W415-1068 / B / 01.02.14
29
EN
* Within the appliance enclosure a 7” (178mm) clearance between the top of the vent pipe and combustible
materials is required. All other clearances within the enclosure, including where the vent pipe exits the
enclosure are subject to 2” (51mm) to the sides and bottom and 3” (76mm) to the top for horizontal and 1”
(25mm) for vertical.
** See venting section.
IMPORTANT:
THE FIRESTOP ASSEMBLY PROVIDED MUST BE USED WHEN THE VENT PIPES PASS
THROUGH ANY WALL OR ARE TERMINATED HORIZONTALLY.
TOP OF
APPLIANCE
OPENING
COMBUSTIBLE
NON-COMBUSTIBLE
TOP OF ENCLOSURE
(COMBUSTIBLE)
84” (2134mm)
MINIMUM
PLUS RISE **
28”
(711mm)
MINIMUM
68”
(1727mm)
MINIMUM
CEILING
96”
(2438mm)
MINIMUM
ENCLOSURE
HEIGHT
STEEL
STUD
FRAME
0” (0m) IF NON-
COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK
AND STONE.
3”
(76mm)
2” (51mm)
MINIMUM 7”
(178mm)
FIRESTOP
ASSEMBLY
NON-COMBUSTIBLE
3”
(76mm)