PM-22 PUMP MONITOR MANUAL

The    PM-22  Series  is  a  variety  of  pump  monitors 
designed  to  protect  single-phase  pumps  from  dry-
well, dead-head, jammed impeller, waterlogged tanks, 
r a p i d   c y c l i n g ,   u n d e r / o v e r     v o l t a g e   a n d 
over/underload. It includes an LCD display that shows 
the voltage, current, power consumption and faults. 
The  trip  point  is  user-adjustable  and  it  also  features 
automatic  calibration  allowing  adjustments  for 
speci c  pumping  applications,  reducing  the 
possibility  of    false  or  nuisance  tripping.  A  unique 
microcontroller-based  sensing  circuit  constantly 
monitors the power and line voltage for  uctuations.
When  a  fault  is  detected  the  PM-22  after  the  trip 
delay—  will  turn  off  the  pump  . The  user  can  select 
automatic  or  manual  reset,  when  automatic  reset  is 
selected the PM -22 will turn on the pump after the 
restart delay (delay is user -adjustable). 
The  PM-22  has  an  internal  contactor  capable  of 
starting motors up to 1.5 HP.

Description

Wiring

The  PM-22  is  used  in  single  phase  pumps  with  a 
current consumption in the range of 4 to 15 Amps. This 
unit should be mounted  in a convenient location in or 
near  the  pump  control  box.  If  the  location  is  wet  or 
dusty a NEMA 3R, 4, or 12 enclosure should be used.

The  PM-22  must  be  protected  by  a  fuse  or  circuit 
breaker to avoid any damage.  The following diagrams 
show  how  to  connect  the  PM-22  depending  on  the 
supply voltage available:

120VAC SUPPLY VOLTAGE 

Features

Ÿ

Protects pumps from dry-well, dead-
head, jammed impeller, waterlogged 
tanks, rapid cycling, under /over 
voltage, and over/underload.

Ÿ

Starts motors up to 1.5 HP without the 
need of an external contactor.  

Ÿ

Stores faults on memory.

Ÿ

LCD displays: Line voltages, current, 
power, failures, time delays, and a 
setup menu.

Ÿ

Auto calibration. 

Ÿ

Manual or automatic reset.

 CB = CIRCUIT BREAKER OR FUSE 
    CA = CONTROL CONTACT      

DANGER!

Potentially hazardous voltages are present. Electrical 

shock can cause death or serious injury.

Installation should be done by qualified personnel 

following all National, State & Local Codes.

BE SURE TO REMOVE ALL POWER SUPPLYING THIS 

EQUIPMENT BEFORE CONNECTING OR DISCONNECTING 

THE WIRING.

READ THE INSTRUCTIONS BEFORE INSTALLING OR 

OPERATING THIS DEVICE.

 KEEP THIS MANUAL FOR FUTURE REFERENCE.

The contact “CA” could be a pressure or float switch, a 
manual switch or any other control used to start/stop 
the pump automatically or manually.

120 VAC

PUMP

CB

CA

T1

S1     

TC

SC

T2   

S2

PUMP-MONITOR     

220 VAC SUPPLY VOLTAGE 

220 VAC

PUMP

CB

CA

T1

S1     

TC

SC

T2   

S2

PUMP-MONITOR     

 CB = CIRCUIT BREAKER OR FUSE 
    CA = CONTROL CONTACT      

PM-22 PUMP MONITOR MANUAL ENGLISH 2018

viernes, 4 de octubre de 2019 10:45:09 a. m.

Содержание PM-22

Страница 1: ...INCE 1973 PUMP MONITOR MODEL PM 22 www nassarelectronics com The best solutions for automation and protection User Manual PM 22 PUMP MONITOR MANUAL ENGLISH 2018 viernes 4 de octubre de 2019 10 45 06 a m ...

Страница 2: ...osureshouldbeused The PM 22 must be protected by a fuse or circuit breaker to avoid any damage The following diagrams show how to connect the PM 22 depending on the supplyvoltageavailable 120VACSUPPLYVOLTAGE Features Ÿ Protects pumps from dry well dead head jammed impeller waterlogged tanks rapid cycling under over voltage and over underload Ÿ Starts motors up to 1 5 HP without the need of an exte...

Страница 3: ...rify that the pump is running normally i e the system is pumping water and the motor current is normal Try to achieve the maximum water flow rate Calibration on a fully recovered well is recommended The calibration may be repeated to assure that setup was done when the pump was running under normal conditions SET RESET DELAY 60 Min SET RESET MANUAL SET UNDER LOAD UL 2312 W Setup Press the SETUP bu...

Страница 4: ...reen This is useful when the system presents considerable load variation and the automatic calibrationvaluesneedtobeadjusted AUTOMATICRESET After a failure has occured except under over voltage the PM 22 will start to count down the time set on the restart delay if the automatic reset is enabled The pump will restart when the timer finishes RESET DELAY 6 MIN LEFT The display shows the time left to...

Страница 5: ...howninthegraphicbelow 100 125 150 175 200 225 250 275 5 10 15 20 25 OVERLOAD TRIP DELAY Sec OVER LOAD TRIP DELAY The overload trip point is set to 125 of the power consumption during automatic calibration but it can alsobe adjustedmanually UNDERVOLTAGEPROTECTION The PM 22 protects the motor if the voltage drops from normal conditions It shuts down the motor after a 5 s trip delay The under voltage...

Страница 6: ...justmentseasier Ifthisunit ispanelmounted thepanelneedstobeinstalledindoors Din rail mounting Mounting hole Mounting hole Mounting options Dimensions This unit can be mounted on a standard 35 mm DIN rail or screwed into a surface using the screws included in the package Enclousure Dimensions 5 7 x 4 1 x 2 4 in PM 22 PUMP MONITOR MANUAL PM 22 PUMP MONITOR MANUAL ENGLISH 2018 viernes 4 de octubre de...

Страница 7: ... by this limited warranty and shall be at the buyer s expense All costs of dismantling reinstallationandfreight andthetimeandexpensesshallbebornebythebuyer LIMITATIONOFREMEDYANDLIABILITY NASSAR ELECTRONICS SHALL NOT BE LIABLE FOR DAMAGES CAUSED BY DELAY IN PERFORMANCE THE REMEDIES OFTHE BUYER SET FORTH IN THIS AGREEMENT ARE EXCLUSIVE IN NO EVENT REGARDLESS OF THE FORM OF THE CLAIM OR CAUSE OF ACTI...

Отзывы: