FIGURE 7

FIGURE 8

This is a thermally activated switch, attached to the back of
the unit and extending up into the dilution draft hood, which
senses the change in temperature and shuts down the
gas valve in the event of a severe downdraft of air or a
blocked or disconnected vent. It acts as a safety shutoff to
prevent a build up of carbon monoxide or an explosion of
unburnt gases during start up. If the flue is blocked or has
no "draw", the spill switch will automatically shut off the
supply of gas within about 5-10 minutes.

TAMPERING WITH THE SWITCH CAN RESULT IN
CARBON MONOXIDE (CO) POISONING AND POS-
SIBLE DEATH.

 

A check for correct venting action must be made be-

fore the installed insert is left with the customer.

Test after installing the unit into either the GI-700 ZERO
CLEARANCE KIT
 or a vented noncombustible fireplace in
the following manner:

1.  Close all doors and windows in the room / start exhaust
fans in the home / turn fireplace blower off.

2.  Set controls to "high" and light the unit.

3.  Wait 5 minutes. Light a match and hold it to the spill tube
opening.

4.  Venting action is satisfactory if smoke is drawn into the
spill tube. Venting action is unsatisfactory if the flame and
smoke are not drawn into the tube.

5.  If venting action is unsatisfactory, turn the unit off, wait

10 minutes and try again. If the smoke or flame is still not
drawn into the spill tube, turn the unit off and check for
adequate fresh air supply, vent blockage or restriction. If
necessary, consult with a qualified inspector.

SPILL  SWITCH

VENTING  ACTION  CHECK

Levelling the insert will eliminate rocking or excessive noise
when the fan is in operation. Replace the securing screw
to the front of the dilution plate.

Install rigid black pipe, a flex connector, if local codes per-
mit
, or 1/2" type L, copper tubing with a 3/8" to 1/2" adapter
and a shut off valve to the fireplace. Seal and tighten se-
curely. The adapter will be required between the gas valve
and the copper tubing or flex connector.

Do not damage or kink flex connector!

Check for gas leaks by brushing on a soap and water solu-
tion.

Do not use open flame!

An on/off switch has been included and can be located at
the lower right, behind the louvre access door or at the right
side trim.

For ease of accessibility, this switch may be replaced with
a wall switch or substituted with a millivolt thermostat that
may be installed in a convenient location on any wall. Route
2-strand (solid core) millivolt wire through the electrical
hole located at the bottom right side of the unit. The recom-
mended maximum lead length depends on wire size:

WIRE SIZE

MAX. LENGTH

14gauge

100 feet

16gauge

60 feet

18gauge

40 feet

Attach the two leads to terminals 1 and 3 located on the
gas valve.

Do not connect either the wall switch or the gas valve to
electricity (110 volts or 24 volts).

FIGURE 5

FIGURE 6

1

2

3

Содержание GI3016-N

Страница 1: ...e vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas sup plier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified ins...

Страница 2: ... vapours and liquids Do not use this fireplace if any part has been under water Immediately call a qualified service techni cian to inspect the fireplace and to replace any part of the control system and any gas control which has been under water Under no circumstances should this fireplace be modified Do not burn wood or other materials in this fire place Adults and especially children should be ...

Страница 3: ...uires the prior approval of an authorized company official Labour costs to the account of to the account of to the account of to the account of to the account of NAPOLEON NAPOLEON NAPOLEON NAPOLEON NAPOLEON are based on a predetermined rate schedule and any repair are based on a predetermined rate schedule and any repair are based on a predetermined rate schedule and any repair are based on a pred...

Страница 4: ... log The appliance off valve must be a T handle gas cock The flexible connector must not be longer than 36 inches The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product WARNING This product must be installed by a licensed plumber or gas fitter when installed within the commonwealth of Massachusetts In absence of local code...

