general information

1.2 

rates and effi ciencies

1.3 

general instructions

For your satisfaction, this appliance has been test-fi red to assure its operation and quality!

RATES AND EFFICIENCIES

NG

P

Altitude (FT)

0-4,500

Max. Input (BTU/HR)

65,000

Min. Inlet Gas Supply Pressure

4.5" (11mb) w.c.

11" (27mb) w.c.

Max. Inlet Gas Supply Pressure

7" * (17mb) w.c.

13" (32mb) w.c.

Manifold Pressure (Under Flow Conditions)

3.5" (9mb) w.c.

10" (25mb) w.c.

•  Never obstruct the front opening of the appliance.

•  Objects placed in front of the appliance must be kept a minimum of 48” (121.9cm) from the front face of the 

appliance.

•  Fire risk. Explosion hazard.

•  High pressure will damage valve. Disconnect gas supply piping before pressure testing gas line at test 

pressures about 1/2 PSIG. Close the manual shut-off valve before pressure testing gas line at pressures equal 

to or less than 1/2 PSIG (35mb).

•  Use only Wolf Steel approved optional accessories and replacement parts with this appliance. Using non-

listed accessories (blowers, doors, louvres, trims, gas components, venting components, etc.) could result in 

a safety hazard and will void the warranty and certifi cation.

THIS GAS APPLIANCE SHOULD BE INSTALLED AND 
SERVICED BY A QUALIFIED INSTALLER

 to conform with 

local codes. Installation practices vary from region to region 
and  it is important to know the specifi cs that apply to your 
area, for example in Massachusetts State:
•  The appliance off valve must be a “T” handle gas cock.
•  The fl exible connector must not be longer than 36” 

(91.4cm).

 The installation must conform with local codes or, in absence 
of local codes, the National Gas and Propane Installation Code CSA B149.1 in Canada, or the National Fuel Gas 
Code, ANSI Z223.1 / NFPA 54 in the United States.
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during 
any pressure testing of that system at test pressures in excess of 1/2 psig (35 mb). The appliance must be 
isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure 
testing of the gas supply piping  system at test pressures equal to or less than 1/2 psig (35 mb). When installed 
with a blower or fan, the junction box must be electrically connected and grounded in accordance with local 
codes. In the absence of local codes, use the current CSA C22.1 Canadian Electrical Code in Canada or the 
ANSI / NFPA 70 National Electric Code in the United States. In the case where the blower is equipped with 
a power cord it must be connected into a properly grounded receptacle. The grounding prong must not be 
removed from the cord plug.

When the appliance is installed directly on combustible material other than wood fl ooring, the appliance shall be 
installed on a metal or wood panel extending the full width and depth.

Solid fuels shall not be burned in this appliance.

* Maximum inlet pressure not to exceed 13”.

Содержание GSS42CFN

Страница 1: ...se any phone in your building Immediately call your gas supplier from a neigh bour s phone Follow the gas supplier s instruc tions If you cannot reach your gas supplier call the re department Failure...

Страница 2: ...W415 2975 09 02 21 EN 2 safety information...

Страница 3: ...d be carefully supervised when they are in the same room as the appliance Toddlers young children and others may be susceptible to accidental contact burns A physical barrier is recommended if there a...

Страница 4: ...tible materials to overheat and catch re Carbon monoxide poisoning may lead to death early signs of carbon monoxide poisoning resemble the u with headache dizziness and or nausea If you have these sig...

Страница 5: ...1 log placement 17 8 2 glowing embers optional 18 8 3 charcoal lumps lava rock 18 8 4 optional front installation 18 8 5 logo placement 19 8 6 minimum mantel clearances 19 9 0 optional remote installa...

Страница 6: ...sure opening when not in use This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certi ed kit is used...

Страница 7: ...t apply to your area for example in Massachusetts State The appliance off valve must be a T handle gas cock The exible connector must not be longer than 36 91 4cm The installation must conform with lo...

Страница 8: ...n 1 4 rating plate information 1 5 dimensions This illustration is for reference only Refer to the rating plate on the appliance for accurate information note The rating plate must remain with the app...

Страница 9: ...able Any enclosure shelter in which the appliance is used must comply with one of the following With walls on all sides but at least one permanent opening at ground level and no overhead cover Fig 1 2...

Страница 10: ...terials in a vertical tube furnace at 1382 F 750 C and UL763 shall be considered non combustible materials Minimum clearance to combusibles must be maintained or a serious re hazard could result The a...

Страница 11: ...for the top and two steel studs on the sides Finishing 1 25mm to back and sides Non combustible nishing 18 45 7cm to top 4 102mm to sides of appliance opening Non combustible nishing material ie cemen...

Страница 12: ...N 12 framing 3 3 minimum enclosure clearances This appliance requires a minimum enclosure height of 58 1 2 148 6cm For temperature requirements the enclosure space around and above the appliance must...

Страница 13: ...op of appliance An outdoor sealant must be used along the edge of the appliance and the non combustible material to keep water from entering the chase Use only non combustible material such as cement...

Страница 14: ...r before closing the door Ensure adequate ventilation For gas and electrical locations see dimensions section All gas connections must be contained within the appliance when complete High pressure wil...

Страница 15: ...peat steps E through I J With pilot lit turn gas knob counter clockwise to the ON position K If equipped with the ame adjustment valve push and turn the knob to high L Turn on all electrical power to...

Страница 16: ...face position the framework to accommodate the thickness of the nished surface Bend out the six nailing tabs attached on top and on either side of the appliance and secure to the 2x4 framing The tabs...

Страница 17: ...ers for a maximum glowing effect Log colours may vary During the initial use of the appliance the colours will become more uniform as colour pigments burn in during the heat activated curing process 8...

Страница 18: ...ts can cause an incorrect ame pattern carbon deposits and delayed ignition PHAZER logs glow when exposed to direct ame Use only certi ed glowing embers and PHAZER logs available from your local author...

Страница 19: ...7mm in from the left side as shown Risk of re Maintain speci ed air space clearances to combustibles Failure to comply with these instructions may cause a re or cause the appliance to overheat Ensure...

Страница 20: ...h batteries installed through the opening in the faceplate and into the receiver The battery pack is secured and released with a catch mechanism Push the receiver into the catch to secure D Insert the...

Страница 21: ...2 21 21 10 0 adjustment 10 1 venturi adjustment 10 2 ame characteristics VENTURI ADJUSTMENT CHART NG 1 8 3 2mm P 1 4 6 4mm Carbon can be distributed in surrounding living area if the air shutter is im...

Страница 22: ...iquids The ow of combustion and ventilation air must not be obstructed 1 In order to properly clean the burner and pilot assembly remove the logs rocks and or glass to ex pose both assemblies 2 Keep t...

Страница 23: ...replacement parts a photocopy of the original invoice will be required to honour the claim When ordering replacement parts always give the following information Model Serial Number of appliance Instal...

Страница 24: ...W415 2975 09 02 21 EN 24 replacement parts...

Страница 25: ...EN W415 2975 09 02 21 25 13 0 accessories...

Страница 26: ...MLY TO RESEAL DO NOT OVER TORQUE Leak test with a soap and water solution Air shutter improperly adjusted Return air shutter to speci ed opening see venturi adjustment section C a rb o nisb ein g d e...

Страница 27: ...faulty Loosen and tighten thermocouple Clean thermocouple and valve connection Replace thermocouple Replace valve Faulty valve Replace Pilot burning no gas to main burner gas knob is on HI wall switch...

Страница 28: ...ty does not cover damages resulting from the use of components not supplied with the appliance or the use of fuel other than those speci ed Any damages to appliance due to weather long periods of damp...

Страница 29: ...EN W415 2975 09 02 21 29 16 0 service history...

Страница 30: ......

Страница 31: ...uble Appelez imm diatement votre fournisseur de gaz d un t l phone voisin Suivez ses instructions Si vous ne pouvez pas rejoindre votre fournisseur de gaz appelez le service des incendies Le non respe...

Страница 32: ...W415 2975 09 02 21 32 FR consignes de s curit...

Страница 33: ...enflamment Les jeunes enfants doivent tre surveill s attentivement lorsqu ils sont dans la m me pi ce que l appareil Les jeunes enfants et autres personnes risque sont sujets aux br lures accidentelle...

Страница 34: ...g ne sd u neinto xic a tio n a um o n o xyd ed eca rb o n eresse m b le nt lag rip p e a vecc p h al e s ve rtig e se t o ud esn au s e s S i vo us p r se ntezc e ssig n e s l ap p are il p eu t n ep...

Страница 35: ...1 installation de l interrupteur mural optionnel 44 5 0 installation du gaz 44 6 0 fonctionnement 45 7 0 supports de fixation 46 8 0 finitions 47 8 1 disposition des b ches 47 8 2 braises incandescen...

Страница 36: ...est con u pour fonctionner avec le type de combustible indiqu sur la plaque d homologation Cet appareil ne peut tre converti un autre type de combustible moins d utiliser un ensemble de conversion ce...

Страница 37: ...se prolongeant sur toute la largeur et la profondeur Les combustible solides ne doivent pas tre br l s dans cet appareil CET APPAREIL AU GAZ DEVRAIT TRE INSTALL ET ENTRETENU PAR UN INSTALLATEUR QUALI...

