devices that use bus powering, you
would apply power to the hub, from which devices would get their power.
Refer to the Fieldbus Foundation
Wiring and Installation 31.25 kbit/s,
Voltage Mode, Wire Medium Application Guide
for specific information
about wiring and installing a Fieldbus network. If you want to make your
own Fieldbus cable, refer to the
Fieldbus Standard for Use in Industrial
Control Systems, Part 2, ISA-S50.02.1992
. The FBUS-HSE/H1 LD
Fieldbus connector pinout is shown in Figure 3-9.
Figure 3-9.
FBUS-HSE/H1 LD Connector Pinout
1
2
3
4
5
6
7
8
9
NC
NC
NC
NC
NC
NC
NC
Data +
Data –
NC = No Connection