Napoleon NZ-26 Скачать руководство пользователя страница 9

W415-0585 / B / 11.28.06

9

Napoleon models NZ-26  & NZ-26WI have the option of taking 

outside air directly into the fireplace through the opening on 

the left hand side or taking inside air through the lower front 

louvres or a combination of both. 
If the optional fresh air kit (available through your Napoleon 

/ Wolf Steel Ltd. dealer) is installed, it must not draw air from 

the attic or garage. It may only come from outside the house. 

The maximum length of the 4 inch air duct is 20 feet; thereafter 

enlarge the duct to a 6 inch diameter.
Decide on the most convenient location for the fresh air inlet 

duct and hood which may be installed above or below floor 

level.
Make a 5 inch hole in an outside wall of the house. From 

outside,  place  the  fresh  air  hood  into  the  hole,  open  side 

down.
At each end, carefully pull back the insulation sleeve expos-

ing the flexible duct. Place the insulated flexible duct over the 

fresh air hood and over the fireplace outside air connector. 

Carefully push the insulation sleeve back over the duct. us-

ing the clamps, fasten the insulated duct into place on both 

sides

.

 

Figure 9.

For outside air only, re-install the inside air cover plate, shown 

in 

Figure 37

, to cover the control box inside air opening. 

See 

Section on Combustion Air Control.

figure 9

OUTSIDE COMBUSTION AIR

MANTLE CLEARANCES

hEARTh EXTENSION

 

A  chimney  venting  the  fireplace  shall  not  vent  any 

other appliance.

The minimum overall chimney height from the top of 

the fireplace is 11 feet.

The maximum overall chimney height from the top of 

the fireplace is 34 feet.

Factory-built  chimney  systems  for  use  in  dwellings 

constructed for three or more families must be enclosed 

above the room in which the fireplace is located. This 

enclosure must have a fire resistance rating equal to or 

greater than that of the floor or roof assembly through 

which they pass.
If the chimney system is enclosed within the attic area, 

a rafter radiation shield is required.
The chimney should not be built with an offset angle in 

excess of 45° in Canada and 0° in uSA.

ChIMNEY INSTALLATION

The chimney must extend at least  feet above its point 

of contact with the roof and at least 2 feet higher than 

any wall, roof or building within 10 feet.
If the chimney extends more than 5 feet above the roof, 

it must be secured using a roof brace or guide wires.
Ensure that minimum clearances are maintained
Portions of the chimney that extend through accessible 

spaces  must  always  be  encased  to  avoid  personal 

contact with the chimney and thereby avoid damage 

to the chimney.
A raincap must be installed to avoid internal damage 

and corrosion.
The chimney must be supported at a maximum of 20 

foot intervals (approx. 200 lbs/20 ft).

The NZ-26 & NZ-26WI were tested to CAN/uLC S610 and uL 127 Factory Built Fireplace Standards. These Fireplaces have  

met the test criteria for Zero Clearance Installation to Combustible Surfaces and Certified to burn Firewood only.

Any 6" diameter chimney listed to these standards may be installed. In accordance with these standards, the unit may also 

be connected to any chimney listed to uLC-S629 for Canada or uL-10HT for the united States. 
Installation of all types of factory-built chimney systems is to be in accordance with the chimney manufacturers installation 

instructions. An appropriate chimney manufacturers anchor base plate and anchor base plate gasket is required in order 

to initiate the twist lock mechanism. use the high temperature gasket, supplied, to seal between the anchor plate and the 

fireplace top.

figure 10

An acceptable 16" x 50" non-combustible (ie: brick, stone 

or ceramic tile) hearth extension must be installed. Ensure 

that the gap between the fireplace and a factory-built hearth 

extension is sealed with sand/cement grout or covered with a 

metal strip (or both) to prevent sparks and embers from fall-

ing into this area. A raised hearth together with the fireplace 

built on a raised platform is recommended for easier wood 

loading and fire viewing.

Mantle  clearance 

can  vary  accord-

ing  to  the  mantle 

depth. 

