9

Specifications

Network ports ................................... 1 RS-232 port, 1 RS-485 

repeater port

Baud Rates ........................................ 300, 1200, 2400, 9600, 

19200, 38400, 57600, 
115200 (switch selectable)

Communication parameters .............. 1 start bit, 8 data bits, 

1 stop bit, No parity

RS-485 isolation ............................... 2500 Vrms breakdown, 

250 Vrms operational

Power Consumption.......................... 1 W + 1.15

 * 

(I/O module 

power requirements

)

Operating Temperature..................... -40° C to +70° C

Storage Temperature......................... -55° C to +100° C 

Relative Humidity............................. 5% to 90% non-condensing 

Weight............................................... 250 g (8.7 oz.)

CE Mark Compliance 

This product meets applicable EU directive(s) as follows:

Safety isolation  ................................ EN 61010 (double insulation 

for 250 Vrms working
isolation, installation 
category II)

EMC Directive

Immunity .................................... EN 50082-1:1994
Emissions  .................................. EN 55011:1991 Group I 

Class A at 10 meters

FP1000.fm  Page 9  Thursday, July 31, 1997  8:49 AM

Содержание FieldPoint FP-1000

Страница 1: ...in high efficiency power supply powers I O modules 40 to 70 C operation Overview The FP 1000 is a network module for the FieldPoint system It provides connection to an RS 232 network using a simple A...

Страница 2: ...teps 1 With a flat bladed screwdriver open the rail clip to the unlocked position as shown in Figure 1 Figure 1 DIN Rail Clip 2 Hook the lip on the rear of the FP 1000 onto the top of a 35 mm DIN rail...

Страница 3: ...installed FP 1000 network module Figure 3 Installed Network Module Network Connection Connect the FP 1000 to a host computer using the 9 position DSub RS 232 connector on the FP 1000 Connect the RS 2...

Страница 4: ...01 modules and the TX of the FP 1000 must be connected to the RX of all of the FP 1001 modules This pair of connections provides communication from the host computer through the FP 1000 to the FP 1001...

Страница 5: ...dule Switches 1 5 set the network address and switches 6 8 set the baud rate Every network module connected to one serial port of the host computer must be given a unique address however modules on di...

Страница 6: ...k Address Switch Settings Switch Positions 1 5 Network Module Address Decimal Switch Positions 1 5 Network Module Address Decimal 0 130 10 140 20 150 30 160 40 170 50 180 60 190 1 2 3 4 5 6 7 8 1 2 3...

Страница 7: ...ud Rate 300 19200 1200 38400 2400 57600 9600 115200 Table 1 Network Address Switch Settings Continued Switch Positions 1 5 Network Module Address Decimal Switch Positions 1 5 Network Module Address De...

Страница 8: ...inals provided on each terminal base for such power supply connections The power connector is a 4 pin screw terminal connector whose pinout is shown in Figure 8 Figure 8 FP 1000 and FP 1001 Power Conn...

Страница 9: ...ational Power Consumption 1 W 1 15 I O module power requirements Operating Temperature 40 C to 70 C Storage Temperature 55 C to 100 C Relative Humidity 5 to 90 non condensing Weight 250 g 8 7 oz CE Ma...

Страница 10: ...10 Mechanical Dimensions Figure 9 shows the mechanical dimensions of the FP 1000 Figure 9 Mechanical Dimensions 4 31 109 5 3 58 90 9 4 19 106 4...

Страница 11: ......

Страница 12: ......

Отзывы: