National Comfort Product 1000 SERIES Скачать руководство пользователя страница 2

c. Braze the liquid line to the service valve.  Allow the ni-

    trogen to keep flowing when brazing the refrigerant 

    line until all brazed joints are completed.

d. Carefully remove the rubber plugs from the evaporator

    liquid and vapor connections.  Use caution as the   

 

    evaporator is pressurized.

e. Braze the liquid line to the evaporator liquid connection

f.  Braze the vapor line to the evaporator vapor connection

g. Provide a heat sink to the vapor line service valve of

    the condensing unit

h. Braze the vapor line to the service valve

5.  When tubing installation is completed, seal openings around 

tubing where tubing enters the unit cabinet.

6.  Standard refrigeration piping practices must be employed 

when installing traps.  When installing the condenser be-

low the evaporator, the suction line must be trapped with 

an inverted trap the height of the evaporator coil.  Consult 

the factory when total equivalent length of refrigerant lines 

exceed 50 ft.

Leak checking of refrigerant line braze joints and evapora-

tor unit using dry nitrogen.

1.  Install service port cap of the vapor line service valve (cap 

was removed for brazing operations).

2.  Connect dry nitrogen source to the service port of the liquid 

line service valve.  Pressurize refrigerant lines and indoor 

coil to approximately 100 PSIG.

3.  Check for leaks using a liquid soap solution. If any leaks are 

located, purge the nitrogen, repair the leak(s) and repeat 

the leak check procedure.

Leak checking of refrigerant line braze joints and evapora-

tor unit using R410a refrigerant.

1.  Connect R410a source to the service port of the liquid line 

service  valve.  Use  of  a  manifold  gauge  set  will  facilitate 

connecting and disconnecting of the refrigerant source for 

leak checking. Pressurize refrigerant lines and indoor coil 

with refrigerant gas.

2.  Leak check with a electronic leak detector or liquid soap so-

lution. If any leaks are detected, use a refrigerant recovery 

system  to  remove  the  refrigerant.  Repair  the  leak(s)  and 

repeat the leak check procedure.

Step 2 - Installing Refrigerant Lines

When replacing a R-22 system, it is recommended, that new 

Line Sets be used. If the old line sets are to be used, they 

MUST be flushed with a commercial flushing agent. R410A 

refrigerant oil, is not compatible with R-22 oil. The indoor 

coil MUST be replaced and a TXV MUST be used.

Important:

The outdoor unit is fully charged at the factory for the recom-

mended model of indoor unit. With other models of indoor units 

the charge must be adjusted.  Be sure both service valves are 

closed during tubing installation and leak checking to avoid loss 

of charge. 

For indoor units with a TXV, a liquid line filter drier 

must be installed (SPORLAN #083-S or similar)

.

1.  The unit has internally mounted service valves.  Field tub-

ing may be routed through the locations provided in either 

the top or rear flange. Care should be taken not to block ac-

cess to internal components.  Seal unused knockouts with 

high  grade  sealant.    Gaskets  are  provided  for  liquid  and 

suction lines.

NOTE:

  Always use refrigeration grade copper tubing that

is internally clean and dry for refrigerant lines. Use clean

hard drawn copper tubing if no appreciable amount of 

bending is necessary.  If soft copper is used, avoid sharp

bends which may cause a restriction.  Always use heat

sink materials during brazing to prevent damage to service

valves (

see Figure 1

).

2.  Run  refrigerant  lines  as  directly  as  possible.  Field  piping 

inside the condensing unit should not block access to ma-

jor  components.  Refrigerant  lines  should  not  be  in  direct 

contact with the floor or ceiling joists. Use insulated or sus-

pension type hangers. When refrigerant lines run through a 

wall, seal openings around the lines with a flexible material 

to avoid vibration to the structure.

3.  Insulate the vapor line with a minimum 1/2” foam rubber or 

other type insulation having an adequate vapor barrier. 

For 

indoor units with a TXV, a liquid line filter drier must be 

installed (SPORLAN #C-083-S or similar)

.

Caution: Dry nitrogen should always be supplied through 

the tubing while it is being brazed, as the high temperature 

required for brazing will cause oxidation of the copper un-

less an inert atmosphere is provided. The flow of dry nitro-

gen should continue until the joints have cooled. Always 

use  a  pressure  regulator  and  safety  valve  to  ensure  that 

only  low  pressure  nitrogen  is  introduced  into  the  tubing. 

Only a small flow is necessary to displace air and prevent 

oxidation.

4.  Install  the  refrigerant  lines  using  the  following  procedure 

(

see also: Figure 1

).

a. Remove the service port caps and Schrader Cores of

    the liquid line service valve and the vapor line service

    valve of the condensing unit.  Connect low pressure dry

    nitrogen to the liquid line valve service port.

b. Provide a heat sink at the service valve such as  

    wrapping a wet rag around it, to prevent damage 

    during the brazing operation

Step 3 - Leak Checking

2

Содержание 1000 SERIES

Страница 1: ...Wall Installation If the optional wall sleeve is used caulk the spaces between the sleeve and the wall Completely fill the clearance between the unit and the wall sleeve with a polyurethane foam seala...

Страница 2: ...fully charged at the factory for the recom mended model of indoor unit With other models of indoor units the charge must be adjusted Be sure both service valves are closed during tubing installation...

Страница 3: ...alloy is used Step 5 This is not a back seating valve To open the valve re move the valve cap with an adjustable wrench Insert a 3 16 or 5 16 hex wrench into the stem Back out counter clockwise until...

