background image

Narada Power Source Co., Ltd.                                                                                      12REXC operation manual V1.0         

15 

3 Charging current limited: 0.05C

10

A; 

4 Cut-off condition: the charging current is less than 0.005C

10

 with another 

extended 3 hours or charging time reached 24 hours (alternative); 

 

Recharging procedure   

1

 Connect the batteries in series with cables or copper bars, and make sure that all 

the screws tightened with each joint, then connect the anode of battery group to the 

anode  of  charging  equipment  (charger),  and  the  cathode  of  battery  group  to  the 

cathode of charger.   

Pay  attention:  A  breaker  or  fuse  should  be  connected  in  the  circuit  in  order  to 

protect  the  batteries  and  charger,  the  capacity  of  breaker  or  fuse  should  be  1.5 

times of circuit maximum current. 

Turn  on  the  charger,  set  the  charging  voltage  and  current  according  to  4.1 

recharging parameter. 

Turn the breaker or fuse, and then turn on the charger to recharging batteries. 

4

 Stop  charging when  reaching the  cut-off condition.  At the last  one hour before 

finishing, test the battery voltage one by  one, the battery  which voltage is below 

2.16V/cell should be dealt with  the method in chapter 3.3, if that battery  can not 

accord with the requirement, it should be rejected. 

 

Cycle procedure   

We can use the method as below to recharge the batteries after long time storage 

(for example: more than 1 year): 

First connect the batteries in series to the charger, discharge batteries with constant 

current  0.25C

10 

(A)  for  about  3  hours.  Then  use  the  method  above  to  charge  the 

batteries. Stop charging when reach the cut-off condition. 

If the capacity still can not be renewed by this method, this means the batteries fail 

because of long time storage or other reasons.   

4.4 Maintenance of wind/solar generating energy storage system   

It is necessary to recharge one time every two months for maintenance because of the 

under-filling state of the batteries used in home energy storage system and wind/solar 

generating  energy  storage  system.  The  battery  maintenance  method  can  operate  as 

below: 

In the case of mains supply, the maintenance and battery recharge methods be the same 

as clause 4.1. 

Содержание 12REXC200

Страница 1: ...LEAD CARBON BATTERY OPERATION MANUAL Version V1 0 NARADA POWER SOURCE CO LTD 12REXC Series Series...

Страница 2: ...d Carbon Working Principle 6 Chapter Two Technical characteristic 7 1 Discharge Curve and Discharge Data 7 2 Charge Curve 8 3 Internal Resistance and Short Circuit Current 8 Chapter Three Operation an...

Страница 3: ...reat harms to environment and heath Please check local laws and regulations to get the validity handle ways or send the equipment to authorized service center The replacement of battery can only be do...

Страница 4: ...erformance Reduce sulfation of the negative plate longer cycle life 1 1 Design life is above 20 years Grid alloy with special patented formula Special patented negative paste formula 4BS paste technol...

Страница 5: ...vide up to 8 class shockproof Streamline and dime light battery outside looking design 2 Main applications Home energy storage system Hybrid energy system such as solar and wind energy Distributed ene...

Страница 6: ...XC300 2 250 300 338 227 281 294 61 5 Lead Carbon Working Principle Fig 1 2 Lead carbon battery working principle sketch map It forms a new active center in negative electrode by adding active carbon t...

Страница 7: ...e vent hydrogen over potential gassing on the negative plate which prevents generation of hydrogen Otherwise the oxygen generated from positive diffuses through separator to the negative and the oxyge...

Страница 8: ...Internal Resistance and Short Circuit Current The internal resistance of the battery is a dynamic nonlinear parameter that is continuously changed along with the temperature and discharge state The i...

Страница 9: ...mpensate Ratio With Floating Voltage mV cell 3 3 Temperature Compensate Ratio With Equalization Voltage mV cell 5 5 High Temperature Warning 35 35 Short circuit protection current A Please refer to ta...

Страница 10: ...e Actual Capacity is the actual output capacity in certain discharge conditions which is equal to product of the discharge current and the discharge time the unit is AH The actual capacity is effected...

Страница 11: ...in best conditions If the floating voltage is higher the floating current is also higher it will accelerate the corruption of grids and shorten the life of the battery If the floating voltage is lowe...

Страница 12: ...Float Voltage V cell 15 2 350 2 275 20 2 325 2 260 25 2 300 2 245 30 2 275 2 230 35 2 250 2 215 40 2 225 2 200 3 2 Ambient temperature vs Battery Life The high temperature will damage the battery red...

Страница 13: ...to test battery conductance and resistance data at different stage with same type instruments from same factory Conductance and resistance data is only a reference to judge whether battery is good Th...

Страница 14: ...o change to equalization charge equalization voltage is recommended The charge time is 24 hours We can also setup the charge voltage according to different DOD different charge current shown in figure...

Страница 15: ...At the last one hour before finishing test the battery voltage one by one the battery which voltage is below 2 16V cell should be dealt with the method in chapter 3 3 if that battery can not accord w...

Страница 16: ...e when another necessary supplementary charge should be made The quality certificates of 12REXC series batteries record the latest charge time of the batteries next charge time can be calculated accor...

Страница 17: ...he end voltage is also an important parameter for battery The battery shall stop discharge when reach a certain voltage The normal end voltage is 1 8Vpc for 10 hours rated If the end voltage is too lo...

Страница 18: ...1 0 18 Annex 1 VRLA Battery Regular Maintenance Record Type Place Status Number of battery Total Voltage V Current A Temperature No Voltage V No Voltage V 1 13 2 14 3 15 4 16 5 17 6 18 7 19 8 20 9 21...