29
W415-0769 / A / 12.10.10
* See “VENTING” section.
5.2 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES
IMPORTANT: The GD82 requires a minimum inside enclosure height of 72”, measured from the bottom
of the appliance. For temperature requirements, this area must be left unobstructed.
2”
2”
72”
26”
8”
56”
MINIMUM
PLUS RISE*
COMBUSTIBLE NON-COMBUSTIBLE
BRICK
1”
COMBUSTIBLE
NON-
COMBUSTIBLE
0” IF NON-
COMBUSTIBLE
FINISHING IS
USED SUCH AS
BRICK AND
STONE
12 1/4”
INSULATION
SLEEVE
2”
!
WARNING
RISK OF FIRE!
THE FRONT OF THE APPLIANCE MUST BE FINISHED WITH ANY NON-COMBUSTIBLE MATERIALS
SUCH AS BRICK, MARBLE, GRANITE, ETC., AS LONG AS THE FINISHING MATERIAL DOES NOT GO
BELOW THE SPECIFIED DIMENSION AS ILLUSTRATED. AS AN ALTERNATIVE, YOU CAN FINISH THE
APPLIANCE WITH DRYWALL, SEE DIAGRAM BELOW FOR DETAILS.
FACING AND / OR FINISHING MATERIAL MUST NEVER OVERHANG INTO THE APPLIANCE
OPENING.
THE APPLIANCE REQUIRES A MINIMUM ENCLOSURE HEIGHT MEASURED FROM THE APPLIANCE
BASE.
Содержание Park Avenue GD82NT-PA
Страница 55: ...55 W415 0769 A 12 10 10 43 1 15 0 SERVICE HISTORY ...
Страница 56: ...56 W415 0769 A 12 10 10 16 0 NOTES 44 1 ...