Страница 4: ...into the system NOTE Oil charge is polyester 32bce 3 When the correct refrigerant charge level is obtained remove the manifold gauge set 4 Replace the gauge port caps Permanently stamp the unit data...

Страница 5: ...or tight ness balance and rust or corrosion 8 Inspect wire connection for evidence of arcing overheating and deterioration Sequence of Operations for Madison Avenue Option Step 7 Maintenance The compr...

Страница 6: ...6 Wiring Schematic NCPD XXX 1010 D NCPD XXX 3010 D Bristol Compressor MODEL CAPACITOR NCPD 418 30ufd 370VAC NCPD 424 35ufd 370VAC NCPD 430 35ufd 370VAC...

Страница 7: ...7 Wiring Schematic NCPE XXX 1010 NCPE XXX 3010 NCPE XXX 4010 Copeland Compressor MODEL CAPACITOR NCPE 418 30ufd 370VAC NCPE 424 35ufd 370VAC NCPE 430 40ufd 370VAC...

Страница 8: ...8 Wiring Schematic NCPE XXX 1010 D NCPE XXX 3010 D NCPE XXX 4010 D Copeland Compressor NCPE 430 XXXX D MODEL CAPACITOR NCPE 418 30ufd 370VAC NCPE 424 35ufd 370VAC NCPE 430 40ufd 370VAC...

Страница 9: ...9 Wiring Schematic NCPD XXX 1010 D NCPD XXX 3010 D Bristol Compressor MODEL CAPACITOR NCPD 418 30ufd 370VAC NCPD 424 35ufd 370VAC NCPD 430 35ufd 370VAC...

Страница 10: ...10 Wiring Schematic NCPD XXX 4010 NCPDXXX 4010 Bristol Compressor MODEL CAPACITOR NCPD 418 30ufd 370VAC NCPD 424 35ufd 370VAC NCPD 430 35ufd 370VAC...

Страница 11: ...11 Wiring Schematic NCPE XXX 4010 Bristol Compressor MODEL CAPACITOR NCPE 418 30ufd 370VAC NCPE 424 35ufd 370VAC...

Страница 12: ...12 Wiring Schematic NCPE XXX 4010 D 30uFd 350VAC Bristol Compressor MODEL CAPACITOR NCPE 418 4010 D 30ufd 370VAC NCPE 424 4010 D 35ufd 370VAC...

Страница 13: ...4 20 208 230 60 1 12 14 4 20 208 230 60 1 12 14 8 25 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 6 5 43 7 3 48 8 0 43 9 1 58 3 10 0 64 RLA Amps LRA Amps FAN MOTOR 0 25 1500 1 4...

Страница 14: ...08 230 60 1 12 14 4 20 208 230 60 1 12 14 4 20 208 230 60 1 12 14 8 25 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 6 5 43 7 3 48 8 0 43 9 1 58 3 10 64 RLA Amps LRA Amps FAN MOT...

Страница 15: ...208 230 60 1 14 10 2 15 208 230 60 1 12 14 4 20 208 230 60 1 12 14 8 25 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 6 5 43 7 3 48 9 1 58 3 10 0 64 RLA Amps LRA Amps FAN MOTOR...

Страница 16: ...P 1500 RPM 14 Prop Fan Motor Mount Access Panel 1000 Top Panel 1000 Right Side Panel Left Side Panel Wire Grille 1000 Radial Fan Mount Touch Up Paint 14208360 14270049 14214033 14270102 14256318 14256...

Страница 17: ...Access Panel 1000 Top Panel 1000 Right Side Panel Left Side Panel Wire Grille 1000 Radial Fan Mount Touch Up Paint 14208361 14270049 14214033 14270102 14256318 14256316 14256315 14256343 14256001A 142...

Страница 18: ...8 9 10 11 12 13 14 15 16 17 18 Outdoor Coil Motor 0 25 HP 1500 RPM 14 Prop Fan Motor Mount Access Panel 3000 Top Panel 3000 Right Side Panel Left Side Panel Wire Grille 3000 Radial Fan Mount Touch Up...

Страница 19: ...Mount Access Panel 3000 Top Panel 3000 14208356 14270049 14214033 14270102 14256305 14256303 14208357 14270049 14214033 14270102 14256305 14256303 14208357 14270049 14214033 14270102 14256305 14256303...

Страница 20: ...23 Outdoor Coil Motor 0 25 HP DC DC Motor Control Blower Wheel 7 6 x 8 0 Blower Housing Inlet Ring 2 req d Motor Blower Mount Access Panel 4000 Top Panel 4000 Right Side Panel Left Side Panel Wire Gri...

Страница 21: ...h Up Paint 14208359 14270049 14214033 14256102 14256332 14256335 14256338 14256337 14269004A 14256339 14299630 14208358 14270049 14214033 14256102 14256332 14256335 14256338 114256337 14269004A 142563...

Страница 22: ...22...

Страница 23: ...equire that defective parts be returned to verify and identify the cause of the defect LIMITATION OF WARRANTIES ALL IMPLIED WARRANTIES INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY ARE HEREBY LIMITE...

Страница 24: ...24...

Страница 25: ...a replacement compressor to be shipped from Bensalem PA The situation may present itself where it is better for the compressor to be returned to National Comfort Products during the 20 month Bristol w...

Страница 26: ...26...

Страница 27: ...eamless rifled copper tubes CABINET Unit cabinet shall be constructed of heavy gauge galvanized or aluminized steel The steel shall be treated by phosphate washes prior to electrostatically applied an...

Страница 28: ...NCPD E Split System Condensing Unit Installation Instructions Rev 08 11 2014...

Отзывы: