Use the periscope kit to locate the air termination above grade. The periscope must be installed so that
when
fi
nal grading is completed, the bottom air slot is located a minimum 12” (304.8mm) above grade. The
maximum allowable vent length is 10’ (3.1m) for a
fi
replace and 8’ (2.4m) for a stove.
9.4A
24” (610mm)
MAXIMUM
0” (0mm) RISE
CORNER INSTALLATION
3.3 SPECIAL VENT INSTALLATIONS
29" (737mm) MINI-
MUM
12"
(305mm)
MIN. TO
GRADE
The maximum vent length for a corner installation is 24" (609.6mm).
24" (610mm)
MINIMUM
30 1/2" (775mm)
3.3.1 PERISCOPE TERMINATION
3.3.2 CORNER TERMINATION
12"
(305mm)
MIN. TO
GRADE