Содержание NZ-26

Страница 1: ...exactly a fire or explosion may result causing property damage personal injury or death SOLID FUEL BURNING ZERO CLEARANCE Installation and operation instructions for Hi Tech listed fireplace THIS FIR...

Страница 2: ...W415 0585 B 11 28 06 WARNINGS SAFETY PRECAUTIONS...

Страница 3: ...emoval Procedures 17 Maintenance Gasket Baffle Replacement NZ 26 Door Glass Replacement NZ 26WI Door Glass Replacement Creosote Formation And Removal Run Away or Chimney Fire Fire Extinguishers and Sm...

Страница 4: ...urchaser the wholesale price of any warranted but defective part s After the first year napoleon will not be responsible for installation labour or any other costs or expenses related to the reinstall...

Страница 5: ...discol oration to the gold plated door internal damage to the fireplace or a house and or chimney fire All venting connections must be in compliance with the chimney manufacturers installation instru...

Страница 6: ...ating system for this application use the NZ62CH This option may not be used in mobile homes No more than two hot air gravity vents can be installed to fireplace Individual vent runs are not to exceed...

Страница 7: ...d insulation or vapour bar rier coming in contact with the fireplace body it is recommended that the walls of the fireplace enclosure be finished ie drywall sheetrock as you would finish any other out...

Страница 8: ...nts figure 7c Finishing Requirements Note In order to avoid the possibility of exposed insulation or vapour bar rier coming in contact with the fireplace body it is recommended that the walls of the f...

Страница 9: ...diation shield is required The chimney should not be built with an offset angle in excess of 45 in Canada and 30 in USA CHIMNEY INSTALLATION The chimney must extend at least 3 feet above its point of...

Страница 10: ...wo 15 30 or 45 elbows Minimum overall chimney height is 11 feet Double off set with four 15 30 or 45 elbows Minimum overall chimney height is 11 feet The first flue offset closest to the top of the un...

Страница 11: ...e flashing giving a 3 4 margin all around Fasten to the roof on the top and sides do not nail through the lower portion of the flashing Make weather tight by sealing with caulking Where possible cover...

Страница 12: ...removals the bottom flame spreader must be taped to the top spreader to ease top brick and baffle removal and to avoid damaging the fibre baffles 1 1 2 gasket rope location rear bricks Unscrew and re...

Страница 13: ...lace chimney and the surrounding enclosure top flame spreader bottom flame spreader fibre baffle 1 of 2 shown top firebrick 1 of 2 shown 3a 3b baffle support bracket figures 29 figures 30 figures 32 I...

Страница 14: ...blower single blower installation to be done by a qualified installer and must be electrically connected and grounded in accordance with local codes In the absence of local codes use the current CSA C...

Страница 15: ...through the chimney The amount of draft in your chimney depends on the length of the chimney local geography nearby obstruc tions and other forces Adjusting the draft control regulates the temperatur...

Страница 16: ...l occurrence and does not pose a safety hazard The paint may also smell a little for the first few fires as it cures and you may wish to open a door or window to alleviate the smell To start a brisk f...

Страница 17: ...ce with 1 2 fibreglass rope if necessary To remove the door open and lift out remove the screws and brackets holding the glass in place Remove all broken glass Wrap the edges of the new glass with a U...

Страница 18: ...not illustrated for further information contact your napoleon dealer REPLACEMENTS PART No DESCRIPTION 33 111kt outside air kit 34 NZ 690kt thermostatic air control kit 35 NZ 62 CH central heating kit...

Страница 19: ...W415 0585 B 11 28 06 19...

Страница 20: ...ly drawn into the chimney there may be a downdraft or cold air in the chimney Roll up some newspaper light it and place it near the fireplace flue until the chimney begins to draw During a firing open...

Страница 21: ...W415 0585 B 11 28 06 21 Wolf Steel Fireplace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name...

Страница 22: ...W415 0585 B 11 28 06 22 NOTES...

Отзывы: