30
Slave setup
Follow Master setup until point 11.
In case of failure of master in a Combo system, will be replaced by slave. As a consequence, all parameters must be setup
independently on each inverter, master mode.
1.
Set:
VASCO’s address in parallel operation.
01 --> 07: VASCO slaves
2.
Press STOP (red button).
3.
In the
advanced parameters
verify that
Autorestart
is set
ON.
4.
Press STOP (red button).
5.
Press STOP again.
Whenever the user accesses the Menu screen of the VASCO master, the communication between VASCOs is automatically
interrupted.
In case of alarm or failure of a pump in a Combo system, this pump’s operation will be replaced (temporary or
permanently) by another pump.
In case of failure of master in a Combo system, it will be replaced by the next slave. As a consequence of this, all
parameters must be setup independently on each inverter as master mode.
10. Trouble-shooting chart
LCD does not switch on after powering
the VASCO
Check the connecting flat cable between the LCD board (attached to the
cover) and the control board
Check the fuses
Check that the power cables are properly connected.
Power line of VASCO is interrupted by
the differential protection contactor
Check the leakage current to ground of EMC filter
Following a rapid off/on the power supply, the differential contactor can
interrupt the power. After turning off the VASCO it is recommended to
wait at least 1 minute before restarting.
When performing the Offset operation
of the pressure device, SENS.PRESS.OFF
alarm occurs
Check that the sensor cable is properly connected to the sensor device
and to the VASCO.
Make sure that the sensor and its cable are not damaged.
Check that the operating range of pressure sensor is of 4 -20 mA type
and the value of 15 V is within the voltage feed range of the sensor
Frequency and pressure oscillation on
constant pressure control mode
Check if the water tank and its air pressure are correctly set. It may be
necessary to increase the tank volume or reduce the pre-charge
pressure.
Check the ki & kp parameters (Installer Parameters menu). At first, it is
suggestable to increase the Ki value. If it not enough reduce of one unit
the Kp value.
During constant pressure control, pump
stops and starts continuously.
Make sure that the value f min Q=0 (minimum frequency with Q=0)
(Installer Parameters menu) is properly set up. Otherwise repeat the
procedure.
Increase the value of parameter stop delay (Installer Parameter menu)
Address