Installation Manual for Comfort Pack

 

Electric Units

Safety First!

“USE COPPER SUPPLY WIRES ONLY”

HIGH VOLTAGE!

DISCONNECT ALL POWER BEFORE SERVING. 

FAILURE TO DO SO MAY RESULT IN PROPERTY 

DAMAGE, PERSONAL INJURY OR DEATH.

!

WARNING

SCROLL COMPRESSORS SHOULD NEVER BE USED TO 

EVACUATE THE AIR CONDITIONING SYSTEM. VACUUMS 

THIS LOW CAN CAUSE INTERNAL ELECTRICAL ARCING 

RESULTING IN A DAMAGED OR FAILED COMPRESSOR.

!

WARNING

!

WARNING

!

CAUTION

USE CARE WHEN HANDLING SCROLL COMPRESSORS. 

SOME TEMPERATURES COULD BE HOT!

!

CAUTION

INSTALLATION AND REPAIR OF THIS UNIT SHOULD 

BE PERFORMED ONLY BY INDIVIDUALS MEETING THE 

REQUIREMENTS OF AN “ENTRY LEVEL TECHNICIAN” 

AS SPECIFIED BY NATIONAL CODES. ATTEMPTING 

TO INSTALL OR REPAIR THIS UNIT WITHOUT SUCH 

BACKGROUND MAY RESULT IN PRODUCT DAMAGE, 

PERSONAL INJURY OR DEATH.

THE UNIT MUST BE PERMANENTLY GROUNDED. 

FAILURE TO DO SO CAN CAUSE ELECTRICAL 

SHOCK RESULTING IN SEVERE PERSONAL INJURY  

OR DEATH.

!

WARNING

FOR YOUR SAFETY, DO NOT STORE OR USE GASOLINE 

OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE 

VICINITY OF THIS OR ANY OTHER APPLIANCE. SUCH 

ACTIONS COULD RESULT IN PROPERTY DAMAGE, 

PERSONAL INJURY, OR DEATH.

THESE UNITS ARE NOT APPROVED FOR MOBILE 

HOME APPLICATIONS. SUCH USE COULD RESULT IN 

PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH.

!

CAUTION

THESE INSTRUCTIONS ARE INTENDED AS AN AID TO 

QUALIFIED, LICENSED SERVICE PERSONNEL FOR 

PROPER INSTALLATION, ADJUSTMENT AND OPERATION 

OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY 

BEFORE ATTEMPTING INSTALLATION OR OPERATION. 

FAILURE TO FOLLOW THESE INSTRUCTIONS MAY 

RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, 

SERVICE OR MAINTENANCE POSSIBLY RESULTING 

IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, 

PERSONAL INJURY OR DEATH.

!

WARNING

DO NOT USE OXYGEN TO PURGE LINES OR PRESSURIZE 

SYSTEM FOR LEAK TEST. OXYGEN REACTS VIOLENTLY 

WITH OIL, WHICH CAN CAUSE AN EXPLOSION 

RESULTING IN SEVERE PERSONAL INJURY OR DEATH.

!

WARNING

Operation

The cabinet includes open-wire resistance heating elements 

with automatic reset thermal overloads, as well as branch 

circuit fuses for short-circuit and electrical overload 

protection. 

*CPE4XX00-U Models Do Not Include Heating Elements

The Comfort Pack is designed to be used with residential 

single-stage cooling two-stage heating wall thermostats 

with automatic or manual mode changeover. Automatic 

changeover thermostats must include a deadband to 

prevent cycling between cooling and heating modes. 

Single-

pole, single-throw thermostats are not suitable for use 

with Comfort Pack

. The unit also contains controls to 

automatically adjust the indoor blower motor speed for 

cooling and heating modes. 

Each unit is equipped with 2 electrical heat banks with the 

exception of the 15kw model which has 3 banks:

APPROXIMATE  

COLD RESISTANCE

3kw

2 Banks           30.4 ohms per bank

5kw  2 Banks           20.8 ohms per bank
7kw  2 Banks           14.81 ohms per bank

10kw 2 Banks           10.4 ohms per bank
15kw  3 Banks           10.4 ohms per bank

Содержание CPE Series

Страница 1: ...This manual must be left with the homeowner for future reference National Comfort Products A Division of National Refrigeration and Air Conditioning Products Inc 539 Dunksferry Road Bensalem PA 19020...

Страница 2: ......

Страница 3: ...e 11 Maintenance page 12 Dimensional Drawing page 13 Electric Data Performance Data page 14 Comfort Pack Electric CFM Temperature Rise page 15 Air Flow page 15 U 0 Wiring Schematic 0 kw page 18 U 3 Wi...

Страница 4: ...Universal Chassis Edition Generation Nominal Cooling Capacity 11 12 000Btu 17 18 000Btu 23 24 000Btu A No Grille B Slotted Filter Door C No Grille with Slotted Filter Door Heating Capacity Electric 0...

Страница 5: ...CE PERSONNEL FOR PROPER INSTALLATION ADJUSTMENT AND OPERATION OFTHISUNIT READTHESEINSTRUCTIONSTHOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN...

