SYMPTOM
PROBLEM
TEST SOLUTION
Main burner goes out; pilot
stays on.
Venting is spilling.
-
Test with spill switch bypassed.
-
Check for vent blockage.
GS28
SYMPTOM
PROBLEM
TEST SOLUTION
Main burner goes out; pilot
goes out.
Vent re-circulating.
-
Check joint seals and installation.
Main burner
fl
ame is a
blue, lazy, transparent
fl
ame.
Blockage in vent.
-
Remove blockage. In really cold conditions, ice buildup
may occur on the terminal and should be removed as
required.
Incorrect installation.
-
Ensure vent con
fi
guration is within prescribed venting
parameters
GDS28
SYMPTOM
PROBLEM
TEST SOLUTION
Door Sticking
Dirt / dust adheres to the hinges;
is heated and burns causing
sticking.
-
Lift door from its hinges. Lubricate with high temp dry
graphite only. Replace.
-
NOTE: Due to the high temperatures that the hinges
experience, wet lubricants such as oil and WD40 will
cause the hinge to seize and are therefore not suitable.
Main burner goes out; pilot
goes out.
Thermocouple shorting or faulty.
-
Loosen and tighten thermocouple.
-
Clean thermocouple and valve connection.
-
Replace thermocouple.