Страница 5: ... non combustible materials If necessary have any repair work done by a qualified person before installing the in sert Remove the existing fireplace damper or lock into an open position Using screws attach the fireplace warning tag W385 0199 to the inside of the firebox of the fireplace into which the insert is being installed The sheet metal parts of the fireplace in which the gas fireplace insert...

Страница 6: ...y again If the smoke or flame is still not drawn into the spill tube turn the unit off and check for adequate fresh air supply vent blockage or restriction If necessary consult with a qualified inspector SPILL SWITCH VENTING ACTION CHECK Levelling the insert will eliminate rocking or excessive noise when the fan is in operation Replace the securing screw to the front of the dilution plate Install ...

Страница 7: ...harcoal embers available from your Napoleon dealer 1 Place the front log onto the main burner pushing it as close as possible to the burner ports without blocking covering them The left and right spacing between the log ends and the burner ports should be equal 2 Place the back log onto the log support brackets located on the rear wall of the combustion chamber The notch situated at the lower left...

Страница 8: ...king of the logo supplied and place on the glass viewing area as indicated LOWER GLASS BRACKET LOGO 11 8 13 8 SECURING SCREW LOCATIONS LOGO PLACEMENT FLUSH GLASS FRONT KIT GI FF FLASHING SURROUND KITS GI 900 GI 909 UPPER LOUVRES Insert the back edge of the upper louvre into the upper louvre clips LOWER LOUVRES Secure the lower louvre assembly to the insert using the 4 screws supplied FLUSH LOUVRE ...

Страница 9: ...re the bay to the insert front at the top and bottom outside corners using 4 screws Note Black louvre assembly if supplied must be installed as uppers due to the high fireplace temperature Assemble the flashing and mount to the inside of the outer shell using 4 securing screws and spacers supplied as shown Hook the ornamental inlays over the spacers Both these options may be attached to the insert...

Страница 10: ...r turn the gas control knob Never use tools If the knob will not push in or turn by hand do not try to repair it Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire de partment Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building 8 Depress and hol...

Страница 11: ...l automatically start approximately 15 minutes after lighting the fireplace and will run for approxi mately 30 minutes after the fireplace has been turned off Use of the fan increases the output of heat Air drawn in through the lower louvre access door is driven up the back of the firebox and exhausted as hot air between the upper louvres Turn off the gas and electric power to the unit Remove the ...

Страница 12: ...S C W LOWER DOOR TRIM 31 GIB OIG GOLD PLATED BAY ORNAMENTAL INSETS 32 GI 778KT BRICK PANEL KIT 33 W470 0002 ENAMEL TOUCH UP AND BRUSH SPECIFY COLOUR 34 GI 700KT ZERO CLEARANCE SHELL 35 111 KT OUTSIDE AIR KIT 36 W690 0001 MILLIVOLTTHERMOSTAT 37 W660 0011 REMOTE CONTROL ADVANTAGE PLUS 38 GD 660 WALL SWITCH 20FT WIRE 39 W500 0033 V S S MOUNTING PLATE FOR WALL SWITCH 40 GI 900AB6 ANTIQUE BRASS FLASHIN...

Страница 13: ...13 W415 0171 E 01 10 05 ...

Страница 14: ...hts replace the wall switch B Wall switch wiring is defec tive disconnect switch wires from valve and connect a jumper wire across terminals 1 and 3 if the main burner lights check the wires for defects and or replace wires C Main burner orifice is plugged remove stoppage in orifice D Remote gas valve operator is defective connect a jumper wire across terminals 1 and 3 if main burner does not ligh...

Страница 15: ...ed in room head aches check for chimney blockage check that chimney is installed to building code room is in negative pressure increase fresh air supply Fireplace is spilling A Wall switch is mounted up side down B Remote wall switch is grounding C Remote wall switch wire is grounding Remote wall switch is in off position main burner comes on when gas knob is turned to ON posi tion reverse replace...

Страница 16: ...16 W415 0171 E 01 10 05 Wolf Steel Fireplace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name ...

Отзывы: