background image

FP-AI-110 and cFP-AI-110

2

ni.com

To install the FP-AI-110, refer to Figure 1 and complete the 
following steps:

1. Slide the terminal base key to either position X (used for any 

module) or position 1 (used for the FP-AI-110).

2. Align the FP-AI-110 alignment slots with the guide rails on the 

terminal base.

3. Press firmly to seat the FP-AI-110 on the terminal base. When 

the FP-AI-110 is firmly seated, the latch on the terminal base 
locks it into place.

Figure 1.  

Installing the FP-AI-110

Installing the cFP-AI-110

The cFP-AI-110 mounts on a Compact FieldPoint backplane 
(cFP-BP-

x

), which provides operating power to the module. 

Installing the cFP-AI-110 onto a powered backplane does not 
disrupt the operation of the FieldPoint bank.

To install the cFP-AI-110, refer to Figure 2 and complete the 
following steps:

1. Align the captive screws on the cFP-AI-110 with the holes on 

the backplane. The alignment keys on the cFP-AI-110 prevent 
backward insertion. 

2. Press firmly to seat the cFP-AI-110 on the backplane.

3. Using a number 2 Phillips screwdriver with a shank of at least 

64 mm (2.5 in.) length, tighten the captive screws to 1.1 N

1

I/O Module

2

Terminal Base

3

Alignment Slot

4

Key

5

Latch

6

Guide Rails

1

3

2

4

5

6

Содержание FieldPoint FP-AI-110

Страница 1: ...l Instruments FP AI 110 Manual Get Pricing Availability at ApexWaves com Call Today 1 800 915 6216 Email sales apexwaves com https www apexwaves com modular systems national instruments fieldpoint FP...

Страница 2: ...nalog input module with the following features Eight analog voltage or current input channels Eight voltage input ranges 0 1 V 0 5 V 0 10 V 60 mV 300 mV 1 V 5 V and 10 V Three current input ranges 0 2...

Страница 3: ...10 The cFP AI 110 mounts on a Compact FieldPoint backplane cFP BP x which provides operating power to the module Installing the cFP AI 110 onto a powered backplane does not disrupt the operation of th...

Страница 4: ...ions Each channel has separate input terminals for voltage VIN and current IIN input Voltage and current inputs are referenced to the COM terminals which are internally connected to each other and to...

Страница 5: ...d the cFP CB x connector blocks Caution Do not connect both current and voltage inputs to the same channel Caution Cascading power between two modules defeats isolation between those modules Cascading...

Страница 6: ...hannel Figure 3 FP AI 110 Analog Input Circuit Measuring Voltage with the c FP AI 110 The input ranges for voltage signals are 0 1 V 0 5 V 0 10 V 60 mV 300 mV 1 V 5 V and 10 V Figure 4 shows how to co...

Страница 7: ...e module reads current flowing into the IIN terminal as positive and current flowing out of the terminal as negative Current flows into the IIN terminal goes through a 100 resistor and flows out from...

Страница 8: ...urce with External Power Supply Input Ranges To prevent inaccurate readings choose an input range such that the signal you are measuring does not exceed either end of the range VSUP VIN V C To Analog...

Страница 9: ...the rate at which the c FP AI 110 samples the inputs The c FP AI 110 resamples all of the channels at the same rate If you set all of the channels to the 50 or 60 Hz filter the c FP AI 110 samples eac...

Страница 10: ...e you need and how to upgrade your firmware go to ni com info and enter fpmatrix Isolation and Safety Guidelines Caution Read the following information before attempting to connect the c FP AI 110 to...

Страница 11: ...tages the V and C terminals with other devices including other FieldPoint devices unless those devices are isolated from human contact For Compact FieldPoint you must connect the protective earth PE g...

Страница 12: ...ollow these guidelines if you are installing the c FP AI 110 in a potentially explosive environment Failing to follow these guidelines may result in serious injury or death Caution Do not disconnect I...

Страница 13: ...an accessible circuits on the same module Caution Make sure that devices and circuits connected to the module are properly insulated from human contact Caution When terminals on the connector block ar...

Страница 14: ...age 60 mV 300 mV 1 V 5 V 10 V 0 1 V 0 5 V 0 10 V 65 mV 325 mV 1 04 V 5 2 V 10 4 V 0 1 04 V 0 5 2 V 0 10 4 V 3 V 16 V 40 V 190 V 380 V 20 V 95 V 190 V 25 V 100 V 300 V 1 500 V 3 000 V 300 V 1 500 V 3 0...

Страница 15: ...ut Range Typical Accuracy at 15 to 35 C of Reading of Full Scale Warranted Accuracy at 15 to 35 C of Reading of Full Scale 60 mV 0 04 0 05 0 05 0 3 300 mV 0 04 0 015 0 06 0 1 1 V 0 04 0 008 0 05 0 04...

Страница 16: ...z filter 0 3 A rms Typical and warranted accuracy by temperature range Offset error drift 100 nA C Gain error drift 40 ppm C 0 1 V 0 06 0 025 0 10 0 12 0 5 V 0 07 0 007 0 11 0 03 0 10 V 0 07 0 005 0 1...

Страница 17: ...ls Environmental FieldPoint modules are intended for indoor use only For outdoor use they must be mounted inside a sealed enclosure Operating temperature 40 to 70 C Storage temperature 55 to 85 C Humi...

Страница 18: ...boratory use IEC 61010 1 EN 61010 1 UL 61010 1 CAN CSA C22 2 No 61010 1 For UL hazardous location and other safety certifications refer to the product label or visit ni com certification search by mod...

Страница 19: ...latory compliance information To obtain the DoC for this product visit ni com certification search by model number or product line and click the appropriate link in the Certification column Mechanical...

Страница 20: ...alling instructions or dial 512 795 8248 For telephone support outside the United States contact your local branch office Australia 1800 300 800 Austria 43 0 662 45 79 90 0 Belgium 32 0 2 757 00 20 Br...

Страница 21: ...o the Terms of Use section on ni com legal for more information about National Instruments trademarks Other product and company names mentioned herein are trademarks or trade names of their respective...

Отзывы: