10
W415-0810 / 06.11.09
2.4 ELECTRICAL
CONNECTION
!
WARNING
DO NOT USE THIS HEATER IF ANY PART HAS BEEN UNDER WATER. CALL A QUALIFIED SERVICE
TECHNICIAN IMMEDIATELY TO HAVE THE APPLIANCE INSPECTED FOR DAMAGE TO THE
ELECTRICAL CIRCUIT.
RISK OF ELECTRICAL SHOCK OR EXPLOSION. DO NOT WIRE 110V TO THE VALVE OR TO THE
APPLIANCE WALL SWITCH. INCORRECT WIRING WILL DAMAGE CONTROLS.
ALL WIRING SHOULD BE DONE BY A QUALIFIED ELECTRICIAN AND SHALL BE IN COMPLIANCE
WITH LOCAL CODES. IN THE ABSENCE OF LOCAL CODES, USE THE CURRENT CSA22.1
CANADIAN ELECTRIC CODE IN CANADA OR THE CURRENT NATIONAL ELECTRIC CODE
ANSI/NFPA NO. 70 IN THE UNITED STATES.
For ease of accessibility, an optional remote wall switch or millivolt thermostat may be installed in a convenient
location. Route a 2 strand, solid core millivolt wire from the valve to the wall switch or millivolt thermostat. The
recommended maximum lead length depends on wire size:
WIRE SIZE
MAX. LENGTH
14
gauge
100
feet
16 gauge
60 feet
18 gauge
40 feet
Disconnect the existing wires from terminals 1 and 3 (from the
ON/OFF switch) and replace with the leads from the wall switch / millivolt thermostat.
50.1
P
I
P ILOT
3
1
2
N
O
L
O
T
H I
L O
FF
O
2.5 RATING
PLATE
WARNING: FIREPLACE SCREENS MUST BE CLOSED WHILE IN OPERATION.
DO NOT ADD ANY MATERIAL TO THE APPLIANCE, WHICH WILL COME IN
CONTACT WITH THE FLAMES, OTHER THAN THAT SUPPLIED BY THE MANUFACTURER WITH THE APPLIANCE. DO NOT USE BLOWER INSERT, HEAT EXCHANGER INSERT OR OTHER
ACCESSORIES NOT APPROVED FOR USE WITH THIS HEATER. IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTAINANCE CAN CAUSE PROPERTY DAMAGE,
PERSONAL INJURY OR LOSS OF LIFE. REFER TO THE OWNER'S INFORMATION MANUAL PROVIDED WITH THIS APPLIANCE. INSTALLATION AND SERVICE MUST BE PERFORMED BY A
QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
W385-0254
MADE IN CANADA
WOLF STEEL LTD, BARRIE, ON, CANADA
SERIAL NUMBER:
GVF40 / CVF400
*
MAXIMUM HORIZONTAL EXTENSION: 2". SEE INSTRUCTION
MANUAL FOR GREATER EXTENSIONS.
ELECTRICAL RATING: 115V 0.82AMP, 60HZ
OPTIONAL FAN KIT: GZ550-KT
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS:
TOP / SIDES / BACK / FLOOR
0
RECESSED DEPTH
25¼"
MANTLE
5"
*
CERTIFIED UNDER: ANSI Z21.11.2-2000 VOLUME II, UNVENTED ROOM HEATER
CERTIFIED FOR USA
ALTITUDE
INPUT
REDUCED INPUT
ORIFICE
MANIFOLD PRESSURE:
10" WATER COLUMN
MINIMUM SUPPLY PRESSURE:
11" WATER COLUMN
MAXIMUM SUPPLY PRESSURE:
13" WATER COLUMN
SIT CONTROL:
#820636
OPERATING PILOT OXYPROTECTOR:
#8404
MANIFOLD PRESSURE:
3.5" WATER COLUMN
MINIMUM SUPPLY PRESSURE:
4.5" WATER COLUMN
MAXIMUM SUPPLY PRESSURE:
7.0" WATER COLUMN
SIT CONTROL:
#820637
OPERATING PILOT OXYPROTECTOR:
# 8214
**
ABOVE 2,000FT, CONSULT LOCAL AUTHORITY HAVING JURISDICTION
NOT FOR USE WITH SOLID FUEL.
**
0-2000FT (0-610m)
30,000 BTU/h
20,000BTU/h
#39
0-2000FT (0-610m)
**
28,500 BTU/h
22,000BTU/h
#53
GVF40-N / CVF400-N
MODEL
GVF40-P / CVF400-P
MODEL
THIS APPLIANCE MAY BE INSTALLED IN AN AFTERMARKET,
PERMANENTLY LOCATED, MANUFACTURED (MOBILE) HOME, WHERE
NOT PROHIBITED BY LOCAL CODES. THIS APPLIANCE IS ONLY FOR USE
WITH THE TYPE OF GAS INDICATED ON THE RATING PLATE. THIS
APPLIANCE IS NOT CONVERTIBLE FOR USE WITH OTHER GASES.
THIS IS A GAS-FIRED UNVENTED ROOM HEATER THAT REQUIRES AD-
EQUATE COMBUSTION AND VENTILATION AIR. THIS UNIT IS
NOT
APPROVED
FOR BEDROOM, BATHROOM AND BED-SITTING ROOM INSTALLATION.
REFERENCE # W/N 15515
For rating plate location, see “DIMENSIONS” section.