Страница 38: ...sur la plaque d homologation Cette illustration est titre de r f rence seulement Consultez la plaque d homologation pour obtenir l information pr cise NOTE La plaque d homologation doit rester avec l...

Страница 39: ...TE Lorsque vous choisissez un emplacement pour votre l appareil prenez soin d viter les endroits trop humides ou proximit de sources d eau courantes Toute enceinte abri dans laquelle l appareil est ut...

Страница 40: ...s mat riaux dans une fournaise avec tube vertical 1382 F 750 C et la norme UL763 sont consid r s comme tant des mat riaux non combustibles A n d viter un risque d incendie les d gagements minimaux aux...

Страница 41: ...re et sur les c t s Ossature incombustible 18 45 7cm du dessus 4 102mm sur les c t s de l ouverture de l appareil Des mat riaux de nition incombustibles p ex panneau de ciment brique pierre tuile peuv...

Страница 42: ...s minimaux de l enceinte L enceinte de l appareil doit avoir une hauteur minimale de 58 1 2 148 6cm A n de respecter les contraintes de temp rature l espace l int rieur de l enceinte autour de l appar...

Страница 43: ...us devez appliquer un scellant pour l ext rieur tout autour de l appareil et le long des mat riaux incombustibles Lorsque vous faites la nition jusqu l appareil n utilisez qu un mat riau incombustible...

Страница 44: ...3 8 9 5mm L appareil est muni d une soupape d arr t manuelle pour fermer l alimentation en gaz Branchez le gaz en conformit avec les codes locaux En l absence de codes locaux l installation doit tre c...

Страница 45: ...a n t u n em in u te p u isre l c h e z le S i lave ille u sen ere s tep a sa llu m e r p te zle s ta p e sE I J L o rsq u elav e ille u s ee s t a llu m e e n fo n c e ze t to u rn e zleb o u to nd...

Страница 46: ...tants d ossature de fa on pr voir l paisseur de la surface nie D pliez les six supports de xation qui se trouvent sur le dessus et de chaque c t de l appareil et xez les aux 2x4 Les supports de xation...

Страница 47: ...vous de positionner la b che de fa on ce que son encoche d gage bien les ori ces du br leur C Placez l extr mit de la b che crois W135 0672 droite du noeud de b che A La fourche de la b che devrait co...

Страница 48: ...r les ori ces du br leur Le blocage des ori ces du br leur peut cr er une amme irr guli re des d p ts de carbone et un retard d allumage Les b ches PHAZERMD rougeoient lorsqu elles sont expos es une a...

Страница 49: ...rvez tous les d gagements aux mat riaux combustibles sp ci s Incapacit de se conformer ces instructions peut causer un incendie ou une surchauffe Assurez vous que tous les d gagements arri re c t s de...

Страница 50: ...le bloc de batteries dans l ouverture de la plaque puis glissez le dans le r cepteur La bo te de batteries est retenu en place par un m canisme de loquet Pour xer le bloc de batteries poussez le dans...

Страница 51: ...ons FR 10 0 r glages 10 1 r glage du venturi 10 2 caract ristiques de la amme R GLAGE DU VENTURI GN 1 8 3 2mm P 1 4 6 4mm Du carbone peut se d poser dans des endroits de s jour avoisinants si le volet...

Страница 52: ...re 7 Remettez en place les b ches les roches ou la vitre nettoy es si quip Omettre de positionner les composants d coratifs ad quatement peut causer des d pots de carbone qui peuvent se d poser l int...

Страница 53: ...es pi ces peuvent tre command es chez votre d taillant autoris Pour un remplacement de pi ce sous garantie une photocopie de la facture originale sera requise a n de pouvoir honorer la demande Lorsque...

Страница 54: ...W415 2975 09 02 21 54 FR pi ces de rechange...

Страница 55: ...W415 2975 09 02 21 55 pi ces de rechange FR 13 0 accessoires...

Страница 56: ...rincipal le bouton du gaz est HI l interrupteur mural thermostat est ON Le thermostat ou l interrupteur sont d fectueux Reliez un l de d rivation entre les bornes de l interrupteur mural si le br leur...

Страница 57: ...iquant une solution d eau savonneuse Du carbone se d pose sur les b ches ou les parois de la chambre de combustion Le volet d air est bloqu Assurez vous que l ouverture du volet d air n est pas bloqu...

Страница 58: ...il par les intemp ries de longues p riodes d humidit la condensation les produits chimiques ou produits d entretien nuisibles ne seront pas la responsabilit de NAPOL ON La facture ou sa copie sera req...

Страница 59: ...W415 2975 09 02 21 59 pi ces de rechange FR 16 0 historique d entretien...

Страница 60: ......

Отзывы: