SILENT ROOM | Troubleshooting
Power issues
There is no electricity in the pod (power outlet, fans and lights are not working)
A
A
C
B
B
C
D
Check if the control box power switch is ON (see control
box layout
c
).
Check if the control box AC power cord is connected
(see control box layout
a
).
Check if the power cord is connected to a power outlet
properly.
There is no electricity in the power outlet (lights and ventilation are working)
Check if the power outlet AC cord is connected to the power OUT socket of the control box properly (see control
box layout
b
).
Fans and lights issues
Lights and (or) ventilation are not working (power outlet is working)
Check DIP switch (see control box layout
f
). Depending on the SILENT ROOM model, it should be adjusted as follows:
SILENT ROOM S
SILENT ROOM M
SILENT ROOM L
Check if control box J5 – J9
connectors are secured with
dedicated DC cords (see control
box layout
j, k
).
Check if there are no PIR faults (see
control box layout
n, o
).
Check if ceiling DC cords are connected with control box DC cords as pictured below:
E
PIR connection
Light connection
Ventilation connection
Check if the J1 connector of
the control box is secured with
dedicated cord (see control box
layout
g
).
SILENT ROOM XL