Full scale is the maximum value of the nominal
input range.
Gain error drift .................................. 7.4 ppm/°C
Offset error drift................................ 3
V/°C
Physical Characteristics
Indicators .......................................... Green
POWER
and
READY
indicators
Weight ............................................... 117 g (4.1 oz)
Warm-up time ................................... 30 minutes
Power Requirements
Power from network module ............ 1.125 W
0–1 V
0.037%;
0.0115%
0.111%;
0.0624%
0–5 V
0.037%;
0.0035%
0.071%;
0.0137%
0–10 V
0.037%;
0.0025%
0.066%;
0.0076%
0–15 V
0.037%;
0.0022%
0.065%;
0.0056%
Input Range with
Overranging
Typical Accuracy
at –40
°
C to 70
°
C
(% of Reading;
% of Full Scale)
Warranted Accuracy
at – 40
°
C to 70
°
C
(% of Reading;
% of Full Scale)
1.05 V
0.081%;
0.0345%
0.168%;
0.1437%
5.25 V
0.081%;
0.0093%
0.148%;
0.0312%
10.5 V
0.081%;
0.0062%
0.145%;
0.0171%
15.75 V
0.081%;
0.0051%
0.144%;
0.0124%
0–1.05 V
0.081%;
0.0329%
0.193%;
0.1422%
0–5.25 V
0.081%;
0.0078%
0.153%;
0.0297%
0–10.5 V
0.081%;
0.0047%
0.148%;
0.0156%
0–15.75 V
0.081%;
0.0036%
0.146%;
0.0109%
Nominal
Input Range
Typical Accuracy
at 15
°
C to 35
°
C
(% of Reading;
% of Full Scale)
Warranted Accuracy
at 15
°
C to 35
°
C
(% of Reading;
% of Full Scale)