4. Add terminal bases to the DIN rail with their local bus 

connectors firmly mated to the FP-1000 local bus connector. 
The FP-1000 is shipped with a protective cover over the local 
bus connector. Remove this protective cover, and place it over 
the local bus connector of the last terminal base in the stack. 
Figure 3 shows an installed FP-1000 network module.

Figure 3.  

Installed Network Module

Network Connection

Connect the FP-1000 to a host computer using the 9-position DSub 
RS-232 connector on the FP-1000. Connect the RS-232 port of the 
FP-1000 to the RS-232 port on your computer using a male-to- 
female “straight-through” cable. Do not use a “null modem” cable 
(usually female-to-female). For reference, the pinout of the 
RS-232 connector on the FP-1000 is shown in Figure 4.

Protective

Cover

Local Bus Connectors

Firmly Mated

Rail Snap

Locked

DIN
Rail

FP1000.fm  Page 3  Thursday, July 31, 1997  8:49 AM

Содержание FieldPoint FP-1000

Страница 1: ...in high efficiency power supply powers I O modules 40 to 70 C operation Overview The FP 1000 is a network module for the FieldPoint system It provides connection to an RS 232 network using a simple A...

Страница 2: ...teps 1 With a flat bladed screwdriver open the rail clip to the unlocked position as shown in Figure 1 Figure 1 DIN Rail Clip 2 Hook the lip on the rear of the FP 1000 onto the top of a 35 mm DIN rail...

Страница 3: ...installed FP 1000 network module Figure 3 Installed Network Module Network Connection Connect the FP 1000 to a host computer using the 9 position DSub RS 232 connector on the FP 1000 Connect the RS 2...

Страница 4: ...01 modules and the TX of the FP 1000 must be connected to the RX of all of the FP 1001 modules This pair of connections provides communication from the host computer through the FP 1000 to the FP 1001...

Страница 5: ...dule Switches 1 5 set the network address and switches 6 8 set the baud rate Every network module connected to one serial port of the host computer must be given a unique address however modules on di...

Страница 6: ...k Address Switch Settings Switch Positions 1 5 Network Module Address Decimal Switch Positions 1 5 Network Module Address Decimal 0 130 10 140 20 150 30 160 40 170 50 180 60 190 1 2 3 4 5 6 7 8 1 2 3...

Страница 7: ...ud Rate 300 19200 1200 38400 2400 57600 9600 115200 Table 1 Network Address Switch Settings Continued Switch Positions 1 5 Network Module Address Decimal Switch Positions 1 5 Network Module Address De...

Страница 8: ...inals provided on each terminal base for such power supply connections The power connector is a 4 pin screw terminal connector whose pinout is shown in Figure 8 Figure 8 FP 1000 and FP 1001 Power Conn...

Страница 9: ...ational Power Consumption 1 W 1 15 I O module power requirements Operating Temperature 40 C to 70 C Storage Temperature 55 C to 100 C Relative Humidity 5 to 90 non condensing Weight 250 g 8 7 oz CE Ma...

Страница 10: ...10 Mechanical Dimensions Figure 9 shows the mechanical dimensions of the FP 1000 Figure 9 Mechanical Dimensions 4 31 109 5 3 58 90 9 4 19 106 4...

Страница 11: ......

Страница 12: ......

Отзывы: