![National Instruments 6527 Скачать руководство пользователя страница 19](http://html2.mh-extra.com/html/national-instruments/6527/6527_programmers-manual_3433890019.webp)
Chapter 2
Register Map and Descriptions
6527 Register-Level Programmer Manual
2-10
ni.com
Master Interrupt Control Register
The Master Interrupt Control Register enables change detection interrupts. To select the line
to use for changes, use the Rising Edge Detection and Falling Edge Detection Registers.
Address Offsets:
15 (hex)
Type:
Read and write
Size:
8-bit
Bit Map:
Bit
Name
Description
7–5
Reserved
Write only zeroes to these bits.
4
FallingEdgeIntEnable
Interrupt Enable control. Enable interrupt on falling edge
detection. This is enabled upon power-up.
1 = Interrupt enabled
0 = Interrupt disabled
3
RisingEdgeIntEnable
Interrupt Enable control. Enable interrupt on rising edge
detection. This is enabled upon power-up.
1 = Interrupt enabled
0 = Interrupt disabled
2
MasterInterruptEnable
Interrupt Enable control. Enable master interrupt.
1 = Interrupt enabled
0 = Interrupt disabled
7
6
5
4
3
2
1
0
Reserved
Reserved
Reserved
Falling
EdgeInt
Enable
Rising
EdgeInt
Enable
Master
Interrupt
Enable
Overflow
IntEnable
EdgeInt
Enable