Страница 6: ...elay Once W1 W2 or G is energized the fan will be operated Once de energized the fan will run for an additional 5 seconds Faults If multiple inputs are received with a cooling input Y than the board w...

Страница 7: ...SECONDARY DRAIN THROUGH GROMMET OF CHASSIS AND CONNECT TO FLEXIBLE TUBING PRIME TRAP PRIOR TO OPERATING INSTALL THE LOWER ACCESS PANEL ON THE CABINET TURN ON POWER TO THE UNIT ALL phases of this insta...

Страница 8: ...ure proper drainage and allow chassis removal The drain line should pitch downward at least 1 per 10 ft to an open building drain trap SECONDARY DRAIN TRAP MUST BE INSTALLED Drain Pan 3 4 I D Flexible...

Страница 9: ...iods of rain and wind the primary drainage path may not be adequate to handle the load Secondary precautions may also be required but not limited to the following Seal flashing to unit Floor drain Add...

Страница 10: ...C22 1 In addition the installer should be aware of any local ordinances or utility company requirements that might apply Check the rating plate for the supply voltage and current requirements A dedica...

Страница 11: ...nd that the service provided by the utility is sufficient to handle the additional load imposed by this equipment Power wiring must comply with national state and local codes Follow instructions on un...

Страница 12: ...and do not require routine service The refrigeration system is sealed and factory charged with R 410A so that routine maintenance is not required The electrical controls do not require routine service...

Страница 13: ...ion Manual for Comfort Pack Electric Units Comfort Pack Dimension Drawing Option B Slotted Filter Door for Open Returns 43 26 57 64 7 15 16 31 13 32 7 21 32 1 1 64 28 15 13 16 Side view 3 3 4 7 43 64...

Страница 14: ...30 CPE41107 U 208 230 60 1 4 7 29 5 1 4 2 4 1 3 3 0 38 8 35 3 40 40 CPE41110 U 208 230 60 1 4 7 29 5 1 4 2 4 1 3 3 0 53 8 48 9 55 50 CPE41700 U 208 230 60 1 6 5 37 5 1 4 1 8 3 6 1 3 3 0 13 13 15 15 CP...

Страница 15: ...80 29 2 520 32 6 450 37 7 380 44 6 Black 4 550 30 8 500 33 9 430 39 4 340 49 9 240 70 6 Orange 5 415 40 9 325 52 2 225 75 4 n a n a n a n a CPE41707 Red 1 780 21 7 770 22 0 760 22 3 725 23 4 680 24 9...

Страница 16: ...80 35 8 520 40 0 450 46 2 380 54 7 Black 4 550 37 8 500 41 6 430 48 3 340 61 1 240 86 6 Orange 5 415 50 1 325 63 9 225 92 3 n a n a n a n a CPE41707 Red 1 780 26 6 770 27 0 760 27 3 725 28 7 680 30 6...

Страница 17: ...715 690 660 620 560 Blue 3 620 580 520 450 380 Black 4 550 500 430 340 240 Orange 5 415 325 225 X X CPE417 Red 1 780 770 760 725 680 Yellow 2 715 690 660 620 560 Blue 3 620 580 520 450 380 Black 4 55...

Страница 18: ...18 Installation Manual for Comfort Pack Electric Units U 00 Wiring Schematic 0Kw...

Страница 19: ...19 Installation Manual for Comfort Pack Electric Units U 3 Wiring Schematic Electric Heat 3 5 7 10Kw...

Страница 20: ...20 Installation Manual for Comfort Pack Electric Units U 3 Wiring Schematic Electric Heat 15Kw...

Страница 21: ...12 Fuse Panel 14693031 14693030 14693029A Top Mount Angle 14256101 Control Board Wiring 14299001 14299002 Upper Intake Grille 14256438 Control Board 14262041 Lower Discharge Grille 14256437 Contactor...

Страница 22: ...25397 TXV 14275100 14275117 14275118 Outdoor Fan Motor 14270057 14270044 14270057 Outdoor Coil Mount 14256430 14256434 Drier 14275947 Outdoor Fan 14214042 Outdoor Motor Mount 14270101 Indoor Blower Mo...

Страница 23: ...Reading between Terminals C R __________ 5 Compressor Winding OHM Reading between Terminals R S __________ 6 Compressor Winding OHM Reading between Terminals C Ground __________ 7 Compressor Winding O...

Страница 24: ...to the goods and are in lieu of and exclude all other warranties express or implied arising by operation of law or otherwise including without limitation merchantability and fitness for a particular p...

Страница 25: ...ure shall render the warranty void B Compressors In addition to the above referenced requirements Customer is also required to purchase a replacement compressor and return the original compressor to N...

Страница 26: ...26 Installation Manual for Comfort Pack Electric Units Notes...

Страница 27: ...27 Installation Manual for Comfort Pack Electric Units Notes...

Страница 28: ...TING A C EQUIPMENT NATIONAL COMFORT PRODUCTS National Comfort Products A Division of National Refrigeration Air Conditioning Products Inc 539 Dunksferry Road Bensalem PA 19020 1 800 523 7138 Fax 215 6...

Отзывы: