background image

12

W415-0619 / A /08.09.07

Closing the air shutter will cause a more yellow 

fl

 ame, but can 

lead to carboning. Opening the air shutter will cause a more 
blue 

fl

 ame, but can cause 

fl

 ame lifting from the burner ports. 

The 

fl

 ame may not appear yellow immediately; allow 15 to 30 

minutes for the 

fi

 nal 

fl

 ame colour to be established.

NOTE:  It is important that the venturi sits down tight on 
the ori

fi

 ce.  The burner is adjustable up/down to ensure 

this.

ADJUSTMENTS

GAS PRESSURE ADJUSTMENT

VENTURI ADJUSTMENT

TURN OFF THE GAS AND ELECTRICAL POWER BEFORE 

SERVICING THE FIREPLACE.

CAUTION:

 Label all wires prior to disconnection when 

servicing controls. Wiring errors can cause improper and 
dangerous operation. Verify proper operation after servicing. 
This 

fi

 replace and its venting system should be inspected 

before use and at least annually by a quali

fi

 ed  service 

person. The 

fi

 replace area must be kept clear and free of 

combustible materials, gasoline or other 

fl

 ammable vapours 

and liquids. The 

fl

 ow of combustion and ventilation air must 

not be obstructed.

1.

 Keep the control compartment, burner, and air shutter

opening clean by vacuuming or brushing, 

at least once a

year

.

2.

 

Check to see that the main burner ignites when the

switch for the burner is turned on. A 5 second light-up
period is satisfactory. If ignition takes longer, consult your
Napoleon® dealer / distributor.

3.

 

Check that the gasketing on the sides, top and bottom of

the door is not broken or missing. Replace if necessary.

MAINTENANCE

FIGURE 24

AIR SHUTTER OPENINGS

LP

5/16” DIA  (x2)

NG

3/16” DIA  (x1)

Outlet pressure can be adjusted if not measuring 3.5” W.C. 
(NG) or 10.0” W.C. (LP).

1. 

 Pressure can be checked by removing cap (A) using 

a 3/16 allen key and replacing it with a 1/8 NPT barb 

fi

 tting.

2. 

 Place pressure gauge tube over the 

fi

 tting.

3.

  Pressure can be adjusted by removing cap (B) using a  

fl

 at screwdriver, and adjusting the nylon plug with the same 

screw driver.
Turning the plug in (clockwise) will increase the pressure.

FIGURE 23

FIGURE 22

Содержание TORCH GT8N

Страница 1: ...losion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO I...

Страница 2: ...ected to a chimney flue pipe serving a separate solid fuel burning appliance Do not use this fireplace if any part has been under water Immediately call a qualified service technician to inspect the f...

Страница 3: ...louring caused by excessive heat abrasive and chemical cleaners nor chipping on porcelain enamel parts mechanical breakage of PHAZER logs and embers nor any venting components used in the installation...

Страница 4: ...ace shall be installed on a metal or wood panel extending the full width and depth Purge all gas lines with the glass door of the fireplace open Assure that a continuous gas flow is at the burner befo...

Страница 5: ...conjunction with the GD178 wall terminal kit use either the 5 foot vent kit GDT5 or the 10 foot vent kit GDT10 These kits allow for extended horizontal venting of the fireplace The maximum allowable v...

Страница 6: ...6 W415 0619 A 08 09 07 N B B G A F C H H L K J M FIGURE 3...

Страница 7: ...inished wall surface Apply a heavy bead of the high temperature sealant Slip the vent pipe a minimum of 2 over the inner sleeve of the air terminal and secure with 3 8 screws 3 Using the 5 diameter fl...

Страница 8: ...l sheetrock as you would finish any other outside wall of a home This will ensure that clearance to combustibles is maintained within the cavity Proceed once the vent installation is complete Note All...

Страница 9: ...ed This fireplace must be electrically connected and grounded in accordance with local codes In the absence of local codes use the current CSAC22 1 CANADIAN ELECTRICAL CODE in Canada or the ANSI NFPA...

Страница 10: ...he top edge of the door clears the front of the fireplace Next gripping the sides of the door lift the door out from the retainer along the bottom of the door DOOR REMOVAL FINISHING FIGURE 16 GLASS RE...

Страница 11: ...plier s instructions If you cannot reach your gas supplier call the fire department 1 STOP Read the safety information located above 2 Turn off all electric power to the fireplace 3 This fireplace is...

Страница 12: ...ear and free of combustible materials gasoline or other flammable vapours and liquids The flow of combustion and ventilation air must not be obstructed 1 Keep the control compartment burner and air sh...

Страница 13: ...32 W175 0271 COUPLER KIT Contact your dealer for questions concerning prices and availability of replacement parts Normally all parts can be ordered through your Napoleon dealer or distributor When or...

Страница 14: ...Check that both 3 and 5 vent liners are free of holes and well sealed at all joints Check that the minimum rise per foot has been adhered to for any horizontal venting White grey film forms Sulphur f...

Страница 15: ...15 W415 0619 A 08 09 07 Fireplace Service History This fireplace must be serviced annually depending on usage DATE DEALER NAME SERVICE TECHNICIAN NAME SERVICE PERFORMANCE SPECIAL CONCERNS...

Страница 16: ...16 W415 0619 A 08 09 07 NOTES...

Отзывы: