W415-0769 / A / 12.10.10
SYMPTOM
PROBLEM
TEST SOLUTION
Pilot goes out
while standing:
Main burner is in
“OFF” position.
Gas piping is undersized.
-
Turn on all gas appliances and see if pilot
fl
ame
fl
utters, diminishes or extinguishes, especially
when main burner ignites. Monitor appliance supply
working pressure.
-
Check if supply piping size is to code. Correct all
undersized piping.
Remote wall
switch is in “OFF”
position; main
burner comes on
when gas knob
is turned to “ON”
position.
Wall switch is mounted
upside down.
-
Reverse.
Remote wall switch is
grounding.
-
Replace.
Remote wall switch wire
is grounding.
-
Check for ground (short); repair ground or replace
wire.
Faulty valve.
-
Replace.