NARVI Oy Finland NC 16 Скачать руководство пользователя страница 6

Yrittäjäntie 14, FI-27230 Lappi  •  tel. +358 0207 416 740  •  fax +358 0207 416 743  •  www.narvi.fi/en

6

GB

Protecting a wall made of combustible material

Figure 3

. If the sauna heater is installed on a floor made of 

combustible materials, an installation base must be used. 
A piece of sheet metal must be installed in front of the in-
stallation  base,  which  extends  at  least  100  mm  over  the 
sides of the heater hatch and at least 400 mm in front of 
the sauna heater. The sheet metal edges facing the sauna 
heater must be turned up, so that coal cannot get under 
the installation base.

The safety clearance of an uninsulated flue from the 
structures made of combustible materials is 1000 mm 
from the sides and 1200 mm from the top.

2.3.2 Non-combustible structure

If the wall is masonry or other structure classified as non-
combustible, it is sufficient to have a 50 mm air gap be-
tween the upright surfaces and the wall.

2.4 Smoke flue

A smoke flue of the sauna heater must meet the require-
ments of class T600 irrelevant of the material of the smoke 
flue. The minimum recommended draft of the smoke flue 
is 12 Pa. 

A modular smoke flue must meet the requirements of class 
T600  and  provided  with  CE-marking.  When  installing  a 
modular smoke flue safety clearances stipulated in the in-
stallation manual of the smoke flue shall be followed. The 
minimum recommended diameter of a modular smoke flue 
is 120 mm. The weight of the smoke flue must not cause 
load on the sauna heater. The sauna heater should be con-
nected  to  a  separate  smoke  flue.  A  smoke  flue  made  of 
bricks must be at least the so-called half-brick smoke flue.

2.5 Ventilation

Ventilation  of  the  steam  room  should  be  sufficiently  effi-
cient and should function so that fresh incoming air is rout-
ed as close to the sauna heater as possible. Also proper 
air circulation has to be provided in the steam room during 
using the sauna so that air can exit from under the sauna 
bench or from under the door of the washing room (suf-
ficient gap).

Extraction  fans  working  in  the  same  room  as  the  firebox 
may cause problems. Incoming air inlets should be located 
so that they do not get blocked (for instance because of 
snow). A firebox needs combustion air in a volume of 6–10 
m3  per  kilo  of  fired  wood.  The  diameter  of  the  ventila-
tion opening must be at least 100 mm. Forced air system 
should be built according to the design prepared by the 
designer of the heating, water and ventilation systems.

After using the sauna there shall be a possibility to ventilate 
and dry the sauna rooms so that air exits via the upper part 
of the steam room.

Figure 3.

Содержание NC 16

Страница 1: ...GB Made by NARVI Oy Finland Narvi NC 16 20 20 VS 24 sauna heaters Installation user and maintenance instructions Version 1 0...

Страница 2: ...Yritt j ntie 14 FI 27230 Lappi tel 358 0207 416 740 fax 358 0207 416 743 www narvi fi en 2 GB...

Страница 3: ...ation of the height 7 3 3 Connection with the smoke flue 7 3 4 Installation of a door and changing of the opening direction of the door 7 3 5 Installation of a water tank faucet models with a water ta...

Страница 4: ...e sauna heater preferably on the lower part of the cover of the sauna heater Do not heat the sauna heater if you lack sufficient knowl edge if you are not allowed to use a sauna because of your health...

Страница 5: ...R UN DERFLOOR HEATING A Kota installation base must be installed under the sauna heater which will protect the floor moisture barrier and un derfloor heating pipes or cables from the thermal radiation...

Страница 6: ...When installing a modular smoke flue safety clearances stipulated in the in stallation manual of the smoke flue shall be followed The minimum recommended diameter of a modular smoke flue is 120 mm The...

Страница 7: ...ue is done from the above a Kota connective flue or Kota smoke flue must be used In case of connection from the above a Kota smoke flue tank for heating water or a Kota stone basket can be installed a...

Страница 8: ...es Before using the stones they must be washed to eliminate any impurities Bigger stones are placed in the bottom of the stone compartment and the rest are piled sparsely so that air can move freely b...

Страница 9: ...from above reduces pollution and ensures cleaner burning The power of the sauna heater can be regulated by the ash drawer If the ash drawer is closed the power of the sauna heater is at its lowest and...

Страница 10: ...n the stones of the sauna heater to dry the sauna room In the ignition phase the closing pan must be fully open Before you close the closing pan after heating check that there is no glowing coal in th...

Страница 11: ...se installation and maintenance meet the requirements stipulated in the instructions The warranty period starts form the moment that the goods are delivered to the end user The supplier is not liable...

Страница 12: ...t i e nominal space heating output Back Side Ceiling 150 mm 150 mm 1 250 mm Pass Pass NPD Pass Pass 0 07 Pass 70 12 Pa 16 kW 7 kg Pass Pass 387 C Narvi Oy 12 EN 15821 2010 Multi firing sauna stoves fi...

Отзывы: