Increase the time value ramp Q=0 parameter (Installer Parameters
value).
DOL pump stops and starts continuously
Increase
delta start pressure
in accordance with chapter 9.1.
Check to see if the water tank and it’s air pressure are correctly set. It
may be necessary to increase the tank volume or reduce the pre-charge
pressure.
Measured pressure p_mis drops too
much before VASCO starts the pump.
Decrease the delta start pressure (Installer Parameters menu) .
Check to see if the water tank and it’s air pressure are correctly set. It
may be necessary to increase the tank volume or reduce the pre-charge
pressure.
Modify the value of ki & kp parameters (Installer Parameters menu).
At first, it is suggestable to reduce the Ki value. If it is not enough
increase of one unit the Kp value.